22
Regency GF900L-1 Gas Fireplace
installation
VERTICAL TERMINATIONS
RIGID PIPE 4" X 6-5/8
" (
102MM X 175MM)
The minimum components required for a basic vertical
termination using Simpson Duravent Rigid Flue System are:
1 Vertical Termination Cap
1 Rigid Pipe Adaptor (510-994)
1 Flashing
1 Storm Collar
1 Length of pipe to suit height requirement
(see chart)
When using Rigid Flue other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent. Use of these systems with the Rigid Pipe adaptor is deemed
acceptable and does not affect the Intertek WHI listing of components.
WARNING:
Do not combine venting components from different flueing systems.
However use of the the AstroCap
TM
and FPI Riser is acceptable with all systems.
The FPI AstroCap
TM
and Regency vertical Cowl are certified for installations using FPI flueing systems as well as Simpson Dura-Vent
®
Direct Vent, is a
proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson
Dura-Vent Co. Inc.
Galvanized pipe is desirable above the roofline due to its higher
corrosion resistance. Continue to add pipe sections through the
flashing until the height of the vent cap meets the minimum height
requirements specified in local codes. Note that for steep roof
pitches, the vertical height must be increased. A poor draft, or
down drafting can result from high wind conditions near big trees
or adjoining roof lines, in these cases, increasing the vent height
may solve the problem.
Pipe Length
Flashing
Rigid PipeA d a p t e r
High wind cap
(not supplied)
(Dura Vent Only)
Roof Pitch
Minimum Flue Height
Meters
flat to 7/12
0.61
over 7/12 to 8/12
0.61
over 8/12 to 9/12
0.61
over 9/12 to 10/12
0.76
over 10/12 to 11/12
0.99
over 11/12 to 12/12
1.22
over 12/12 to 14/12
1.52
over 14/12 to 16/12
1.83
over 16/12 to 18/12
2.13
over 18/12 to 20/12
2.29
over 20/12 to 21/12
2.44