City Series CV60E
|
51
installation
Venting Arrangement for Vertical Terminations
Vertical venting with straight vertical venting and or with a max. of two (2) 90
o
Elbows (1 - 90
o =
2 - 45
o
)
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
90
o
elbows, with Rigid Pipe Venting Systems.
• Two 45
o
elbows equal to one 90
o
elbow.
• Vent must be supported at offsets.
• Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the
"Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever
passing through a wall.
• Must use optional rigid pipe adaptor (Part# 770-994) when
using rigid pipe vent systems.
• Refer to the "Vent Restrictor Position" section for details on
how to change the vent restrictor from the factory setting
of Set 0 through to Set 3 if required.
Maximum: 36.39 ft.
(11.09m)
Minimum 87 5/16” (2.21m)
Min. 58-3/16” (1478mm)
*
Minimum length of pipe
between elbows 12” (305mm)
Maximum: 27.4 ft. (8.4m)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
Vertical Height (Feet)
32
34
36
38
6
8
Horizontal (Feet)
2
0
4
10
12
16
18
14
20
Vent Restrictor on Set 1
Vent Restrictor on Set 3
Factory Set no Restrictor
*