28
|
City Series CV60E
installation
Clearances
The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney-related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Flue Clearances to Combustibles
Horizontal - Top
3"
Horizontal - Side
2"
Horizontal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
firestop is used.
1-1/2"
Note: This appliance uses 5" x 8" venting.
28
|
City Series CV60E
installation
Clearances CV60E
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Clearance: single sided
Dimension
Measured From:
A1: :
Mantel Height (min.)
**
Top of Fireplace Opening
A: From Floor
10 1/4” (260 mm)"
Bottom of Fireplace Opening
B: Sidewall (on one side)
8" (203mm)
Side of Fireplace Opening
C: Enclosure width
65 11/16" (1668mm)
Side of Fireplace Opening
D: Mantel Depth (max.)
**
E: Alcove Width
109.5” (2781mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
35" (889mm)
Front to Unit (Maximum)
H: Convection Air Outlet
*180 square inches
G: Convection Air Outlet Opening Offset
*0-2" (0-51mm)
K: Minimum clearance to celing
1 3/4” (44 mm)
M: Clearance to Sprinkler Head (Min.)
36" (914mm)
Perpendicular
From back wall to chase front
from chase grill
Hearth
0"
hearth required
**
See mantel clearances chart in this manual.
Flue Clearances to Combustibles
Horizontal - Top
3"
Horizontal - Side
2"
Horizontal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
1-1/2"
Note: This appliance uses 5" x 8" venting.
Alcove
E
F
D
A1
B
A
J
G
H
L
*
A minimum of 180 square
inches of open area, not
lower than 0-2" from top of
enclosure, required for all
installations
Side view
M
Chase grill
Sprinkler
J: Opening Height
18" (457 mm)
Bottom/Top of Fireplace Opening
Top of chase to ceiling
20-5/16" (516mm)
I: Framing depth
From base of unit to ceiling
81 1/4" (2038 mm)
L: Ceiling height
Alcove
Clearance
Dimension
Measured From:
A1: Mantel Height (min.)
**
Top of Fireplace Opening
A: From Floor (min.)
10-1/4" (260 mm)
Bottom of fireplace opening
B: Sidewall (on one side) min.
8" (203 mm)
Side of fireplace opening
B1: Sidewall (on one side) min.
24" (610 mm)
Side air outlet to side wall (min.)
C: Enclosure Width (min.)
65-11/16" (1668 mm)
Side of fireplace opening
D: Mantel Depth (max.)
**
E: Alcove Width
109-1/2" (2781 mm)
Sidewall to sidewall (minimum)
F: Alcove Depth
35" (889 mm)
Front to unit (maximum)
G: Convection Air Outlet Opening Offset
(min.)
H: Convection Air Outlet
*0-2" (0-51 mm)
*180 square inches
Max. offset from top of chase enclosure
I: Framing Depth (min.)
20-5/16" (516 mm)
From back wall to chase front
J: Opening Height
18" (457 mm)
Bottom/top of fireplace opening
K: minimum clearance to ceiling
1-3/4" (44 mm)
Top of chase to ceiling
L: Chase Enclosure (min.)
81-1/4" (2064 mm)
From base of unit/floor to top of enclosure
M:Clearance to Sprinkler Head (min.)
36" (914mm)
Perpendicular from chase grill
Hearth
0"
No hearth required
** See mantel clearances chart in the manual.
28
|
City Series CV60E
installation
Clearances CV60E
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Clearance: single sided
Dimension
Measured From:
A1: :
Mantel Height (min.)
**
Top of Fireplace Opening
A: From Floor
10 1/4” (260 mm)"
Bottom of Fireplace Opening
B: Sidewall (on one side)
8" (203mm)
Side of Fireplace Opening
C: Enclosure width
65 11/16" (1668mm)
Side of Fireplace Opening
D: Mantel Depth (max.)
**
E: Alcove Width
109.5” (2781mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
35" (889mm)
Front to Unit (Maximum)
H: Convection Air Outlet
*180 square inches
G: Convection Air Outlet Opening Offset
*0-2" (0-51mm)
K: Minimum clearance to celing
1 3/4” (44 mm)
M: Clearance to Sprinkler Head (Min.)
36" (914mm)
Perpendicular
From back wall to chase front
from chase grill
Hearth
0"
hearth required
**
See mantel clearances chart in this manual.
Flue Clearances to Combustibles
Horizontal - Top
3"
Horizontal - Side
2"
Horizontal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
1-1/2"
Note: This appliance uses 5" x 8" venting.
Alcove
E
F
D
A1
B
A
J
G
H
L
*
A minimum of 180 square
inches of open area, not
lower than 0-2" from top of
enclosure, required for all
installations
Side view
M
Chase grill
Sprinkler
J: Opening Height
18" (457 mm)
Bottom/Top of Fireplace Opening
Top of chase to ceiling
20-5/16" (516mm)
I: Framing depth
From base of unit to ceiling
81 1/4" (2038 mm)
L: Ceiling height
*A minimum of 180 square
inches of open area, not
lower than 0-2" from top of
enclosure, required for all
installations.
L
Chase grill
Sprinkler
Side view
M