Caution Requirements

The top, back and sides of the fireplace are defined by 

standoffs. The metal ends of the standoff may 

NOT

 be 

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk 

if these clearances (air space) to combustible materials are not 

adhered to. It is of greatest importance that this fireplace and vent 

system be installed only in accordance with these instructions.

CLEARANCES CB40EPV

Flue Clearances to 

Combustibles

Horizontal - Top

3"

Horizontal - Side 

2"

Horizontal - Bottom

2"

Vertical

2"

Passing  through  wall/floor/
ceiling  -  when  firestop  is 
used.

1-1/2"

*  A minimum of 120 square inches of open area, not lower than 3" from top of enclosure, required for all

installations — this can be achieved by having an open area in front, each side, and/or above as shown
in the four diagrams on the next page.

The 

HeatWave

  Duct  Kit  has 

different  clearance  and  framing 
requirements, check the 

HeatWave

 

manual for details.

E

F

Alcove

Clearance: 3 sided

Dimension

Measured From:

A: From Floor

Min. 0"

Bottom of Fireplace Opening

A1 : Mantel Height (min.)

**

Top of Fireplace Opening

B: Sidewall (on one side)

8-1/2" (216mm)

Side of Fireplace Opening

C: Enclosure Width (min.)

48-7/16" (1230mm)

Minimum inside dimensions

D: Mantel Depth (max.)

**

E: Alcove Width

84" (2134mm)

Side wall to side wall (min.)

F: Alcove Depth

36" (914mm)

Front of Unit

G: To Enclosure Ceiling (min/max)

0-3" (76mm)

From top of enclosure

H: Convection Air outlet 

120 sq. inches (min)

* Top/front or side of enclosure

I: Enclosure Depth (min.)

19" (483mm)

Minimum inside dimensions

J: Opening Height

15-1/16" (383mm)

Bottom/Top of Fireplace Opening

K: To Ceiling (min) All 3 sides

1-1/2"

To Top of Ceiling

L: Chase Enclosure (min.)

63" (1600mm)

From base of unit/floor

M:  Clearance to Sprinkler Head (Min.)

36" (914mm)

Perpendicular from chase grill

Hearth

0"

No hearth required

** 

See mantel clearances chart in this section

L

Chase grill

Sprinkler

Side view

M

City Series Power Vent

CB40EPV Gas Fireplace

Содержание CB40EPV Series

Страница 1: ...ure High 3 8 W C 0 94 kPa 10 5 W C 2 62 kPa Manifold Pressure Low 1 1 W C 0 27 kPa 2 9 W C 0 72 kPa Orifice Size Altitude 0 4500 ft 42 DMS 53 DMS Minimum Input Altitude 0 4500 ft 0 1372m 15 500 BTU h 4 54 kW 15 500 BTU h 4 54 kW Maximum Input Altitude 0 4500 ft 0 1372m 28 500 BTU h 8 33 kW 28 500 BTU h 8 33 kW Vent Sizing 4 Inner 6 5 8 Outer 4 Inner 6 5 8 Outer CSA P 4 1 60 02 60 85 ...

Страница 2: ...ferent clearance and framing requirements check the HeatWave manual for details E F Alcove Clearance 3 sided Dimension Measured From A From Floor Min 0 Bottom of Fireplace Opening A1 Mantel Height min Top of Fireplace Opening B Sidewall on one side 8 1 2 216mm Side of Fireplace Opening C Enclosure Width min 48 7 16 1230mm Minimum inside dimensions D Mantel Depth max E Alcove Width 84 2134mm Side w...

Страница 3: ...ng with vents in front sides or top Full framing with low vents in front or sides Full framing with vents in front or sides K C I A1 A D L J H B L I C D A1 A J G G H H H B I C G A A1 G D J L H H B I B A D C J G G L H H City Series Power Vent CB40EPV Gas Fireplace ...

Страница 4: ...2 1232mm C Framing Depth 19 483mm D Minimum Height to Combustibles 63 1600mm G Vent Centerline Height 56 1 4 1429mm I Gas Connection Opening Height 2 51mm J Gas Connection Height 4 106mm K Gas Connection Inset 13 330mm L Gas Connection Opening Width 3 1 2 89mm Note A combined minimum of 120 square inches of open area is required for the convection air outlet to cool the enclosure Ensure clearances...

Страница 5: ...front facing are shown in the diagram on the right Note Ensure the paint that is used on the mantel and the facing is high quality or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram 12 MANTEL LEG 8 1 2 CB40E 2 12 6 4 8 10 0 14 9 15 1 16 10 20 26 Top of Fireplace Opening 12 305mm 1 2 Drywall wood wood panel etc 5 1 8 To Bottomof Fireplace Opening ...

Страница 6: ...R TO 4 X 6 5 8 Note Rigid pipe is approved for up to 72 feet Note Flex pipe is approved for up to 40 feet using 2 X 946 756 20 foot flex kits 0 2 4 6 40 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 8 Horizontal Feet 4 0 6 10 12 16 18 14 20 22 24 3 Ft max 32 34 28 26 30 36 38 42 44 40 46 48 50 54 56 52 58 60 Vertical Feet 62 64 66 68 70 72 2 4 6 8 Restrictor Factory Set 1 2 72 overall length Max ...

Страница 7: ... from the back standoffs to the inside mounting surfaceofterminationcap Createalevelsurfacetomounttheventterminal TheTerminalmustnotberecessedintosiding Measurethewallthickness Flat Wall Installation Wall Thickness inches Vent Length Required inches 4 5 1 2 6 7 8 1 2 9 10 11 1 2 12 9 14 1 2 11 14 5 8 Adj Pipe 15 23 1 2 17 24 Adj Pipe Adj Pipe Length Rigid Pipe Adapter o 90 Elbow Pipe Length Vent r...

Страница 8: ...with Vent Terminal 1 510 994 Rigid Pipe adaptor sold separately 1 Power Vent Fan included w Power Vent kit 1 Power Vent Frame included w Power Vent kit 1 911 250 P 45 5 wire BX cable or sold separately 1 911 251 P 90 5 wire BX cable sold separately amount required for install 4 x 6 5 8 Rigid Pipe sold separately 1 946 535 Power Vent Kit sold separately Models Equipped with Surefire Ignition The Po...

Страница 9: ...supply is required to operate this system 946 535 Power Vent Kit with Vent Terminal 2 Max 946 756 20 Flex Kit sold separately 1 Power Vent Fan included w Power Vent kit 1 Power Vent Frame included w Power Vent kit 1 911 250 P 45 5 wire BX cable or sold separately 1 911 251 P 90 5 wire BX cable sold separately 1 946 535 Power Vent Kit sold separately Models Equipped with Surefire Ignition The Power...

Отзывы: