background image

Regency CLASSIC C33-2 Freestanding Gas Stove

11

Diagram 2

LOG SET

 INSTALLATION

WARNING:  Dangerous operating
conditions may occur if these logs
are not positioned in their approved
locations.  Read the instructions
below carefully and refer to the
diagrams. If logs are broken do not
use the unit until they are replaced.
Broken logs can interfere with the
pilot and burner operation.

Diagram 1

TEST FOR FLUE

SPILLAGE

This heater must be properly connected to a
venting system.

WARNING: Operation of this heater
when not connected to a properly
installed and maintained venting
system or tampering with the vent
safety shutoff system can result in
carbon monoxide (CO) poisoning
and possible death.

A “spillage” test must be made before the
installed unit is left with the customer.  Follow
the procedure below:

INSTALLATION

Valve Description

1) Gas cock knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection
5) Main Operator
6) Outlet Pressure Tap
7) Inlet Pressure Tap
8) Pilot Outlet
9) Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole

1) Start all exhaust fans in the home and then

close all doors and windows in the room.

2) Light the unit and set controls to maximum.

3) After five minutes, test that there is a “pull”

on the flue by placing a smoke match,
cigarette or similar device which gives off
smoke, on the edge of the draft hood. See
Diagram below.

The smoke should be drawn into the draft hood.
If the smoke is still not drawn into the draft hood,
turn the unit off and check for the cause of the
lack of draft. If necessary, seek expert advice.

Note: If the flue is blocked or has a strong

reverse flow, the thermally actuat-
ed safety switch mounted in the
draft hood will automatically shut
off the gas supply in less than 10
minutes. If the heater turns off
because of this during the spillage
test, check for the cause of the lack
of draft and if necessary, seek
expert advice.

To reset the thermally actuated safety switch,
let the unit cool for 10 minutes, then press the
red reset button on the back of the switch. See
Diagram below.

The gas log kit contains the following:

a)

Front Log

b)

Rear Log

c )

Small Cross Logs (2)

d)

Bag of embers

e)

Bag of rock wool

1) Remove the logs from the box and carefully

unwrap them.  The logs are fragile,
handle with care.  Do not force into
position.

2) Place the rear deflector on the rear log

support pins in the back of the unit.

3) Place the rear log into the rear of the firebox,

aligning the holes on the underside of the log
with the rear log support pins and carefully
push  the log down onto the pins. See
diagrams 1 and 2.

4) Ensure the front deflector is over front log

pins.  See diagram 1.

5) Place the front log in the front of the unit,

aligning the holes on the underside of the log
with the log support pins in the front of the
unit.  Carefully push the log down onto the
pins. See diagram 1.

6) Place the cross logs on top of the larger logs

aligning the holes on the underside of the
cross log with the log pins in the larger logs.
See diagrams 1 & 2. Carefully push the
cross logs onto the pins.

7) Distribute the embers along the mesh em-

ber tray, but do not cover the burner ports.
(Burner ports are the little holes on the top
of the burner tube.)  Pull off ember size
pieces from the rock wool.  Gently place the
pieces on top of the embers. See diagram
3.

Содержание C33-LP2

Страница 1: ...ectrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FPI FIREPLACE PRODUCTS INTERNATIONAL LTD 6988 Venture St Delta BC Canada V4G 1H4 908 636a MODELS C33 NG2 Natural Gas C33 LP2 Propane C33 Classic Freestanding Gas Stove ClassicC33models...

Страница 2: ...uwithall the warmth and charm of a woodstove at the flick of a switch The models C33 NG2 and C33 LP2 have been approved by Warnock Hersey for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your CL...

Страница 3: ...g 10 Test for Flue Spillage 11 Log Set Installation 11 Safety Latch 12 DoorHandle 12 Optional Remote Wall Switch 12 OptionalRemoteControlInstallation 12 Optional Wall Thermostat 12 WiringDiagram 13 Final Check 12 Normal Operating Sounds of Gas Appliances 13 OperatingInstructions OperatingInstructions 14 LightingProcedure 14 ShutdownProcedure 14 Copy of Lighting Plate Instructions 15 Maintenance Ma...

Страница 4: ...3 8 WC C E 0 94Kpa Manifold pressure Low 1 1 WC C E 0 27Kpa Orifice size 38 DMS Altitude 2000 4500 ft pi 610 1370m Maximum Input 29 000 BTUH 8 5Kw h Minimum Input 15 300 BTUH 4 48Kw h Serial No 201 HIGH ALTITUDE CONVERTED NATURAL GAS Model C33 NG2 Field Convertable for Altitude 2000 4500 ft Report No 476 1345 00 Made in Canada 908 634a DO NOT REMOVE THIS LABEL Minimum Clearances to Combustibles Ba...

Страница 5: ... 610 m Maximum Input 33 000 BTUH 9 67Kw h Minimum Input 17 000 BTUH 4 98Kw h FACTORY EQUIPPED FOR PROPANE Model C33 LP2 GAS FIRED VENTED ROOM HEATER This appliance must be installed in accordance with local codes if any If not follow ANSI Z223 1 CAN 1 B149 Electrical Supply 115 V 1 13 A 60 Hz Not for use with solid fuel Optional Fan Part 490 917 Listed Certified for Report No Tested to GAS FIRED V...

Страница 6: ...ENT CLEANING MAY BE RE QUIREDDUETOEXCESSIVELINT FROMCARPETING BEDDINGMA TERIAL ETC IT IS IMPERATIVE THAT CONTROL COMPART MENTS BURNERSANDCIRCULAT ING AIR PASSAGEWAYS OF THE APPLIANCEBEKEPTCLEAN DUE TO HIGH TEMPERATURES THEAPPLIANCESHOULDBELO CATED OUT OF TRAFFIC AND AWAYFROMFURNITUREANDDRA PERIES WARNING FAILURE TO INSTALL THIS APPLIANCE CORRECTLY MAY CAUSE A SERIOUS HOUSE FIRE AND WILL VOID YOUR ...

Страница 7: ...mbine clearances from one type of installation with another in order to achieve closer clearances Use the minimum clearances shown in the diagrams Alcove installations are approved as long as side wall clearances are maintained C33 2 Clearances to Combustibles A Side Wall to Unit 10 250 mm B Back Wall to Unit 6 150 mm E Side Wall to Unit 1 5 38 mm C33 2 Reference Dimensions to Flue Centerline C Ba...

Страница 8: ... stove to cool to room tempera ture 3 Open the pedestal door and remove the screws on the door cover plate Leg Units Remove bottom access panel 4 Loosen the nutsert screws 5 Remove Fan Assembly from the key slots at the fan base Take the fan out from the rectangular opening Diagram 3 6 Turn the fan around 90 degrees Pedestal units only Diagram 2 7 Disconnect the green ground wires to the grounding...

Страница 9: ...tibles cut a mini mum 3 inch diameter hole though the floor directly under your pedestal base to the outside Pipe fresh air into the pedestal area by using a minimum 3 duct pipe with a mesh grill at the outside termination Note Blanking plate combustion air hole is 4 diameter IMPORTANT Read all instructions carefully before starting the installation Failure to follow these instruc tions may create...

Страница 10: ...ures of 1 2 psig this appliance and its indi vidual shut off valve must be dis connected from the piping sys tem If test pressures equal to or less than 1 2 psig are used then this appliance must be isolated from the piping system by clos ing its individual manual shut off valve during the testing Output capacity The efficiency rating of the appliance is a product thermal efficiency rating determi...

Страница 11: ...the cause of the lack of draft If necessary seek expert advice Note If the flue is blocked or has a strong reverse flow the thermally actuat ed safety switch mounted in the draft hood will automatically shut off the gas supply in less than 10 minutes If the heater turns off because of this during the spillage test check for the cause of the lack of draft and if necessary seek expert advice To rese...

Страница 12: ...se a convenient location on the wall to install the receiver protection from extreme heat is very important Run wiresfrom the fireplace to that location Use the Thermostat Wire Table 2 Connect the two wires to the gas valve See diagram below CAUTION Do not wire millivolt remote control wires to the 120V AC wires 3 Install 3 AAA alkaline batteries in transmit ter and 4 AA alkaline batteries in the ...

Страница 13: ... gauge material from the rest of the firebox and body Therefore the varying thick nesses of steel will expand and contract at slightly different rates which can cause tick ing and cracking sounds You should also be aware that as there are temperature chang es within the unit these sounds will likely re occur Again this is normal for steel fireboxes Blower Thermodisc When this thermally activated s...

Страница 14: ...derstand these instructions before operating this appliance 3 Check to see that all wiring is correct and enclosed to prevent possible shock 4 Check to ensure there are no gas leaks 5 Make sure the glass in the door frame is properly positioned Never operate the appliance with the glass removed 6 Verify that the venting is unobstructed 7 Verify log placement If the pilot cannot be seen when lighti...

Страница 15: ...ately call your service technician or gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas supplier 5 Turn gas control knob counterclockwise to ON 6 Use rocker switch to operate main burner 908 649a OFF WARNING If you do not follow these instructions exactly a fire or explosion may result causingpropertydamage pers...

Страница 16: ...ing exposed to cold weath er 4 Inspect joints to verify that no pipe sections or fittings have been disturbed and conse quently loosened Also check mechanical supports such as Wall Straps for rigidity CAUTION ANYSAFETYSCREEN ORGUARDREMOVEDFORSERV ICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERAT INGTHEAPPLIANCE CLOTHING OR OTHER FLAMMA BLE MATERIAL SHOULD NOT BE PLACEDONORNEARTHEAPPLI ANCE NEVER...

Страница 17: ...low the stove to cool before removing or replacing glass 2 To remove the door from the stove remove the securing screw located between the ashlip and the door then unfasten the latch 3 Remove gold hinge caps from door 4 Lift door off hinge 5 Lay door on a soft flat surface 6 Remove the screws in the glass retainer clips and remove the glass retainer rod Remove any remaining pieces of glass and ens...

Страница 18: ...ove 3 Remove access panel a Front panel on pedestal model See diagram 1 b Panel from bottom of leg shield See diagram 2 Note Access panel only has to be loos ened to be taken out 11 Disconnect Piezo wire To remove valve from valve assembly continue 12 Remove two 2 thermopile wires 13 Remove thermocouple with a 9 mm met ric wrench 14 Remove pilot nut with an 11 mm wrench 15 Remove valve to orifice ...

Страница 19: ...Retainer 9 846 973 Door Handle Latch Assembly 10 910 250 Spill Switch 12 846 570 7 8 Gasket Repair Kit 13 846 918 Hinge Cap Gold 2 set 14 Screw 10 24 x 3 4 15 1 4 split lock washer 16 Screw 10 24 x 1 2 17 471 031 Door Retainer Clip 19 948 101 Spring Handle Large 490 917 Fan Assembly 120 V Optional 20 910 157 P Fan motor 120 V 22 910 794 Power Cord 910 140 Fan HI OFF LOW switch 28 910 142 Fan Auto ...

Страница 20: ...ilot Assembly 3 flame S I T LP 67 904 604 Orifice 36 NG 904 390 Orifice 52 LP 68 948 279 Burner LP 69 948 294 Burner NG 70 948 232 Air Shutter Adjusting Rod Burner Tray Assy NG Burner Tray Assy LP 72 490 023 Deflector Front Log 73 460 009 Deflector Rear Burner Front 74 490 025 Deflector Btm Burner Rear Log LP 75 490 068 Rear Log Deflector Top Propane 79 460 011 Deflector Rear Burner Back NG 80 902...

Страница 21: ...rd 121 Access Panel 140 850 126 Cast Legs Black 850 127 Cast Legs Gold 850 128 Cast Legs Brush Nickel 142 850 125 Steel Legs 490 926 CompletePedestal 100 948 216 Regency Logo 102 904 257 Magnetic Catch Large 103 11 Pedestal Hinge 108 910 246 Burner ON OFF Switch 2 way 109 910 272 LT DummyPlug 110 Strain Relief for power cord 123 Pedestal Blanking Plate 124 820 058 Pedestal Cover Plate 125 Rear Cov...

Страница 22: ..._____________________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________...

Страница 23: ... issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect The authorized selling dealer is responsible for all in field service work carried out on your Regency product FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is cla...

Страница 24: ...________________________________ Printed in Canada Regency fireplace products are designed with reliability and simplicity in mind In addition ourinternalQualityAssurance Teamcarefullyinspectseachunitthor oughly before it leaves our door Fireplace Products International Ltd is pleased to extend this Limited Lifetime Warranty to the orig inal purchaser of a Regency Product See the inside back cover...

Отзывы: