B41XTCE-11 Gas Fireplace

MANTEL CLEARANCES

Due to the extreme heat this fireplace emits, the mantel clearances are critical.  

Note: 

Ensure the paint that is used on the mantel 

and the facing is "heat resistant" or the paint 

may discolour.

MANTEL LEG CLEARANCES

Combustible mantel clearances from top of front 
facing are shown in the diagram on the right.

Note:  A non-combustible mantel may be 

installed at a lower height if the framing is 

made of metal studs covered with a non-

combustible board. The non-combustible 

mantel when installed at a lower overall 

height may not be lower than 6 inches 

from the top of the fireplace opening.

Combustible

Mantel Clearances

2

0

12

6

4

8

10

0

Top of

Fireplace

Opening

12”

1"

7”

A

B

C

Non-combustible

Header

(steel stud)

on edge

14

To Floor

12

24

Inches

D

6”

Non-combustible

Standoff

Mantel Clearances

B41XTCE

A

B

C

D

From Top of

Fireplace Opening

32-11/16"

(830mm)

25-13/16"

(656mm)

22-1/16"

(560mm)

17-9/16"

(446mm)

9” Side Wall

(Measured from side of

Fireplace Opening)

7”

4”

Mantel

leg

Mantel

leg

Allowable mantel leg

projection.

3"

1-1/2"

Gas Fireplaces

Содержание B41XTCE-NG11

Страница 1: ...Systems FPI AstroCap Flex Vent Rigid Pipe Vent Systems Simpson Direct Vent Pro Selkirk Direct Temp Metal Fab Sure Seal ICC Excel Direct Vent 28 1 2 38 3 8 22 11 16 46 11 16 25 9 16 16 7 16 32 5 8 38 1 4 36 3 8 26 3 16 3 1 4 49 1 4 11 5 8 7 5 16 1 9 16 1 1 2 35 44 1 4 3 5 8 29 1 8 23 7 16 38 7 16 1185mm 974mm 46 11 16 1185mm 976mm 889mm 738mm 92mm 594mm 649mm 664mm 1251mm 38mm 1123mm 417mm 829mm 18...

Страница 2: ...ired clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Mantel Height min 17 9 16 446mm Top of Fireplace Opening B Sidewall 9 229mm Side of Fireplace Opening C Ceiling 36 5 8 930mm Top of Fireplace Opening D Mantel Depth max 12 304mm 25 13 16 6...

Страница 3: ... made of metal studs covered with a non combustible board The non combustible mantel when installed at a lower overall height may not be lower than 6 inches from the top of the fireplace opening Combustible Mantel Clearances 2 0 12 6 4 8 10 0 Top of Fireplace Opening 12 1 7 A B C Non combustible Header steel stud on edge 14 To Floor 12 24 Inches D 6 Non combustible Standoff Mantel Clearances B41XT...

Страница 4: ...shing material tile slate etc the material can be installed directly onto the metal surface clean front of the unit in the area shown below CLEAN FINISH 6 If applying a non combustible facing it may be installed over the metal surface clean front of the unit in the area shown below Combustible and Non combustible Facing and Finishing Materials around unit 38 7 16 976mm 29 737mm Combustible Materia...

Страница 5: ...ough edges may be visible from an angle To maintain a clean finished edge facing material edges may be finished with a J style trim or metal corner bead both materials available at your local building or hardware store IMPORTANT Materials used must be NON COMBUSTIBLE IMPORTANT FINISHING DETAIL NOTE Before placing unit into final position it is important to know the total thickness height of finish...

Страница 6: ...ipe Venting Systems for Propane and Natural Gas Two 45o elbows equal to one 90o elbow Maximum of four 45o elbows allowed Vent must be supported at offsets Firestops are required at each floor level and whenever passing through a wall Maintain clearances to combustibles as listed in the Clearances section Refer to the Vent Restrictor Position section for details on how to change the vent restrictor...

Отзывы: