Fire Test Procedure
The test described below
must
be performed weekly in
a UL household fire installation. This procedure tests
the bell(s) attached to the system using standby power
only.
1.
Call the central station to inform them that you will
be conducting a test.
2.
Make sure the system is disarmed.
3.
Remove the screw that secures the model 9220
transformer to the outlet. (The 9220 is housed in
tan plastic and is plugged into an electrical outlet.)
4.
Unplug the transformer from the 120 volt
receptacle.
5.
Press
TEST
followed by your access code. The
bell(s) will sound for a few seconds. The test will
be recorded at the central station.
6.
Plug the transformer back into the receptacle.
7.
Replace the transformer retaining screw.
While the transformer is unplugged, the system may
sound the AC trouble audible signal. If this happens,
press
MUTE
MUTE
to silence it. The trouble condition
will clear automatically within one minute after the
transformer has been reinstalled.