Regency F1100/F3100 Freestanding Woodstove
|
11
11
|
installation
8
8
8
8
Minimum Alcove Clearance and Clearance to Combustible Materials
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84"
Maximum depth of alcove - 36"
combustibles whichever is smaller) from the rear of the stove.
Minimum Overall Width (X) of Floor
Protector
for all installations:
Small Stove
F1100S
38"
Large Stove
F3100L
42"
*The rear clearance to combustibles is less than 6" (152mm), for corner installations the rear corners may be angled to take advantage of the
closer clearances.
Floor Protection
(Ember Protection only required)
A combustible floor must be protected by a non-combustible material (like tile,
concrete board, or certified to UL-1618 or as defined by local codes) extend
-
ing beneath the heater and a minimum of 8" from each side and minimum
16" from the front face of the stove and minimum 6" (or the rear clearance to
NOTE: In Canada, floor protection must extend 18" to the front and 8" to each side of the stove.
From
From Flue
Min.
Min.Hearth
Unit
Unit
Center-line
Width
to Rear Wall
G H
I J
K
L
Small F1100S
with Airmate
11"
7"
23"
13.5"
46"
39"
with Rear Deflector
13"
5"
25"
11.5"
50"
37"
Large F3100L
with Airmate
16"
9.5"
30"
16"
60"
46.5"
with Rear Deflector (not approved for Alcove)
Minimum Overall Depth (Y) of Floor Protector
Residential Residential Mobile Home Alcove
Unit "C" Vent
Close Clearance Close Clearance
Y
Z Y Z Y Z Y
Z
Small F1100S
with Airmate
38"
6"
37"*
5"
38"
6"
38"
6"
with Rear Deflector
38"
6"
37"*
5"
37"*
5"
37"*
5"
Large F3100L
with Airmate
43"
6"
43"
6"
43"
6"
43"
6"
with Rear Deflector
43"
6"
43"
6"
43"
6"
n/a
n/a
NOTE: This clearance is also required for air space between the appliance and wall/
ceiling.