Regulation Modes (3c)
This panel contains a radio button for selecting the regulation mode:
•
AVR3 Regulation Mode
is used for Automatic Voltage Regulation with
three-phase generator voltage sensing.
•
AVR1 Regulating Mode
is used for Automatic Voltage Regulation with
single phase generator voltage sensing.
•
FCR Regulation Mode
is used for field current regulation. In this mode
the DVR
®
regulator will maintain a fixed level of field current.
•
VAR Regulating Mode
is used for reactive VAR regulation. This mode
is only enabled when the VAR/PF_OFF input is open. Otherwise, the
regulator will regulate as if AVR3 mode were selected.
•
PF Regulating Mode
is used for power factor regulation. This mode
is only enabled when the VAR/PF_OFF input is open. Otherwise, the
regulator will regulate as if AVR3 mode were selected.
Number of CT’s (3d)
This panel contains a radio button for selecting the number of CT’s to be
used for current and power measurement.
•
Three (A, B, C)
is used for metering of all three phase currents inde-
pendently. This sensing mode should only be selected when using three
current transformers. This is only available on the 2500.
•
One (B Only)
is used for metering of phase B current only. This sensing
mode should only be selected when using one current transformer in
phase B. Currents for phases A and C will not be metered and power
measurements will be based on the assumption phase B current flows
equally in phases A and C.
•
None
is used if no current transformers are connected.
VR Excitation (3e)
This panel contains a radio button for disabling or enabling excitation to
the field.
•
Excitation Off
is used to disable excitation to the generator exciter field.
The status indicator in the header will display a “STBY” state. This state
is recommended for making adjustments to the regulator settings.
•
Excitation On
is used to enable excitation to the generator exciter field.
If the regulator was previously “Off,” selecting this state will initiate a
new soft start for AVR1 and AVR3 regulation modes.
Note:
Any changes to the regulator settings made prior to selecting “Exci-
tation On” will be lost unless they are saved to EEPROM. See the Header
section above for details on saving settings to EEPROM.
Input Power Source (3f)
This panel contains a radio button for selecting the input power source
type.
•
PM Generator
is selected if the input power is derived from a perma-
nent magnet generator.