F O R M
DVR
®
2400 and DVR
®
2500 Digital Voltage Regulator
Installation, Operation and Maintenance Manual
SB0056E
Revised
November 2018
Regal Beloit America, Inc.
100 East Randolph Street
Wausau, WI 54402-8003
www.regalbeloit.com/Brands/
Marathon-Generators
Parameter Name
Parameter Value
Description
SIZE
281 to 1040
Frame size of generator
rEG
AVR3
AVR3 – Voltage regulation with three-phase sensing
AVR1
AVR1 – Voltage regulation with single-phase sensing
FCR
FCR – Field current regulation
VAR
VAR – Reactive VAR regulation
PF
PF – Power factor regulation
StPt
100.0 to 630.0
Voltage set point (Vrms) in AVR3 and AVR1 mode
0.000 to 4.000
Field current set point (Adc) in FCR mode
0% to 100%
VAR set point (% of rated VAR) in VAR mode.
-0.60 to 0.60
PF set point (PU) in PF mode.
UFrQ
40.0H to 70.0H
Under frequency knee (Hz)
SLoP
1.00U to 5.00U
Under frequency slope multiplier
Pr
0 to 6000
Rated power of generator (kW)
PFr
0.600 to 0.900
Rated power factor of generator (per unit)
Pt
1.0 to 150.0
Potential transformer ratio
Ct
1 to 2000
Current transformer ratio
droP
0.0% to 10.0%
Voltage droop (%) at rated reactive power
AU
OFF
Auxiliary Off – Auxiliary input is disabled
CNT1
Auxiliary Control-1 – Auxiliary input modifies regulation set point
(±3 or ±5 or ±10 Vdc input) (±5 or ±10Vdc for 2500 only)
CNT2
Auxiliary Control-2 – Auxiliary input modifies regulation set point
(4 to 20 mA input)
SLOP
Auxiliary Dynamic Slope - Auxiliary input modifies under frequency slope multiplier (0 - 5V)
Table 6-3. DVR
®
Regulator HMI EDIT Mode Parameters