- 34 -

troubleshooting Guidelines 

(CoNt’D)

Symptom

Potential Problem

Solution

The motor is 
operating in the 
wrong direction.

The rotation sensing 

feature needs to  

be reset.

WARNING: ALWAYS 

DISCONNECT MAIN 

HVAC SYSTEM 

POWER BEFORE 

DISCONNECTING OR 

RE-CONNECTING 

ANY WIRES OR 

CONNECTORS TO THE 

EVERGREEN MOTOR.

1.   Disconnect the main power to    

the HVAC system.

2.   Disconnect the High Voltage 

SIGNAL connection(s) from the 

motor to the HVAC system.

3.   Reconnect the main power to  

the HVAC system. Confirm there 

is proper voltage to the High 

Voltage POWER connections on 

the motor.

4.   Energize any of the Low Voltage 

SIGNAL (speed) tap selections 

continuously for a minimum of  

5 minutes.

5.   Disconnect the main power to 

the HVAC system for a minimum 

of 1 minute. Confirm there is 

no voltage to the High Voltage 

POWER connections on the 

motor. During this time  

reconnect the High Voltage 

SIGNAL connection(s). 

Now the Rotation Sensing feature  

will operate as described on page  

23 “Rotation Sensing”. If the motor 

does not perform the Rotation 

Sensing feature, repeat this 

procedure carefully and confirm  

all timings with a watch. 

If the motor again selects the wrong 

direction, confirm that the selected 

Evergreen IM is not too large for the 

system. See the selection chart on 

page 30. If the motor has not been 

sized properly, replace the motor.  

If the motor meets the selection 

criteria please call the Evergreen 

Hotline at 866-503-8566.

®

I

If the troubleshooting guidelines provided here do not solve the  
problem or you have a problem not listed here please contact:

evergreen Contractor Hotline 1-866-503-8566

 

If the evergreen Im needs to be replaced, it must be a direct  
evergreen Im replacement.

Evergreen IM manual 01-13.indd   34

2/13/13   11:12 AM

Содержание Genteq Evergreen IM

Страница 1: ...A Regal Brand EVERGREEN IM INSTALLATION GUIDE REG9551_Evergreen_EM_Installation_Guide_v2 indd 1 2 26 13 9 12 AM...

Страница 2: ...tation for high quality highly reliable products and strong customer relationships make us the preferred brand throughout the industry 1946 West Cook Road Fort Wayne IN 46818 1 866 503 8566 www theDea...

Страница 3: ...Power 7 8 High Voltage Signal 9 12 Low Voltage Signal 13 14 Special Applications 15 Continuous Fan Operation 16 Final Notes 17 Airflow Tests 18 22 Sequence of Operation 23 28 Maintenance 28 Troublesh...

Страница 4: ...a good practice to confirm that the power is off with a meter Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions whic...

Страница 5: ...tor for the HVAC System it is being applied to This unique ECM motor will operate and connect to the HVAC systems controls much differently than the replaced PSC motor For proper safe and efficient op...

Страница 6: ...motor is applicable to the HVAC System using the Application Guide above Confirm the motor being replaced is a direct drive indoor blower motor operating at 115 or 230VAC This is a dual voltage motor...

Страница 7: ...Hi___ MLo___ Lo___ TESP____ TR___ Furnace Heat Speed Hi___ MHi___ MLo___ Lo___ Furnace Heat Speed Hi___ MHi___ MLo___ Lo___ 1st Stage Air Conditioning and or Gas Propane or Oil Heating Systems Cooling...

Страница 8: ...g mounts Torsion flex brackets can be used on the Hp motor only They are not approved for the 1 Hp motor due to noise and longevity If the mounting bracket must be replaced selecting one with the same...

Страница 9: ...drip loop can be made with the signal and power lines The blower wheel should be centered in the blower housing The wheel should also not be resting up against the motor bearing housing If this is no...

Страница 10: ...age jumper Step 1 DO NOT CONNECT OR DISCONNECT ANY PLUGS OR JUMPERS WITH LINE VOLTAGE POWER CONNECTED OR APPLIED TO THE HARNESS Install the proper voltage jumper for the system the motor will be insta...

Страница 11: ...on 230VAC systems Step 6 Connect the Green w Yellow stripe ground wire that is pre connected to the silver control end of the motor to any cabinet ground within reach The blower section is an accepta...

Страница 12: ...r each unique HVAC System it could be used on The diagrams on the following pages will cover the most common HVAC system high voltage fan operation outputs Depending on the HVAC System there may be on...

Страница 13: ...AL HV connections of the Evergreen IM motor to provide the desired horse power output using the diagram below Configure the output of the Evergreen IM to match the horse power rating of the PSC motor...

Страница 14: ...or cool systems see the diagrams below Single Stage Heat Two Stage Heat Single Stage Heat Two Stage Heat Single Stage Cool Single Stage Cool Two Stage Cool Two Stage Cool The dashed lines represent n...

Страница 15: ...AL HV connection s from the motor in Step 2 to the combined fan output connections on the HVAC system in Step 3 See examples below I The dashed lines represent new field wiring added after the PSC mot...

Страница 16: ...the HVAC system thermostat connections Step 2 Strip the insulation back to connect bare wire or install terminals as needed to the appropriate speed selections determined below Step 3 Connect the Low...

Страница 17: ...trip Heat Y Call for heating and cooling operates the outdoor unit contactor W2 Call for Emergency Heat Gas Propane or Oil Heat Systems W Call for heating on single stage systems W1 Call for first sta...

Страница 18: ...e same speed from two different thermostat demands the special Y adapter included in the box must be used DO NOT attempt to use any other method to wire two thermostat lines to the same speed The Y ad...

Страница 19: ...tion section on page 28 for more information Increasing Constant Fan Airflow If more airflow is desired during constant fan operation there are two options Option 1 Connect any of the Low Voltage SIGN...

Страница 20: ...llation for future reference if needed The motors Hp rating can be found on the label located on the box Always verify the HVAC System operation in all demand modes applicable heating cooling and cont...

Страница 21: ...ooling Airflow and temperature measurements are often inaccurate without traversing the measured area This applies to measurements taken inside the duct and at the return grille and supply registers A...

Страница 22: ...ion An operating temperature rise that is higher than the manufacturer s recommendation can cause system failure on high limit Both of these situations can decrease the life of the heat exchanger It i...

Страница 23: ...ly register Analog or digital thermometers are accurate enough for these readings Some dual temperature meters will automatically calculate the difference Temperature rise is calculated as the differe...

Страница 24: ...not meet the required CFM of the system adjust the Low Voltage SIGNAL speed tap connected to the 24VAC thermostat demand up or down and take the readings again Repeat as needed to attain the proper CF...

Страница 25: ...ere are multiple circuits for multiple sets of strips add the amperage from all the circuits together Step 3 Calculate the temperature rise of the system See Measuring Temperature Rise on page 20 for...

Страница 26: ...s feature the motor will automatically determine the proper operating direction of the blower wheel without any wiring to configure During rotation sensing the motor will turn on and off running for a...

Страница 27: ...an controls de energize the 115VAC to the High Voltage SIGNAL connections the motor will turn off Important Note The Evergreen IM has numerous built in ramp timings to improve comfort and decrease the...

Страница 28: ...or will continue to operate at the fixed reduced speed setting until the High Voltage SIGNAL connection s are de energized This allows the HVAC System to maintain any built in fan off delays 3 HVAC Sy...

Страница 29: ...to maintain any built in fan on delays 2 HVAC System fan control s energize 115VAC to the High Voltage SIGNAL connection s Motor will ramp 15 second maximum ramp up to the highest value Low Voltage S...

Страница 30: ...Voltage SIGNAL speed tap than is currently energized the motor will ignore that communication 3 If a higher value Low Voltage SIGNAL speed tap is de energized while one or more lower value taps are s...

Страница 31: ...from a 24VAC thermostat demand At the end of all Low Voltage SIGNAL speed tap demands the motor will ramp down 45 seconds minimum ramp to the special high efficiency constant fan speed Maintenance Th...

Страница 32: ...taps should be continuous un switched line voltage This voltage alone will not operate the motor If proper voltage is not present troubleshoot the HVAC system Continue troubleshooting here after prope...

Страница 33: ...on 1 2 Hp Motor HV1 1 3 1 4 Hp operation HV2 1 4 1 5 Hp operation HV1 HV2 3 4 1 Hp operation 1 Hp Motor HV1 3 4 1 2 Hp operation HV2 1 2 Hp operation Selecting the Correct Replacement Motor Check off...

Страница 34: ...oltage above 30VAC could permanently damage the motor This voltage alone will not operate the motor Confirm there is proper 24VAC between the selected Low Voltage SIGNAL speed tap and the BLUE Common...

Страница 35: ...cting the Correct Replacement Motor CAUTION Do not install the larger motor to solve an airflow problem This could cause many other worse problems including rotation issues noise and hub failure If th...

Страница 36: ...or motor is too high WARNING ALWAYS DISCONNECT MAIN HVAC SYSTEM POWER BEFORE DIS CONNECTING OR RE CONNECTING ANY WIRES OR CONNECTORS TO THE EVERGREEN MOTOR To reduce the speed of the motor change the...

Страница 37: ...o voltage to the High Voltage POWER connections on the motor During this time reconnect the High Voltage SIGNAL connection s Now the Rotation Sensing feature will operate as described on page 23 Rotat...

Страница 38: ...orse power Hp rating of the replaced PSC motor Use the fol lowing chart to determine which High Voltage SIGNAL HV connection s to use Installed Evergreen IM Set up Data Heat Pump Systems Cooling Heati...

Страница 39: ...Square Feet Square Inches divided by 144 Square Inches Height x Width BTUH Output BTU per hour CFM Cubic Feet per Minute TD Temperature Difference Temperature Rise T CFM Velocity x Area CFM BTUH TD x...

Страница 40: ...3 8566 www theDealerToolbox com 2012 Regal Beloit Corporation Part GTQ 8004 Rev 06 11 7466X 01 13 2 5K BH CP 1946 West Cook Road Fort Wayne IN 46818 1 866 503 8566 theDealerToolbox com A Regal Brand E...

Отзывы: