SPR 0.1PA
29
Terminals:
PE, N, L – terminals (0,05-1,5 mm
2
) of supply (24 V AC resp. 110/120 V AC, resp. 230/240 V AC, 50/60 Hz
(according to the specification – voltage and frequency are stated on type plate of EA)
0 V, +24 V – terminals (max. 0,05 - 1 mm
2
) of output voltage 24 V DC (40 mA)
COM, CLOSE OPEN, I1, I2 – terminals (0,05 - 1 mm
2
) of control inputs 24 V DC
+IN, -IN, SH – terminals (0,05 - 1 mm
2
) of unified input current signal resp. voltage signal
+L, -L, SH – terminals (0,05 - 1 mm
2
) of output current signal (passive) 4-20 mA
COM, NO, NC, NO, NO – terminals (0,05 - 1,5 mm
2
) of
relay
READY,
relay
R1 a R2 (
on control unit
)
COM5, NO5, NC5 – terminals (0,05 – 1,5 mm
2
) relay RE5 (on the module of the additional relays)
COM1, RE4, RE3, RE2, RE1 – terminals (0,05 - 1,5 mm
2
) relay RE4, RE3, RE2, RE1 (on the module of the
additional relays)
COM, NO, NC – terminals (0,05 – 1,5 mm
2
) of relay READY
(on the module of the additional relays)
Note 1
: 230/220 V AC eventually 24 V AC supply voltage is to be fed to the N,L terminals of the
voltage supply source terminal board (X) according to the chosen variant of the electric actuator.
PE ground wire does not need to be connected when 24 V AC power supply is used.
Note 2:
relay R1; R2; RE1 to RE5: disabled; open position; close position; torque-open (not valid for
this type of the EA); torque – close (not valid for this type of the EA); torque open or torque close (not
valid for this type of the EA); torque open or position open (not valid for this type of the EA); torque
close or position close (not valid for this type of the EA); open; close; movement; movement flasher; to
position; from the position; warning; remote control; local control; control shut off.
Program possibilities for
READY
relay: faults, faults or warnings, faults or no remote, faults or
warnings or no remote.
Program possibilities for output signal (from
EPV
passive): 4 to 20 mA, 20 to 4 mA.
Control programme options (regulating): 2P, 3P, 3P/2P
switched over to I2
Program possibilities for input control signal (N): 4 to 20 mA, 20 to 4 mA, 0 to 20 mA, 20 to 0 mA.
Program possibilities for inputs I1: DISABLED, SAFE, DBL (local releasing, remote releasing), STOP.
Program possibilities for inputs I2: DISABLED, SAFE, DBL (local releasing, remote releasing), 2P (for
control programme option 3P/2P I2) allows control using the binary 24V AC / DC inputs with I2 input
activated.
Program possibilities of reaction SAFE: OPEN, CLOSE, STOP,
SAFE POSITION
The identical functions cannot be set on I1 & I2 inputs in addition to the OFF state (e.g., if the SAFE
function is set on I1 input, it is not possible to select the SAFE function on I2 input at the same time.
Relay READY on the control unit is doubled with relay READY on the module of the additional relays.
Relay R1 and relay R2 on the control unit is doubled with relay RE1 and relay RE2 on the module of the
additional relays.
Содержание SPR 0.1PA
Страница 9: ...SPR 0 1PA 7 1 7 2 Fig 1 5 4 3 8...
Страница 14: ...12 SPR 0 1PA INTERNAL PROTECTION TERMINAL Fig 2 FUSE SUPPLY F3 Fig 2a EXTERNAL PROTECTION TERMINAL...
Страница 29: ...SPR 0 1PA 27 6 Accessories 6 1 Wiring diagrams...
Страница 32: ...30 SPR 0 1PA 6 2 Dimensional drawings...
Страница 33: ...SPR 0 1PA 31...
Страница 34: ...32 SPR 0 1PA...
Страница 35: ...SPR 0 1PA 33...
Страница 36: ...34 SPR 0 1PA...
Страница 37: ...SPR 0 1PA 35...
Страница 38: ...36 SPR 0 1PA...