33
RECEIVER (BLINKING SYMBOLS)
7 SEGMENTS DISPLAY
LED
SYMBOL
MEANING
RED GREEN YELLOW
REMEDY
Customer configuration
rejected
WARNING
"F" symbol remains fix on
the display after the
blinking
ON OFF OFF
OSSD erroneously
connectedt o 24VDC
ON OFF OFF
External Feedback
contactors missed
ON OFF OFF
Carefully check the connections
ON OFF OFF
ON OFF OFF
Internal error
ON OFF OFF
Send the equipment for repair
to the REER laboratories.
OSSD1 - OSSD2
short-circuit
ON OFF OFF
Take action in one of the following ways:
•
(STANDARD and MASTER MODELS)
Carefully check the connection of terminals
1 and 3 (OSSD) on the connector.
•
(SLAVE MODELS)
Send the equipment for repair to the REER
laboratories.
(only for MASTER and
STANDARD models)
Overload of the OSSD static
outputs
ON OFF OFF Carefully check the connection of terminals 1
and 3 (OSSD) on the connector.
OSSD static outputs error
ON
OFF
OFF
Take action in one of the following ways:
•
(STANDARD and MASTER MODELS)
Carefully check the connection of terminals
1 and 3 (OSSD) on the connector. If
necessary, adjust load reducing the current
required to max 500 mA (2
µ
F)
•
(SLAVE MODELS)
Send the equipment for repair to the REER
laboratories.