INSTALLATION AND ELECTRIC CONNECTIONS 

  The M SG BOX RST modules can be fixed to the wall, using the proper plastic brackets inserted in 

the holes placed on the box rear side corners. These brackets can easily rotate to reach 90°.  

  The  light  curtain  must  be  connected  to the  respective  connectors  M12  (Fig.1)  using  the  dedicated 

cables. 

  The  cables  coming  out  from  the  cable gland  (PG11)  must  be  connected  -  depending  on  its 

utilization  -  to  the  connectors  CJ1,  CJ2  and  CJ3.  Terminal  tightening  torque:  4,4lb-in  (0,5  Nm)  is 
mandatory. 

  Use 60/75°C copper (Cu) conductor only. Wire size range: AWG 12÷30, (solid/stranded) (UL).  

 

Terminal board CJ1 

CLAMP 

NAME 

DESCRIPTION 

NA2_B 

Ends of the contact normally open n. 2 

NA2_A 

NA1_B 

Ends of the contact normally open n. 1 

NA1_A 

NCB 

Ends of contacts normally closed, in parallel

 

NCA 

 

 

Figure 6 

– M SG BOX RST connection sample 

 
 

Terminal board CJ2 

CLAMP 

NAME 

DESCRIPTION 

+24Vdc 

24 

 20% 

0V 

0 Vdc 

PE 

Protective Earth  

 
 

Terminal board CJ3 

CLAMP 

NAME 

DESCRIPTION 

OSSD1 

Safety status output 1 

OSSD2 

Safety status output 2 

K1_K2 

Feedback external relays K1/K2 input 

-  

SEL_A 

Operation mode selection 

SEL_B 

Operation mode selection 

 

Содержание SAFEGATE M SG BOX RST

Страница 1: ...itches for the configuration of the barrier itself DESCRIPTION M SG BOX RST is characterized by Luminous push button for restart and output status indication Connectors for wiring the box to the barri...

Страница 2: ...9 CONFIGURATION The configuration of the operating modes is described below This configuration is performed following the descriptions of the tables below by setting the various jumper connectors and...

Страница 3: ...matic Mode without EDM DIP SWITCH SW1 1 2 3 4 5 6 7 8 on off DIP SWITCH SW2 1 2 3 4 5 6 7 8 on off Automatic Mode with EDM internal relays DIP SWITCH SW1 1 2 3 4 5 6 7 8 on off DIP SWITCH SW2 1 2 3 4...

Страница 4: ...al relays DIP SWITCH SW1 1 2 3 4 5 6 7 8 on off DIP SWITCH SW2 1 2 3 4 5 6 7 8 on off Manual Mode without EDM external relays DIP SWITCH SW1 1 2 3 4 5 6 7 8 on off DIP SWITCH SW2 1 2 3 4 5 6 7 8 on of...

Страница 5: ...1 CJ2 and CJ3 Terminal tightening torque 4 4lb in 0 5 Nm is mandatory Use 60 75 C copper Cu conductor only Wire size range AWG 12 30 solid stranded UL Terminal board CJ1 CLAMP NAME DESCRIPTION 1 NA2_B...

Страница 6: ...ed in the technical data nevertheless to guarantee correct insulation and avoid damage or premature aging protect each output line with a 3 15 A delayed fuse and verify that the features of the load c...

Страница 7: ...sal helps to avoid any negative impact on the environment and health and encourages re use and recycling of the materials the equipment is made of In each individual Member State of the European Union...

Страница 8: ...www reersafety com M SG BOX RST 16 8541290 01 24 03 2020 Rev 0 All REER Safegate manuals and configuration software are available at www reersafety com download safegate...

Отзывы: