INSTALLATION AND ELECTRIC CONNECTIONS
The M SG BOX RST modules can be fixed to the wall, using the proper plastic brackets inserted in
the holes placed on the box rear side corners. These brackets can easily rotate to reach 90°.
The light curtain must be connected to the respective connectors M12 (Fig.1) using the dedicated
cables.
The cables coming out from the cable gland (PG11) must be connected - depending on its
utilization - to the connectors CJ1, CJ2 and CJ3. Terminal tightening torque: 4,4lb-in (0,5 Nm) is
mandatory.
Use 60/75°C copper (Cu) conductor only. Wire size range: AWG 12÷30, (solid/stranded) (UL).
Terminal board CJ1
CLAMP
NAME
DESCRIPTION
1
NA2_B
Ends of the contact normally open n. 2
2
NA2_A
3
NA1_B
Ends of the contact normally open n. 1
4
NA1_A
5
NCB
Ends of contacts normally closed, in parallel
6
NCA
Figure 6
– M SG BOX RST connection sample
Terminal board CJ2
CLAMP
NAME
DESCRIPTION
1
+24Vdc
24
20%
2
0V
0 Vdc
3
PE
Protective Earth
4
-
-
Terminal board CJ3
CLAMP
NAME
DESCRIPTION
1
OSSD1
Safety status output 1
2
OSSD2
Safety status output 2
3
K1_K2
Feedback external relays K1/K2 input
4
-
-
5
SEL_A
Operation mode selection
6
SEL_B
Operation mode selection