HIDEAWAY
ACTIVE SENSOR-FLUSH URINAL
Plumbers, please ensure a copy of the installation
instructions is left with the end user for future reference
HIDEAWAY
ACTIVE SENSOR-FLUSH URINAL
10.0
Diagnostic Function:
To assist in finding faults in the electronic components
the controller is equipped with a diagnostic function. Follow the
instructions below to activate this function.
1)
Press and hold down ‘Button 1’ (flush time) for 10 to 20 seconds.
While holding the
button the LED will flash dimly, which is normal.
2) After 10 to 20 seconds release the button.
3) The LED will now flash in a bright sequence as outlined below. This LED flash
sequence is consecutive and check
s
for 5 potential faults.
Between each fault check the LED will switch off for a 5 second pause.
DIAGNOSTIC FUNCTION
CORRECTIVE ACTION RESPONSE
Battery Power check:
One long flash = Battery OK
OR
Multiple flashes = Battery Power LOW
Note:
This check is for battery power controller checking only, not
mains power
Operating correctly
Replace battery
Problem fixed
If problem cannot be resolved
–
call 07 3875 2465
5 seconds pause
Pause then, Capacitive Sensor check:
One long flash = Sensor OK
OR
Multiple flashes = Capacitive Sensor not OK
Operating correctly
Ensure sensor cable is connected correctly at both plug connections.
Re-start Urinal by turning power off and then on again after 30 seconds.
Check red LED response as soon as power is switched on (see
Commissioning). Look for 2 confirmation flushes to confirm urinal is
functioning normally.
Problem fixed
If problem cannot be resolved
–
call 07 3875 2465 for assistance
5 seconds pause
Pause then, Temperature Sensor check:
One long flash = Sensor OK
OR
Multiple flashes = Temperature Sensor not OK
Operating correctly
Ensure sensor cable is connected correctly at both plug connections.
Re-start Urinal by turning power off and then on again after 30 seconds.
Check red LED response as soon as power is switched on (see
Commissioning). Look for 2 confirmation flushes to confirm urinal is
functioning normally.
Problem fixed
If problem cannot be resolved
–
call 07 3875 2465 for assistance
5 seconds pause
Pause then, Solenoid Valve check:
One long flash = Solenoid Valve OK
OR
Multiple flashes = Solenoid Valve is not OK
Operating correctly
Ensure Solenoid Valve is connected.
Re-start Urinal by turning power off and then on again after 30 seconds.
Check red LED response as soon as power is switched on (see
Commissioning). Look for 2 confirmation flushes to confirm urinal is
functioning normally.
Problem fixed
If problem cannot be resolved
–
call 07 3875 2465 for assistance
5 seconds pause
Pause then, indicates Average user statistics over the past 30
days.
1.
Flash = less than 20 usages per day
2.
Flashes = between 20 and 60 usages per day
3.
Flashes = more than 60 usages per day
Pause then, Completion of Diagnostic Mode is followed by 2
confirmation flushes.
Informative only, no action required.
In the event of power being disconnect or switched off, all user settings and functions are retained by the Flush Control Unit.
Button 1
page 13 of 16