background image

Install LDA- H

Drawing No. LP0673

Revised 08 2021

1

GENERAL DESCRIPTION

The Large Display is a versatile display available as a DC volt, current, 

or process meter with scaling, serial communications and dual relay 

outputs. The 5  digit displays are available in either 2.25" or 4" high red 

LED digits with adjustable display intensities. The 2.25" high models are 

readable up to 130 feet. The 4" high models are readable up to 180 feet. 

Both versions are constructed of a NEMA 4X/IP65 enclosure in light 

weight aluminum.

All models also come with dual Form C relay outputs and RS232 / 

RS485 serial communications.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear 

in this document or on equipment must be observed to ensure personal 

safety and to prevent damage to either the device or equipment 

connected to it. 

Do not use these products to replace proper safety interlocking. No 

software-based device (or any other solid-state device) should ever be 

designed to be responsible for the maintenance of personnel safety or 

consequential equipment not equipped with safeguards. Red Lion 

disclaims any responsibility for damages, either direct or consequential, 

that result from the use of this equipment in a manner not specified.   

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

LD2A

2.25" High 5 Digit Red LED Volt/Current Meter w/ 

Relay Output and RS232/RS485 Serial Comms

LD2A05P0

LD4A

4" High 5 Digit Red LED Volt/Current Meter w/ 

Relay Output and RS232/RS485 Serial Comms

LD4A05P0

LD Plug

Cord Grip Plug for LD models  *

LDPLUG00

* Required to maintain Type 4X/IP65 specification, if end plate cord grip does not 

have cable installed.

SPECIFICATIONS

1. 

DISPLAY

: 5 digit, 2.25" (57 mm) or 4" (101 mm) intensity adjustable 

Red LED (-99999 to 99999)

2. 

POWER REQUIREMENTS

:

AC POWER: 50 to 250 VAC 50/60 Hz, 26 VA

DC POWER: 21.6 to 250 VDC, 11 W

DC Out: +24 VDC @ 100 mA if input voltage is greater than 50 VAC/

VDC +24 VDC @ 50 mA if input voltage is less than 50 VDC

Isolation: 3000 Vrms for 1 min. to all inputs and outputs

3. 

INPUT RANGES

: Jumper Selectable

D.C. Voltages

: 200 mV, 2 V, 20 V, 200 V, 10 V

INPUT 

RANGE

ACCURACY @ 

23 

°

C LESS 

THAN 85% RH

INPUT 

IMPEDANCE

MAX 

INPUT 

SIGNAL

RESOLUTION

TEMP. 

COEFFICIENT

200 mV

0.1% of span 1.033 M

75 VDC

10 µV

70 ppm /°C

2 V

0.1% of span 1.033 M

75 VDC

0.1 mV

70 ppm /°C

10 V

0.1% of span 1.033 M

250 VDC

1 mV

70 ppm /°C

20 V

0.1% of span 1.033 M

250 VDC

1 mV

70 ppm /°C

200 V

0.1% of span 1.033 M

250 VDC

10 mV

70 ppm /°C

D.C. Currents

: 200 

µ

A, 2 mA, 20 mA, 200 mA

INPUT 

RANGE

ACCURACY @ 

23 

°

C LESS 

THAN 85% RH

INPUT 

IMPEDANCE

MAX 

INPUT 

SIGNAL

RESOLUTION

TEMP. 

COEFFICIENT

200 µΑ

0.1% of span

1.111 K

15 mA

10 nA

70 ppm /°C

2 mA

0.1% of span

111 

50 mA

0.1 µA

70 ppm /°C

20 mA

0.1% of span

11 

150 mA

1 µA

70 ppm /°C

200 mA 0.1% of span

500 mA

10 µA

70 ppm /°C

D.C. Process

: 4 to 20 mA, 1 to 5 VDC, 0/1 to 10 VDC

INPUT RANGE

SELECT RANGE

4 - 20 mA

Use the 20 mA range

1 - 5 VDC

Use the 10V range

1 - 10 VDC

Use the 10V range

4.

 OVERRANGE/UNDERRANGE INDICATION:

Input Overrange Indication

:  “

OLOL

”.

Input Underrange Indication

:  “

ULUL

”.

Display Overrange/Underrange Indication

: “

.....

”/“-

.....

” 

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

The protective conductor terminal is bonded to conductive 

parts of the equipment for safety purposes and must be 

connected to an external protective earthing system.

  2.25" & 4" HIGH RED LED DIGITS

  PROGRAMMABLE SCALING AND DECIMAL POINTS

  PROGRAMMABLE USER INPUT

  DUAL 5 AMP FORM C RELAY

  ALUMINUM NEMA 4X/IP65 CASE CONSTRUCTION

  RS232/RS485 SERIAL COMMUNICATIONS

  UNIVERSALLY POWERED

MODEL LD - Large DC Volt/Current/Process Display

AIR PRESSURE STABILIZATION VENT

(57.15)

2.25

X
Z

Y

DIMENSIONS  In inches (mm)

22 (558.8)

12 (304.3)

Z (Center)

7.875 (200)

26 (660.4)

LD4A05P0

4 (101.6)

16 (406.4)

LD2A05P0

Y (Height)

X (Length)

PART 

NUMBER

CC

US LISTED

US LISTED

UL

R

IND. CONT. EQ.

E137808

CC

US LISTED

US LISTED

UL

R

PROCESS CONTROL EQUIPMENT

E179259

Содержание LD Plug

Страница 1: ... VDC 100 mA if input voltage is greater than 50 VAC VDC 24 VDC 50 mA if input voltage is less than 50 VDC Isolation 3000 Vrms for 1 min to all inputs and outputs 3 INPUT RANGES Jumper Selectable D C Voltages 200 mV 2 V 20 V 200 V 10 V INPUT RANGE ACCURACY 23 C LESS THAN 85 RH INPUT IMPEDANCE MAX INPUT SIGNAL RESOLUTION TEMP COEFFICIENT 200 mV 0 1 of span 1 033 MΩ 75 VDC 10 µV 70 ppm C 2 V 0 1 of s...

Страница 2: ...stallation Category II Pollution Degree 2 11 CERTIFICATIONS AND COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class B Safety requirements for electrical equipment for measurement control and laboratory use EN 61010 1 General Requirements EN 61010 2 030 Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Listed File E137808 E179259 Ty...

Страница 3: ...istor when the load is switched One of the most effective ways is to place a diode across the inductive load Most RLC products with solid state outputs have internal zener diode protection However external diode protection at the load is always a good design practice to limit EMI Although the use of a snubber or varistor could be used RLC part numbers Snubber SNUB0000 Varistor ILS11500 or ILS23000...

Страница 4: ...N O 2 COMM 2 Sinking Logic Sourcing Logic USER COMM 6 5 CURRENT EXC 4 3 2 1 TBC VOLT ANALOG COMM USER RANGE SELECT JUMPERS 2 mA 20 V 200 V 10 V 200 mV 2 V 200 mA 20 mA 200µA Current Signal self powered Terminal 3 ADC Terminal 2 ADC Voltage Signal self powered Terminal 1 VDC Terminal 2 VDC Current Signal 2 wire requiring excitation Terminal 4 EXC Terminal 3 ADC 1 2 200 VDC MAX VOLT ANALOG COMM INPU...

Страница 5: ... high as 10M baud the LDA is limited to 38 4k baud The same pair of wires is used to both transmit and receive data RS485 is therefore always half duplex that is data cannot be received and transmitted simultaneously 3 4 SERIAL WIRING TBD A COMM RXD TXD 4 2 3 1 B 5 232 485 5 LD METER RECEIVING DEVICE 5V 4 47K 47K 3 B A COMM Transmit Enable OPTIONAL Terminal Block Connection Figure 1 1 TXD RXD COMM...

Страница 6: ...d proceed through each module in sequence When programming is complete it is recommended to record the parameter programming and lock out parameter programming with the user input or programming security code FACTORY SETTINGS Factory Settings may be completely restored in Module 2 This is useful when encountering programming problems ALTERNATING SELECTION DISPLAY In the explanation of the modules ...

Страница 7: ... the decimal location for the Input Value For Apply APLY style the meter shows the previously stored Input Value To retain this value press the SEL button to advance to the next parameter To change the Input Value press the RST button and apply the input signal to the meter Adjust the signal source externally until the desired Input Value appears Press the SEL button to enter the value being displ...

Страница 8: ...ut 8 seconds 6 When the display reads the selected range connect the positive lead of the DC current source to the current input and apply full scale input signal for the range Note For 200 mA range apply 100 mA as indicated on the display Press PAR Display reads CALC for about 8 seconds 7 Repeat steps 3 through 6 for each input range to be calibrated When display reads CAL NO press the PAR button...

Страница 9: ...gramming parameters This code can be used along with the Program Mode Lock out P Loc in the User Input Function parameter Module 1 Two programming modes are available Full Programming mode allows all parameters to be viewed and modified Quick Programming mode permits only the Setpoint values to be modified but allows direct access to these values without having to enter Full Programming mode Progr...

Страница 10: ...en the setpoint is a control output usually balanced hysteresis is used For alarm applications usually unbalanced hysteresis is used For unbalanced hysteresis modes the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints Note Hysteresis eliminates output chatter at the switch point while time delay can be used to prevent false trig...

Страница 11: ...igger point per the Setpoint Action shown in Setpoint Output Figures Latch means that the output can only be turned off by the front panel RST button or user input manual reset serial reset command or meter power cycle When the user input or RST button is activated momentary action the corresponding on output is reset immediately and remains off until the trigger point is crossed again Previously ...

Страница 12: ...BREVIATED PRINTING This parameter determines the formatting of data transmitted from the meter in response to a Transmit Value command or a Block Print Request Select NO for a full print transmission consisting of the meter address mnemonics and parameter data Select YES for abbreviated print transmissions consisting of the parameter data only This setting is applied to all the parameters selected...

Страница 13: ...minator Received First Character of Reply Reply Transmission NO REPLY FROM METER RESPONSE FROM METER Time Timing Diagram Figure Receiving Data From The Meter Data is transmitted from the meter in response to either a transmit command T a block print request command P or a User Input print request The response from the meter is either a full field transmission or an abbreviated transmission dependi...

Страница 14: ...rity bit is sent The transmitter sets the parity bit to a zero or a one so that the total number of ones contained in the transmission including the parity bit is either even or odd This bit is used by the receiver to detect errors that may occur to an odd number of bits in the transmission However a single parity bit cannot detect errors that may occur to an even number of bits Given this limitat...

Страница 15: ...1 d d S S P P 1 1 I I N N P P 2 2 U U A A S S N N User Input Assignment L L O O E E n n Min Display Enable Max Capture Delay Time Max Display Enable H H I I E E n n H H I I t t 2 2 S S E E C C Min Capture Delay TIme L L O O t t Factory Service Operations F F C C S S Access Code For Service Operations C C o o d d E E P P A A r r Parity Bit Baud Rate b b A A U U d d Data Bit d d A A t t A A 5 5 S S ...

Страница 16: ...W COURSE OF DEALING COURSE OF PERFORMANCE USAGE OFTRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install commission...

Отзывы: