Installation DA6UIN-B

Drawing No.  LP1122

Revised  03/2020

DA Series Universal Analog Input Module  

       

 

With 

Isolated 

Channels

Installation Guide

1

MODULE PACKAGE CHECKLIST

This product package should contain the items listed below. If 

any items are missing or damaged, contact Red Lion immediately.

 - DIN rail mount DA 6UIN Module

 - Installation Guide

GENERAL DESCRIPTION

The DA 6UIN module is designed for use with the DA70 

controllers, that can support up to 10 I/O modules simultaneously.  

This module features 6 Universal Analog Inputs operating at 

16-bit resolution, which makes it an ideal choice for a data-

acquisition application. The module can accept a wide range of 

thermocouples and RTDs, as well as 0/4-20 mA and 0-10 V 

Process signals. Each input has a dedicated alarm LED that 

indicates a variety of conditions.

The modules connect and communicate via proprietary 

backplane to the DA host device. The DA host device, equipped 

with serial ports as well as Ethernet port(s), allows the system to 

share data with PCs, PLCs, and SCADA systems.

Internal power management circuits allow the module to be 

replaced while power is applied, which reduces downtime in the 

event of a module failure. All configuration information is stored 

locally within the module, as well as in the Host, so replacement 

modules do not need to be configured. 

CONFIGURATION

The DA 6UIN modules are configured with Windows

®

 

compatible Crimson

®

 software. The software is an easy to use, 

graphical interface which provides a means of configuration and 

commissioning of new systems, as well as routine module 

re-calibration.

ALARMS

There are a total of 6 red Alarm LEDs – one per Universal Input 

channel. The 6UIN module Status LED shows general module 

health status. Please reference the LED section for a list of LED 

functions.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that 

appear in this document or on equipment must be observed to 

ensure personal safety and to prevent damage to either the 

device or equipment connected to it. 

Do not use these products to replace proper safety interlocking. 

No software-based device (or any other solid-state device) should 

ever be designed to be responsible for the maintenance of 

personnel safety or consequential equipment not equipped with 

safeguards. Red Lion disclaims any responsibility for damages, 

either direct or consequential, that result from the use of this 

equipment in a manner not specified.

CAUTION: Risk of Danger 

Read complete instructions prior to installation and 

operation of the unit.

ATTENTION : Risque de danger

 

Lire les instructions complètes avant l’installation et 

l’utilisation de l’appareil.

WARNING - EXPLOSION HAZARD - SUBSTITUTION 

OF COMPONENTS MAY IMPAIR SUITABILITY FOR 

CLASS I, DIVISION 2
AVERTISSEMENT - DANGER D’EXPLOSION - LE 

REMPLACEMENT DE COMPOSANTS PEUT NUIRE À 

L’APTITUDE À LA CLASSE I, DIVISION 2

 

z

Universal inputs accept TC, RTD, 0-5 V, 0-10 V, 0-20 mA, 

4-20 mA, 0-50 mV signals

 

z

Offers complete isolation; inputs, power and Controller 

 

z

Ideal for data acquisition applications

 

z

Fully isolated design provides reliable operation

 

z

Configured using Crimson

®

 software (version 3.1 or later)

FOR USE IN HAZARDOUS LOCATIONS: 

Class I, Division 2, Groups A, B, C, and D 

T4

C

US

UL

R

LISTED

IND.CONT. EQ.

E317425

0.49

(12.51)

0.45 (11.50)

4.53 (114.97)

6.22

(157.91)

1.91

(48.51)

1.35

(34.32)

32

31

30

29

28

27

26

25
24

23

22

21

20

19

18

17
16

15

14

13

12

11

10

09
08

07

06

05

04

03

02

01

6.00

(152.40)

DIMENSIONS In inches (mm)

II 3 G Ex ec IIC T4 Gc 

DEMKO 20 ATEX 2268X 

IECEx UL 20.0007X

Содержание DA Series

Страница 1: ...he 6UIN module Status LED shows general module health status Please reference the LED section for a list of LED functions SAFETY SUMMARY All safety related regulations local codes and instructions that appear in this document or on equipment must be observed to ensure personal safety and to prevent damage to either the device or equipment connected to it Do not use these products to replace proper...

Страница 2: ...rmity at 23 C after 20 minute warm up Probe Break Response If channel is enabled upscale drive Input Fault Alarm bit set high ALM LED illuminates 5 CURRENT INPUTS Ranges 0 20 mA or 4 20 mA Programmable Scaling 30 000 Input Impedance 10 Ohm Max Continuous Overload 100 mA Accuracy 0 1 of span Input Fault Response Upscale Drive Input Fault Alarm bit set high ALx LED illuminates below 2 mA and above 2...

Страница 3: ...very effective at reducing EMI and increasing relay contact life b If a DC inductive load such as a DC relay coil is controlled by a transistor switch care must be taken not to exceed the breakdown voltage of the transistor when the load is switched One of the most effective ways is to place a diode across the inductive load Most Red Lion products with solid state outputs have internal zener diode...

Страница 4: ... the various stages of the start up routine power up as well as any errors that may occur LED COLOR S MEANING Flashing Blue Module is booting Flashing Green Module is switching to configuration Green Module is performing normally Flashing Green Purple Module is performing auto calibration Flashing Blue Yellow Module is being flash upgraded by Crimson Flashing Red Error general error with module Fl...

Страница 5: ...irmware RED LION CONTROLS TECHNICAL SUPPORT If for any reason you have trouble operating connecting or simply have questions concerning your new DA Module contact Red Lion s technical support Support support redlion net Website www redlion net Inside US 1 877 432 9908 Outside US 1 717 767 6511 Red Lion Controls Inc 20 Willow Springs Circle York PA 17406 ORDERING INFORMATION DESCRIPTION PART NUMBER...

Страница 6: ...6 Drawing No LP1122 Revised 03 2020 This page intentionally left blank ...

Страница 7: ...7 Revised 03 2020 Drawing No LP1122 This page intentionally left blank ...

Страница 8: ...e local state or federal law b The Company shall not be liable for a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install commission or maintain the Product according to specifications ii Customer alters or repairs such Product without the prior written consent of Company c Subject to paragraph b with respect to any such Product during ...

Отзывы: