4
Preface
Drawing No. LP1106
Safety Information
Revision B
ST-IPm-8460
SixTRAK IPm
®
RTU/Controller
Environmental Safety Cautions and Warnings
CAUTION: This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D or non-
hazardous locations only.
ATTENTION: Cet équipement est adapté pour une utilisation dans la classe I, Division 2, Groupes A, B, C
et D ou non dangereux endroits seulement.
WARNING: Explosion Hazard – Substitution of components may impair suitability for Class I, Division 2.
ALERTE: Risque d’explosion - Remplacement d’un composant peut empêcher la conformité de Classe I,
Division 2.
WARNING: Explosion Hazard - When in hazardous locations, disconnect power before replacing or wiring
modules.
ALERTE: Risque d’explosion - Ne débranchez pas l’équipement à moins que l’alimentation ait été coupée
ou que l’environnement est connu pour être non dangereux.
WARNING: Explosion Hazard – Do not connect or disconnect any connections while circuit is live unless
area is known to be non-hazardous.
ALERTE: Risque d’explosion - Ne pas brancher ou débrancher les connexions lorsque le circuit est sous
tension sauf si la zone est connue pour être non dangereux.
Safety Information
Environmental
Pollution degree: 2 (Per IEC 61010-1)
Electrical
Properly ground the unit before connecting anything else to it. If the equipment is used in a manner “not” specified by
Red Lion, the protection provided by the equipment may be impaired.
Overvoltage category: II (Per IEC 61010-1)
Safety Standards
This unit meets the standards listed below, plus others.
Note:
Some ratings may be pending on newer models. Contact Red Lion for the latest information.
Electrical safety:
CE per Low Voltage Directive and IEC 61010-1
UL recognition per UL508
CSA per C22.2/142
Markings:
Direct Current: 10-30 VDC (minimum/maximum)
Protective Conductor Terminal
See warnings below.
Install the controller in accordance with local and national electrical codes.
Lightning Danger: Do not work on equipment during periods of lightning activity.
Do not connect a telephone line into one of the Ethernet RJ45 connectors.