DESCRIPTION

FlexCard option cards are for use in PAX2 series meters/controllers with 

FlexBus option. FlexCard programming is integrated into the host PAX2 

programming, which provides for parameters to be shared between them. 

FlexCards provide increased flexibility of input/output capabilities. The 

selection of FlexCard functionality is independent of other installed option 

card(s) functionality. A FlexCard can be installed in any available PAX2 

FlexBus slot.

This bulletin contains information for Analog Input FlexCards including 

Process Input/Remote Setpoint and Heater Current Monitor. Input connections 

are made through a screw-clamp terminal block at the rear of the PAX2 meter/

controller. Each card provides four solid-state outputs, that can be mapped to 

numerous parameter values in the host meter/controller. Output wiring 

connections are provided by a removable spring-cage terminal block, which 

engages PCB edge fingers through an access slot on the top of the PAX2 

meter/controller.

The 

Process Input/Remote Setpoint (

Prc

)

 FlexCard accepts a DC Voltage 

(0 to 10V) or DC Current (0 to 20mA) input signal and provides a process 

value to the host PAX2 meter/controller. PID control, if desired, is performed 

directly by the card, separate from the host meter/controller. This allows for 

multiple PID loops to be used in a single PAX2 meter/controller. Process 

parameters such as input range selection, scaling, offset value and PID control 

parameters are programmed through the host meter/controller.

When installed in a PAX2C controller, this FlexCard provides an additional 

analog input, which can be configured as a remote setpoint input or as a 

secondary process input. Configuration of the analog input as a remote 

setpoint signal allows ratio control, master setpoint/multiple slave operation, 

and the ability to cascade the PAX2C with another controller. Configuration 

of the analog input as a secondary process signal allows operation as a two-

process cascade controller within a single unit.

The 

Heater Current Monitor (

HCur

)

 FlexCard is useful for early warning 

of heater degradation, or heater circuit failure. The input is designed to 

connect to a current transformer with an output of 100 mA AC, to monitor the 

AC current load of the heater. A Heater Current alarm ensures that proper 

heater current is present when the control output is ON, and little or no current 

is present when the output is OFF. This provides indication of a shorted or 

open heater circuit. A direct readout of process heater current can also be 

displayed, if desired. Heater current limit values and input scaling are 

programmed through the host PAX2 meter/controller.

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

PX2FCA

Process Input/Remote Setpoint Input Card

PX2FCA00

Heater Current Monitor Input Card

PX2FCA10

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in 

this literature or on equipment must be observed to ensure personal safety and 

to prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the 

protection provided by the equipment may be impaired. Do not use this unit 

to directly command motors, valves, or other actuators not equipped with 

safeguards. To do so can be potentially harmful to persons or equipment in the 

event of a fault to the unit.

GENERAL SPECIFICATIONS

1. 

POWER

:

Power for the card is provided by the host PAX2 meter/controller.

2. 

INPUT SPECIFICATIONS AND CONNECTIONS

:

Refer to individual card information.

3. 

OUTPUT SPECIFICATIONS

: Four Solid-State NFET outputs

Type: Switched DC, N Channel open drain MOSFET

Current Rating: 1 ADC max

VDS ON: < 0.2 V @ 1 A

VDS Max: 30 VDC

Offstate Leakage Current: 0.5 µA max.

4. 

OUTPUT POWER SUPPLY (+Vout)

: 18 to 25 VDC @ 40 mA maximum. 

5. 

CERTIFICATIONS AND COMPLIANCES

:

Complies with all certifications and compliances of the host PAX2 meter/

controller in which it is installed.

6. 

CONNECTIONS

:

Rear Terminals: Fixed

Type: High compression cage-clamp terminal block

Wire Strip Length: 0.31” (8 mm)

Wire Gauge Capacity: 26 to 16 AWG (0.14 to 1.5 mm

2

Torque: 4.4-5.3 inch-lbs (0.5-0.6 N-m)

Top Terminals: Removable 

Type: Spring - cage terminal block. 

Wire Strip Length: 0.27” (7.0 mm)

Wire Gauge Capacity: 24 to 16 AWG (0.2 to 1.5 mm

2

) solid or stranded.

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

Bulletin No.  PX2FCA-B 
Drawing No.  LP0925
Released  03/15

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

 

z

USE IN PAX2 WITH FlexBus™ OPTION

 

z

FOUR SOLID STATE OUTPUTS

 

z

INSTALL FlexCard™ OPTION CARD IN ANY OPEN SLOT

Process Input/Remote Setpoint w/PID Control
Heater Current Monitor

MODEL PX2FCA - Analog Input FlexCards

Содержание PX2FCA

Страница 1: ... ensures that proper heater current is present when the control output is ON and little or no current is present when the output is OFF This provides indication of a shorted or open heater circuit A direct readout of process heater current can also be displayed if desired Heater current limit values and input scaling are programmed through the host PAX2 meter controller ORDERING INFORMATION MODEL ...

Страница 2: ...e option card slot Note that after the FlexCard top terminal case knock out is removed from the PAX2 case Reference Step 8 only another FlexCard with top terminals should be installed in the option slot location 4 Set the FlexCard Card Address DIP switch to match the option card slot position in which it will be installed Attach the appropriate slot location label to the rear of the top terminal b...

Страница 3: ...iv Input Resistance 5 Ω Accuracy 2 0 full scale 5 to 100 of range Frequency 50 to 400 Hz Overload 200 mA continuous Output on time delay for break alarm 1 second No Connection CT CT No Connection TO HEATER CONTROL LINE CURRENT TRANSFORMER NEUTRAL 120 240 V F1 F2 F3 F4 Rear Terminal Block Voltage Input F1 Current Input Input No Connection F2 F3 F4 0 20 mA Rear Terminal Block Voltage Input Current I...

Страница 4: ...d Red Lion Controls harmless from defend and indemnify RLC against damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalti...

Отзывы: