red lion G308A Скачать руководство пользователя страница 3

3

I

NSTALLING AND

P

OWERING THE

G308

MOUNTING INSTRUCTIONS

This operator interface is designed for through-panel mounting. A panel cut-

out diagram and a template are provided. Care should be taken to remove any
loose material from the mounting cut-out to prevent that material from falling
into the operator interface during installation. A gasket is provided to enable
sealing to NEMA 4X/IP66 specification. Install the ten kep nuts provided and
tighten evenly for uniform gasket compression. 

Note: Tightening the kep nuts beyond a maximum of 17 inch-pounds (1.92 N-

m) may cause damage to the front panel.

CONNECTING TO EARTH GROUND

Each G308 has a chassis ground terminal on the back of the unit. Your unit

should be connected to earth ground (protective earth).

The chassis ground is not connected to signal common of the unit.

Maintaining isolation between earth ground and signal common is not required
to operate your unit. But, other equipment connected to this unit may require
isolation between signal common and earth ground. 

To maintain isolation

between signal common and earth ground care must be taken when connections
are made to the unit.

For example, a power supply with isolation between its

signal common and earth ground must be used. Also, plugging in a USB cable
may connect signal common and earth ground.

1

1. USB’s shield may be connected to earth ground at the host. USB’s shield

in turn may also be connected to signal common.

POWER SUPPLY REQUIREMENTS

The G308 requires a 24 VDC power supply rated at 24 W. Your unit may

draw considerably less than 24 W depending upon the options being used. As
additional features are used your unit will draw increasing amounts of power.
Items that could cause increases in current are additional communications,
optional communications card, CompactFlash card, and other features
programmed through Crimson.

In any case, it is very important that the power supply is mounted correctly if

the unit is to operate reliably. Please take care to observe the following points:

The power supply must be mounted close to the unit, with usually not

more than 6 feet (1.8 m) of cable between the supply and the operator
interface. Ideally, the shortest length possible should be used.

The wire used to connect the operator interface’s power supply should

be at least 22-gage wire. If a longer cable run is used, a heavier gage
wire should be used. The routing of the cable should be kept away from
large contactors, inverters, and other devices which may generate
significant electrical noise.

A power supply with a Class 2 or SELV rating is to be used. A Class 2

or SELV power supply provides isolation to accessible circuits from
hazardous voltage levels generated by a mains power supply due to
single faults. SELV is an acronym for “safety extra-low voltage.” Safety
extra-low voltage circuits shall exhibit voltages safe to touch both under
normal operating conditions and after a single fault, such as a
breakdown of a layer of basic insulation or after the failure of a single
component has occurred.

CONFIGURING A G308

The G308 is configured using Crimson software. Crimson is available as a free

download from Red Lion’s website, or it can be purchased on CD. Updates to
Crimson for new features and drivers are posted on the website as they become
available. By configuring the G308 using the latest version of Crimson, you are
assured that your unit has the most up to date feature set. Crimson software can
configure the G308 through the RS232 PGM port, USB port, or CompactFlash.

The USB port is connected using a standard USB cable with a Type B connector.

The driver needed to use the USB port will be installed with Crimson.

The RS232 PGM port uses a programming cable made by Red Lion to

connect to the DB9 COM port of your computer. If you choose to make your
own cable, use the “G308 Port Pin Out Diagram” for wiring information.

The CompactFlash can be used to program a G3 by placing a configuration

file and firmware on the CompactFlash card. The card is then inserted into the
target G3 and powered. Refer to the Crimson literature for more information on
the proper names and locations of the files.

CABLES AND DRIVERS

Red Lion has a wide range of cables and drivers for use with many different

communication types. A list of these drivers and cables along with pin outs is
available from Red Lion’s website. New cables and drivers are added on a
regular basis. If making your own cable, refer to the “G308 Port Pin Outs” for
wiring information.

USB, DATA TRANSFERS FROM THE

COMPACTFLASH CARD

In order to transfer data from the CompactFlash card via the USB port, a

driver must be installed on your computer. This driver is installed with Crimson
and is located in the folder C:\Program Files\Red Lion Controls\Crimson
2.0\Device\ after Crimson is installed. This may have already been
accomplished if your G308 was configured using the USB port.

Once the driver is installed, connect the G308 to your PC with a USB cable, and

follow “Mounting the CompactFlash” instructions in the Crimson 2 user manual.

C

OMMUNICATING

W

ITH THE

G308

All tolerances ±0.010" (±0.25 mm).

ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING
DIVISION 2 WIRING METHODS AS SPECIFIED IN ARTICLE 501-
4 (b), 502-4 (b), AND 503-3 (b) OF THE NATIONAL ELECTRICAL
CODE, NFPA 70 FOR INSTALLATION WITHIN THE UNITED
STATES, OR AS SPECIFIED IN SECTION 19-152 OF CANADIAN
ELECTRICAL CODE FOR INSTALLATION IN CANADA.

WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.

The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.

Содержание G308A

Страница 1: ...e details 4 Battery type is lithium coin type CR2025 5 Industrial grade two million write cycles MODEL G308A GRAPHIC LCD OPERATOR INTERFACE TERMINAL WITH VGA DISPLAY AND TOUCHSCREEN Bulletin No G308A E Drawing No LP0613 Released 1 08 Tel 1 717 767 6511 Fax 1 717 764 0839 www redlion net CompactFlash is a registered trademark of CompactFlash Association z CONFIGURED USING CRIMSON SOFTWARE VERSION 2...

Страница 2: ...omponent Recognition Program of Underwriters Laboratories Inc Type 4X Enclosure rating Face only UL50 UL Listed File E211967 UL61010 1 UL1604 CSA 22 2 No 61010 1 CSA 22 2 No 213 M1987 LISTED by Und Lab Inc to U S and Canadian safety standards IECEE CB Scheme Test Certificate US 9737C UL CB Scheme Test Report E179259 V01 S04 Issued by Underwriters Laboratories Inc IEC 61010 1 EN 61010 1 Safety requ...

Страница 3: ... low voltage Safety extra low voltage circuits shall exhibit voltages safe to touch both under normal operating conditions and after a single fault such as a breakdown of a layer of basic insulation or after the failure of a single component has occurred CONFIGURING A G308 The G308 is configured using Crimson software Crimson is available as a free download from Red Lion s website or it can be pur...

Страница 4: ...Rx 3 Tx N C 4 DTR 3 COM 5 GND N C 6 DSR 1 CTS 7 RTS 6 RTS 8 CTS N C 9 RI 1 CBLPROG0 can also be used to communicate with either a PC or an ICM5 2 DB9 adapter not included 1 foot long 3 DB9 adapter not included 10 feet long ETHERNET COMMUNICATIONS Ethernet communications can be established at either 10 BASE T or 100 BASE TX The G308 unit s RJ45 jack is wired as a NIC Network Interface Card For exam...

Страница 5: ...ler CBLRLC05 TxA 8 TxA 8 TxB 7 TxB 7 COM 6 COM 6 TxEN 5 TxEN 5 RxA TxA 3 2 2 3 RxA TxA 3 2 2 3 RxB 4 1 RxB 4 1 TxB 1 4 TxB 1 4 Name Modular Controller Name G3 Connections DH485 COMMUNICATIONS The G308 s RS422 485 COMMS port can also be used for Allen Bradley DH485 communications WARNING DO NOT use a standard DH485 cable to connect this port to Allen Bradley equipment A cable and wiring diagram are...

Страница 6: ...lock the drive unless they need to write data Windows 98 may lock the drive any time it is mounted thereby interfering with logging Refer to Mounting the CompactFlash in the Crimson 2 User Manual TOUCHSCREEN This operator interface utilizes a resistive analog touchscreen for user input The unit will only produce an audible tone beep when a touch on an active touchscreen cell is sensed The touchscr...

Страница 7: ...our local waste regulations Also the battery must not be disposed of in fire or in a manner whereby it may be damaged and its contents come into contact with human skin The battery used by the G308 is a lithium type CR2025 CAUTION RISK OF ELECTRIC SHOCK The inverter board attached to the mounting plate supplies the high voltage to operate the backlight Touching the inverter board may result in inj...

Страница 8: ... II cards Use cards with a minimum of 4 Mbytes and a maximum of 2 Gbytes with the G308 s CompactFlash socket Cards are available at most computer and office supply retailers CompactFlash can be used for configuration transfers larger configurations data logging and trending Information stored on a CompactFlash card by a G308 can be read by a card reader attached to a PC This information is stored ...

Отзывы: