EL212 Installation Guide Rev 16-Jan-14
Page 26 of 28
POWER INPUT and ALARM OUTPUT
Dual-redundant internal power supplies
10-pole screw block can be positioned in front or back
Power input options:
o
+/-24-48 VDC (D option)
(absolute min and max):
+/-18-75 VDC
o
+/-110-250 VDC or 100-240 VAC (50/60 Hz)(A
option)
(absolute min and max):
+/-90-
300 VDC or 85-264 VAC
Power consumption:
o
60 Watts typ. w/ all ports linked
o
28 Watts with no transceivers
o
Add 1.25 Watts typical per transceiver
Protection: current overload and reverse polarity
Alarm output: form-C relay (NO and NC contacts)
o
Max. voltage: 250 VAC, 30 VDC
o
Max. current: 2A @ 30 VDC or 250 VAC
MECHANICAL
Universal mounting: (Sixnet-exclusive feature
– Patent
Pending!)
o
Front or rear/reverse wiring with power in front or
back
o
1U rack mount (19” brackets included)
o
Optional 23”, 24", EIA, WECO, ETSI and wall
brackets available
Ingress protection: IP50 sealed from dust and
contaminants
Heavy-gauge corrosion-resistant metal enclosure
Dimensions (HxWxD): 1.75(1U)x17.3x12”
(45x439x305mm)
Weight (typical): 5.5 lbs (2.5 kg)
ENVIRONMENTAL
Operating/storage temperature: Designed and tested
to -
40 to +85˚C per IEC 60068-2-1/2
Humidity: 5 to 95% RH (non-condensing) per IEC
60068-2-78
Vibration: 20mm/s from 1 to 150 Hz per IEEE 1613
Class V.S.3
Vibration: Amp: 3mm from 2-9 Hz, 1g from 9-
200Hz, 1.5g from 200-500 Hz per IEC 61850-3
Shock: 30g @ 11ms per IEC 61850-3
Shock - Free Fall: 250mm distance
EMC and STANDARDS COMPLIANCE
Substation: IEC 61850-3 / IEC 60870-2-2; IEEE 1613
EMC immunity: IEEE C37.90 and c37.90.1/2/3; IEC/TS
61000-6-5, IEC 60870-2-1, IEC 61000-4
2/3/4/5/6/8/10/11/12/16/17/18/29, IEC 60255-5, CE
EMC emissions: FCC Part 15;
EN 55022 (CISPR22), CE
Safety: UL508 / ANSI / ISA12.12.01/CSA C22.2
142/213. EL212F-DC-V1, T4 @ 85C (Surrounding
Air); EL212F-AC-V1, T3C @ 50C (Surrounding Air).
EN61010-1, Zone 2 (ATEX). Only the EL212F-DC-V1
is approved for Zone 2 (ATEX) areas.
RoHS, WEEE and CE compliant
ISO9001:2008 certified company
Warranty: 5 years on design and manufacturing
defects
MTBF A0/D0 models:
208,166 Hours GB @ 40˚C per
MIL-HNDBK-217F2
MTBF AA/DD models: 204,345 Hours GB @ 40˚C per
MIL-HNDBK-217F2
Содержание EL212F
Страница 1: ...www redlion net EL212F Industrial Ethernet Managed Switch Installation Guide Revision 16 January 2014 ...
Страница 2: ...EL212 Installation Guide Rev 16 Jan 14 Page 2 of 28 This page intentionally left blank ...
Страница 14: ...EL212 Installation Guide Rev 16 Jan 14 Page 14 of 28 Mechanical Dimensions for the EL212 ...
Страница 28: ...EL212 Installation Guide Rev 16 Jan 14 Page 28 of 28 This page intentionally left blank ...