red lion CUB4RT Скачать руководство пользователя страница 2

2

SPECIFICATIONS (Cont’d)

CUB4TC Thermocouple Inputs

:

Input Impedance

: 20 M

Lead Resistance Effect

: 0.03µV/ohm

Maximum Input Voltage

: 30 VDC, TC+ to TC-

Maximum Input Voltage TC-

: 3 VDC max. with respect to common

CUB4RT RTD Inputs

Lead Resistance

Cu427: 3 ohms/lead, 6 ohms total
All others: 10 ohms/lead, 20 ohms total 

Balanced Lead Resistance

: Automatically compensated up to max per lead.

Unbalanced Lead Resistance

: uncompensated

*  After 20 min. warm-up. Accuracy specified for the 0 to 50°C operating range

includes meter temperature coefficient and ice point tracking effects (TC
only.) The accuracy specifications includes the A/D conversion errors,
linearization conformity, and thermocouple ice point compensation (TC
only.) Total system accuracy is the sum of the meter and probe errors.
Accuracy may be improved by field calibrating the meter readout at the
temperature of interest.

7. 

CERTIFICATIONS AND COMPLIANCES:

SAFETY
UL Recognized Component, File # E179259, UL3101-1, CSA 22.2 No. 1010-1

Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.

Type 4X Enclosure rating 

(Face only), 

UL50

IECEE CB Scheme Test Certificate #UL2356A-179259/USA,

CB Scheme Test Report #98ME60090-000098

Issued by Underwriters Laboratories Inc.

IEC 1010-1, EN 61010-1:

Safety requirements for electrical equipment

for measurement, control and laboratory use, Part 1.

IP65 Enclosure rating 

(Face only), 

IEC 529

ELECTROMAGNETIC COMPATIBILITY

Notes:

1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:

Process signal may deviate during EMI disturbance.

For operation without loss of performance:

Unit is panel mounted in a metal enclosure (Buckeye SM7013-0 or

equivalent).

I/O cables routed in metal conduit connected to earth ground.

2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms:

Process signal may deviate during EMI disturbance.

For operation without loss of performance:

Install power line filter, RLC#LFIL0000 or equivalent, at the unit.

Refer to EMC Installation Guidelines section of the bulletin for additional

information.

8. 

CONNECTION:

Wire clamping screw terminals.

9. 

CONSTRUCTION:

High impact plastic case with clear viewing window.

(Panel gasket and mounting clips included.) Unit is rated for NEMA 4X/IP65
indoor use. Installation Category I, Pollution Degree 2.

10. 

WEIGHT:

3.3 oz. (93.5 g)

Enclosure class B

EN 55022

RF interference

Emissions to EN 50081-1

900 MHz ± 5 MHz

Level 3; 10 V/m

150 KHz - 80 MHz

ENV 50204

Level 3; 10 V/rms 

2

EN 61000-4-6

RF conducted interference

Level 3; 2 Kv power

Level 4; 2 Kv I/O

EN 61000-4-4

Fast transients (burst)

80 MHz - 1 GHz

Level 3; 10 V/m 

1

EN 61000-4-3

Electromagnetic RF fields

Level 3; 8 Kv air

Level 2; 4 Kv contact

EN 61000-4-2

Electrostatic discharge

Immunity to EN 50082-2

Simulation of cordless telephone

200 Hz, 50% duty cycle

±

1.7

°

C

±

0.9

°

C

-100 to 260

9.035 Ohm 

A

Cu427

±

1.5

°

C

±

0.7

°

C

-80 to 260

120 Ohm

B

Ni672

±

2.7

°

C

±

0.7

°

C

-200 to 850

100 Ohm

B

Pt385

±

2.7

°

C

±

0.7

°

C

-200 to 850

100 Ohm

Accuracy *

@ 23°C

±1LSD

B

Pt392

Accuracy *

@ 0 to 50°C

±1LSD

Range

Nominal

@ 0°C

Type

Jumper Position

(See Wiring

Diagram)

TC

TYPE

RANGE

ACCURACY*

@ 23°C

±

°C

WIRE COLOR

ACCURACY*

@ 0 to 50°C

±

°C

5.8

4.3

15.0

ANSI

BS 1843

T

-200 to 400°C

-328 to 752°F

2.3

BLUE

WHITE

J

-200 to 760°C

-328 to 1400°F

1.9

WHITE

YELLOW

R

0 to 1768°C

32 to 3214°F

4.5

BLACK

WHITE

S

0 to 1768°C

32 to 3214°F

4.5

BLACK

WHITE

B

200 to 1820°C

300 to 3308°F

9.1<540

°C

4.5>540

°C

GREY

NONE

E

-200 to 787°C

-328 to 1448°F

2.7

VIOLET

BROWN

N

-200 to 1300°C

-328 to 2372°F

2.8

ORANGE ORANGE

K

-200 to 1372°C

-328 to 2502°F

2.3

YELLOW

BROWN

mV

-10.00 to 60.00

0.02 mV

N/A

N/A

15.0

42.6<540

°C

15.0>540

°C

4.9

8.1

5.8

0.08 mV

DISPLAY

t

J

r

S

b

E

n

K

LIN

EMC INSTALLATION GUIDELINES

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of the
electrical noise, source or coupling method into the unit may be different for
various installations. In extremely high EMI environments, additional measures
may be needed. The unit becomes more immune to EMI with fewer I/O
connections. Cable length, routing and shield termination are very important and
can mean the difference between a successful or a troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.

1. The unit should be mounted in a metal enclosure, that is properly connected

to protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield to earth ground (protective earth) only at the panel

where the unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly 

grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity, or if the installation
is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far away as

possible from contactors, control relays, transformers, and other noisy
components.

5. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3

Note:

Reference manufacturer’s instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

Содержание CUB4RT

Страница 1: ...TC Backlight version 0 15 C Volt CJC error if powered from other than 12 VDC May be compensated with offset Example 24 VDC supply 24V 12V 0 15 C V 1 8 C Enter 1 8 C user offset 3 TEMPERATURE EFFECTS C...

Страница 2: ...o 1400 F 1 9 WHITE YELLOW R 0 to 1768 C 32 to 3214 F 4 5 BLACK WHITE S 0 to 1768 C 32 to 3214 F 4 5 BLACK WHITE B 200 to 1820 C 300 to 3308 F 9 1 540 C 4 5 540 C GREY NONE E 200 to 787 C 328 to 1448 F...

Страница 3: ...ges FLPrG and or FLCAL will be periodically flashed on the display FLPrG indicates that non calibration data is corrupt This flashing display will remain active even if power is removed and reapplied...

Страница 4: ...ber or press the SEL button to wrap around to the LSD After the desired value is on the display press and hold the SEL button for three seconds to enter the value and return to the main menu CAL YES N...

Страница 5: ...lay will read 00 000 to 20 000 ohms All other RTD types with the jumper in position B will cause the display to read 000 00 to 400 00 ohms Apply 105 000 mV wait 5 sec press SEL 105 000 mV IN8 Apply 90...

Страница 6: ...reference temperature probe to measuring end of the CUB4TC thermocouple The two probes should be shielded from air movement and allowed sufficient time 15 minutes minimum to equalize in temperature A...

Страница 7: ...the hole in the mounting clip 4 Install the unit through the panel cut out until the front bezel flange contacts the panel 5 Slide the mounting clip over the rear of the unit until the mounting clip i...

Страница 8: ...after No warranties expressed or implied are created with respect to The Company s products except those expressly contained herein The Customer acknowledges the disclaimers and limitations contained...

Отзывы: