SPECIFICATIONS

1. 

POWER

: 24 VDC ± 10% 

400 mA min. (1 module)
3 Amps max. (16 modules)
Must use Class 2 or SELV rated power supply.

2. 

COMMUNICATIONS

:

USB/PG Port

: Adheres to USB specification 1.1. Device only using Type B

connection.

Serial Ports

: Format and Baud Rates for each port are individually software

programmable up to 115,200 baud.

RS232/PG Port

: RS232 port via RJ12

COMMS Ports

: RS422/485 port via RJ45, and RS232 port via RJ12

DH485 TXEN

: Transmit enable; open collector, V

OH

= 15 VDC, 

V

OL

= 0.5 V @ 25 mA max.

Note: For additional information on the communications or signal common

and connections to earth ground please see the “Connecting to Earth
Ground” in the section “Installing and Powering the CSMSTRSX.”

Ethernet Port

: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).

3. 

LEDs

:

STS – Status LED indicates condition of master.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.

4. 

MEMORY

:

On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM: 2 Mbytes

5. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -30 to +70°C
Operating and Storage Humidity: 80%  max relative humidity,

non-condensing, from 0 to 50°C

Vibration According to IEC 68-2-6: 5 to 150 Hz, in X, Y, Z direction for 1.5

hours, 2 g’s.

Shock According to IEC 68-2-27: Operational 25 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters

6. 

CONSTRUCTION

: Case body is burgundy high impact plastic and

stainless steel. Installation Category I, Pollution Degree 2.

7. 

POWER CONNECTION

: Removable wire clamp screw terminal block.

Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)

8. 

MOUNTING

: Snaps onto standard DIN style top hat (T) profile mounting

rails according to EN50022 -35 x 7.5 and -35 x 15.

9. 

CERTIFICATIONS AND COMPLIANCES

SAFETY

UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for
Measurement, Control and Laboratory use.

Notes:
1. Criterion A: Normal operation within specified limits.
2. This device was designed for installation in an enclosure. To avoid

electrostatic discharge to the unit in environments with static levels above
4 kV precautions should be taken when the device is mounted outside an
enclosure. When working in an enclosure (ex. making adjustments, setting
jumpers etc.) typical anti-static precautions should be observed before
touching the unit.

10. 

WEIGHT

: 12.9oz (365.7g)

Immunity to Industrial Locations

:

Electrostatic discharge

EN 61000-4-2

Criterion A

2

4 kV contact discharge
8 kV air discharge

Electromagnetic RF fields

EN 61000-4-3

Criterion A
10 V/m

Fast transients (burst)

EN 61000-4-4

Criterion A
2 kV power  
2 kV signal

Surge

EN 61000-4-5

Criterion A
1kV L-L,2 kV L&N-E power 

RF conducted interference

EN 61000-4-6

Criterion A
3 V/rms

Emissions:

Emissions

EN 55011

Class A

1

Visit www.redlion.net for a complete list of PID modules, data acquisition modules, communications drivers and cables. 

The CSMSTRV2 was designed as a direct replacement for the original CSMSTRSE. This new model provides benefits such
as support via Crimson 2.0 software that allows configuration files to be uploaded. To save programming time, files originally
created in Crimson 1.0 (.cdb files) may be imported into Crimson 2.0.

2

Use this part number to purchase Crimson on CD with a printed Modular Controller Manual, USB cable, and RS-232 cable.

Otherwise, download free of charge from www.redlion.net.

3

Industrial grade two million write cycles.

ORDERING INFORMATION

G3CF512M

G3CF256M

PSDRXXXX

Accessories

Power Supply

G3CF

PSDR

512 MB CompactFlash Card 

3

256 MB CompactFlash Card 

3

64 MB CompactFlash Card 

3

DIN Rail Mounted Power Supply

PART NUMBER

TYPE

MODEL NO.

DESCRIPTION

CSMSTRV2

CSMSTRGT

CSMSTRSX

Master Module

CSMSTR

1

Modular Controller Master, Comms, Ethernet

CSTERM00

CSBASE00

RSRSTP00

CBLUSB00

G3CF064M

CBLxxxxx

SFCRM2MC

CBLPROG0

Software

Communications

Cables (10 feet)

SFCRM2

CBL

Replacement Termination Plug

Replacement Base

Rail Stops (Qty 2)

USB Cable

Communications Cables

1

Crimson 2.0

2

, Modular Controller Manual, and Download Cable

RS232 Programming Cable

Modular Controller with multiple protocol converter, data logger,
web server with Virtual HMI up to QVGA (320 x 240) size and
expansion slot.

Modular Controller with multiple protocol converter, data logger,
web server with Virtual HMI up to VGA (640 x 480) size and
expansion slot with increased SDRAM.

Содержание CSMSTRV2-A

Страница 1: ...share data with other devices at high speeds The CSMSTRV2 was designed as a direct replacement for the original CSMSTRSE This new model provides benefits such as support via Crimson 2 0 software whic...

Страница 2: ...and Laboratory use Notes 1 Criterion A Normal operation within specified limits 2 This device was designed for installation in an enclosure To avoid electrostatic discharge to the unit in environments...

Страница 3: ...ly not more than 6 feet 1 8 m of cable between the supply and the master Ideally the shortest length possible should be used The wire used to connect the master s power supply should be at least 22 ga...

Страница 4: ...h ground protective earth at one end where the unit is mounted b Connect the shield to earth ground at both ends of the cable usually when the noise source frequency is over 1 MHz c Connect the shield...

Страница 5: ...walkeremd com Standard Ethernet cable Use appropriate communications cable See Ordering Information for descriptions of the available cables WARNING Do NOT use a standard DH 485 cable to connect this...

Страница 6: ...or permanent connection ETHERNET COMMUNICATIONS Ethernet communications can be established at either 10 BASE T or 100 BASE TX The Master s RJ45 jack is wired as a NIC Network Interface Card For exampl...

Страница 7: ...One or more slave modules are missing from the system Master and installed modules will perform normally in this state INDICATION 2 blinks pause repeat Missing configuration or configuration being upd...

Страница 8: ...or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be...

Отзывы: