8. Write the current date on the battery pack.
9. Fit the new battery pack into the circuit board.
10. Plug battery back into the circuit board.
11. Refit the gear tray into the base, making sure the two
plastic clips capture it correctly.
12. Refit the diffuser and press each of the four lugs to ensure
they are fully located.
13. Restore power and allow charging for 24 hours.
14. Perform a full operation check and update the test record.
INS
TALLA
TION INS
TRUCTIONS
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
T: 0800 195 0006 F: 0870 195 0006
www.redarrowtrading.com
LED EMERGENCY EXIT SIGN
FOR MODEL: LFACLED502B
MAINTENANCE
•
When this fitting comes to the end of it’s life or you choose
to replace it, please do not dispose of it with your normal
household waste. Please recycle where the facilities exist,
check with your local authority or retailer for suitable
options.
ADDITIONAL INFORMATION
• 3 Hours emergency duration.
• 3.7V Deep discharge protection.
• 5.7V Overcharge protection.
• 20mm Cable entries.
• Maintained.
• Ni-Cd 4.8V 600mAh Battery included.
• Supplied with an arrow up exit legend.
• White finish.
GUARANTEE
This product is guaranteed for a period of 1 year from the date of purchase. The guarantee is invalid in the case
of improper use, tampering, removal of the Q.C. date label, installation in an improper working environment
or installation not according to the current edition of the I.E.E. Wiring Regulations (BS7671). The guarantee is
also invalidated if the luminaire has been Mega tested. Should this product fail during the guarantee period it
will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept
responsibility for any installation costs associated with the replacement of this product. Your statutory rights