LED EMERGENCY EXIT SIGN
FOR MODEL: LFACLED502B
3. Six-monthly – Interrupt the power supply and check the lamp
remains illuminated after one hour.
4. At the end of third year, and annually thereafter – check the
three hour duration: batteries must be replaced when they
can no longer support the three hour operation.
5. Complete the record sheet (page 5) on installation and retain
in a maintenance file.
6. Update file with on-going test records for inspection by a fire
officer or other duly authorised person.
OPERATION
Non-Maintained
• The lamp is normally off and battery on automatic charge
(green LED on) when the A.C. supply is healthy. Solid state
circuitry automatically switches the lamp on when the A.C.
supply is interrupted.
Maintained
• The lamp is normally on when the supply to the switched live
is on. The battery is on automatic charge (green LED on).
The lamp will switch on or remain on if the A.C. supply is
interrupted.
Monitoring
• The green LED indicator lamp will be on continuously. It will go
out if the A.C. supply or charger fails.
FAULT FINDING AND CORRECTIVE ACTION
• The green LED indicator is not illuminated: The A.C. supply is
not connected or the battery is not connected or the charger
has failed.
• The unit is not meeting the required emergency duration: The
fitting may need cycling. Discharge and then recharge for
a full 24 hours and then retest. The battery may need
replacing if the emergency duration is still not achieved.