Configurations
6
BAL_DFA_70_EN_1V0_REC_102-127109270
23 / 34
6
Configurations
6.1
Description of parameters
IMPORTANT
With the type "low energy", the parameters can only be changed by qualified personnel.
W = Factory parameter:
basic operator
(FP)
PARAMETER
W
REMARK
DRIVING CYCLE
→ closing speed
20
Speed when closing the door.
0 = lowest speed
40 = highest speed
– The maximum speed depends on the opening angle and acceleration.
→ opening speed
36
Speed when opening the door.
0 = lowest speed
40 = highest speed
– The maximum speed depends on the opening angle and acceleration.
– DIN: >1.5 s <4 s
TIME DELAY OPEN
→ time delay open
2
Determines how long the door remains minimally open after it has been
opened by a trigger signal of type AKA, AKI or tap-automatic.
0..20 = 0 to 20 seconds, increment 1 s
21..40 = 22 to 60 seconds, increment 2 s
– The time delay open starts when all trigger and safety signals for
closing stop.
→ SSK time delay open
5
Determines the minimum time the door remains open after it has been
opened by a trigger signal of the type SSK.
0..20 = 0 to 20 seconds, increment 1 s
21..40 = 22 to 60 seconds, increment 2 s
– The hold open time starts when all trigger and safety signals for closing
stop.
NOTICE
The time delay open can be reduced if sensors are used that hold the door open, e.g.
hold
time
.
DRIVE
→ opening angle
35
The opening angle is determined during the teach-in run and corresponds
to the value 40.
0 = minimum opening angle
40 = maximum opening angle
–
DIN
: min. 95°