RM-216 CB.11 Easy Line Documentation  

RDN 10000796 

15.12.2014 

1   Safety instructions 

 

 

The filter control system RM-216 C when connected to the mains poses an electrical hazard. 

Device failure, serious or even fatal injuries may occur as a result of improper installation of the 

connected equipment. Consequently, follow in particular the points set out below in addition to 

the general safety regulations for equipment in industrial electrical installations: 

  Installation of the device may be carried out only by qualified experts, in accordance with the 

provisions of IEC 364, DIN VDE 0105 for electrical equipment. 

  All applicable laws, conditions, orders and regulations governing the setting up of electrical 

equipment must be observed with respect to the installation site. 

  Setting of equipment with degree of protection IP00 without covers, may only be performed 

by authorized expert staff, when disconnected, and whilst observing the local safety and 

accident prevention regulations. 

  The RM-216 C may only be operated in the permitted operating area. 

  Switch off the mains supply before replacing the filter control or any components connected 

to it. Otherwise the equipment may be damaged. 

 

 

 

 

 

 

 

2   Equipment specification 

The RM-216 CB is used to control 24 V DC solenoid valves on filtering separators with compressed air 

pulse cleaning. After connecting the supply voltage, the filter control system functions fully automatically 

without further activation. 

 

Содержание EasyLine RM-216 CB.11

Страница 1: ...Operating and Installation Instructions Filter control system RM 216 CB 11 EasyLine ...

Страница 2: ...r the replacement of the device fuse 12 7 2 Cleaning the controller 12 7 3 Manufacturing 13 8 Text messages on the display 14 9 Details on the equipment function 15 10 Glossary 16 11 Technical specifications 17 Regulations VDE 0160 EN 60 439 Part 500 EN 50178 2004 108 EC Legend Warning against physical and health hazards or damages to the product and other properties Attention make absolutely sure...

Страница 3: ...able laws conditions orders and regulations governing the setting up of electrical equipment must be observed with respect to the installation site Setting of equipment with degree of protection IP00 without covers may only be performed by authorized expert staff when disconnected and whilst observing the local safety and accident prevention regulations The RM 216 C may only be operated in the per...

Страница 4: ...bly Wall mounting of the filter controls is not permitted The device may only be mounted to machine parts 4 Step by step installation Supply voltage connection A UL class 2 power supply unit is recommended for the operation of the filter controller with extra low voltage ...

Страница 5: ...RM 216 CB 11 Easy Line Documentation RDN 10000796 5 15 12 2014 Solenoid valve connection Connection of expansion modules RM LV8 RM LV16 ...

Страница 6: ...accessible for the user and to be marked as disconnecting device for the equipment The wires and cables used for the connection of the controls must be suitable for an ambient temperature of up to 130 C Use shielded cable for all bus lines The shielding must be connected unilaterally to the protective earthing PE Signal cables must not be laid parallel to power cables Tighten all cable glands in u...

Страница 7: ...ll up all following parameters P02 P11 in sequence The parameters already displayed can be accessed by repeatedly pressing the button To change the value of a displayed parameter press the ENTER button for at least one second The program then changes from parameter selection mode to parameter setting mode Press the button to increase the parameter value displayed in increments Press the button to ...

Страница 8: ...RM 216 CB 11 Easy Line Documentation RDN 10000796 8 15 12 2014 ...

Страница 9: ...ve test 2 Input test 3 5 For manufacturer purposes only Off 0 0 5 P09 P09 Ser run hour Service operating hours P10 P10 Ser run h AL Service operating hours alarm 0 h 0 25000 h P11 P11 Ser r h Code Service operating hours code 0 0 250 Number of all valves connected to the RM 216 CB and to the expansion modules The parameter is used by the equipment for internal monitoring purposes and need only be ...

Страница 10: ...ning perform the following steps Remove the factory fitted wire jumper on input E1 E2 terminals 10 11 Connect a free auxiliary contact make contact of the fan contactor to terminals 10 and 11 The input should be operated in isolation Set parameter P05 Down time cleaning cycles to the required number of cycles see also section 5 2 Setting parameters If the fan is switched on the contact on E1 E2 cl...

Страница 11: ...gnet coil faulty Replace coil No down time cleaning Parameter P05 0 down time cleaning cycles Set parameter P05 Down time cleaning cycles to a different value There is no signal from the fan control Activate signal to input I1 I2 Cleaning ineffective Interval time too long Set parameter P02 Interval time to a lower value Pressure too low Set pressure to 6 8 bar min 5 bar Set parameter P02 Interval...

Страница 12: ...the cover Pull off the transparent plastic cap of the fuse holder see picture Pull the fuse from the holder Insert the new fuse into the holder Use only the UL listed fuses that are mentioned in chapter 11 Technical specifications on page 17 Shut off after one hour at 135 of the nominal current Place the transparent plastic cap of the fuse holder Position the housing cover on the bottom part of th...

Страница 13: ...as manufactured by RECO Gesellschaft für Industriefilterregelung mbH Junkersring 11 D 53844 Troisdorf Germany 49 0 2241 39704 0 for Norbert Heinrich Automatisierungstechnik Feldstraße 16 32549 Bad Oeynhausen Germany Tel 49 0 5734 6002318 Please contact Norbert Heinrich Automatisierungstechnik to obtain technical support ...

Страница 14: ...and I2 Stand By Val No The control has been enabled via input E1 E2 and stopped via input D1 D2 Cleaning Off Val No The control has been enabled via input E1 E2 and started via input D1 D2 Cleaning On Val No Down time cleaning active DTC Cleaning ON 000 Pcs The alarm switching point for the service hours counter has been exceeded Call Service Val No A connected O module RM LV8 or RM LV16 is out of...

Страница 15: ...r elements terminals 8 9 If automatic components for dust removal extractor elements are fitted these need to be in operation during cleaning and during down time cleaning Connect the cut out for controlling these drive units to the isolated output S1 S2 Alarm relay output A1 A2 A3 terminals 5 6 7 As soon as the supply voltage is present on the RM 216 CB relay contact A1 A2 closes terminals 5 6 an...

Страница 16: ...xtractor element on and off I O module Input output module module for the input and output of control signals Operation mode Status of the RM 216 CB in which the equipment is ready for operation Parameter selection mode Status of the RM 216 CB in which the equipment operator can select a parameter Parameter setting mode Status of the RM 216 CB in which the equipment operator can set a parameter Pa...

Страница 17: ...pulse mode 42 Watt Outputs for expansion modules Supply voltage and pulse wires to the expansion modules Fuses F1 230 V M 0 2 A 250 V 5 x 20 mm Type Bell 5MT 200 mA ESKA UL 521 010 F2 110 V M 0 3 A 250 V 5 x 20 mm Type Bell 5MT 300 mA ESKA UL 521 012 Extra low voltage Fusing via PTC resistor Electrical connections Screw terminals Permissible wire gauge single wire 22 16 AWG 0 5 1 5 mm Flexible 22 ...

Страница 18: ... 18 15 12 2014 Disclaimer The contents of this documentation has been verified for correctness and completeness Nevertheless errors can not be excluded so that we cannot guarantee the correctness of this information Subject to alterations at any time ...

Отзывы: