42
CONTROL PANEL
REC-E08.10
Air handling unit RT 400S-EC
REC Indovent AB, Box 37, SE-431 21 Mölndal, Sweden
|
tel. +46 31 675500
|
www.rec-indovent.se
Bypass restriction
(at.low.outdoor.temperatures).
•. In.the.main.menu
•. Press.arrow.down.
.or.up.
.until..
. “SERVICE”.appears.in.the.display
•. Confirm.by.pressing.......
•. “CODE.xxx”.(3.digits).appears.
. in.the.display
•. Enter.service.code.
253
.by.pressing.the.up.or.
. down.button......Confirm.by.pressing........
. Note:.If.you.enter.the.wrong.code,.you.will.be.
. returned.automatically.to.the.“SERVICE”.menu.
•. If.you.enter.the.correct.code,.
. “SUPP.AIR”.appears.in.the.display
•. Press.arrow.down.
.or.up.
.until..
. “BP.L.LIM”.appears.in.the.display
•. Confirm.by.pressing.......
•. The.current.setting.appears.in.the.display..The.
. lamp.change.mode.lamp.......comes.on..Use.
. arrow.up/down.....to.set.the.required.value,.in.
. increments.of.1°C.(between.5-30°C)..
. 11°C.is.recommended.
•. Confirm.your.selected.setting.by.pressing........
•. Press.the.menu.button.......to.go.back.
. to.the.main.menu.
CODE
253
SERVICE
SUPP AIR
BP L LIM
BP L LIM
11