41
CONTROL PANEL
REC-E08.10
Air handling unit RT 400S-EC
REC Indovent AB, Box 37, SE-431 21 Mölndal, Sweden
|
tel. +46 31 675500
|
www.rec-indovent.se
Adjusting exhaust air minimum flow
•. In.the.main.menu
•. Press.arrow.down.
.or.up.
.until.
. ”SERVICE.SETTINGS”.appears.in.the.display.
•. Confirm.by.pressing.
.
•. “CODE.xxx”.(3.digits).appears.in.the.display).
•. Enter.service.code.
253
.by.pressing.the.
. down.button.
..Confirm.by.pressing.
.........
. Note:.If.you.enter.the.wrong.code,.you.will.be.
. returned.automatically.to.the.“SERVICE”.menu.
•. If.you.enter.the.correct.code,.
. “SUPP.AIR”.appears.in.the.display
•. Press.arrow.down.
.or.up.
.until.
. “MIN.EX.AIR”.appears.in.the.display.
•. Confirm.by.pressing.
.
•. The.current.setting.appears.in.the.display..The.lamp
. change.mode.lamp.
.comes.on..Use.arrow.
. up/down.
.
to.specify.as.a.percentage.of.the.unit’s.
. capacity,.the.volume.of.supply.air.that.
. is.planned..Adjustable.between.19-50%.
•. Confirm.your.selected.setting.by.pressing.
.
•. Check.the.new.flow.over.the.units..If.necessary,.
. make.further.adjustments.to.the.capacities..
•. If.the.minimum.flow.for.exhaust.air.must.also.be.
. adjusted,.use.the.arrow.keys.until.“MIN.SUPP.AIR”.is
. shown.on.the.display..The.procedure.is.otherwise.the.
. same.as.for.the.supply.air.flow..Once.the.adjustment.
. has.been.made,.press.the.menu.button.
.to.return.
. to.the.main.menu.
SERVICE
SETTINGS
CODE
253
SUPP AIR
MIN EX
AIR
MIN EX
AIR 50%
Adjusting supply air minimum flow
•. In.the.main.menu
•. Press.arrow.down.
.or.up.
.until
. “SERVICE”.appears.in.the.display.
•. Confirm.by.pressing.
.
•. “CODE.xxx”.(3.digits).appears.in.the.display).
•. Enter.service.code.
253
.by.pressing.the.
. down.button.
..Confirm.by.pressing.
......
. Note:.If.you.enter.the.wrong.code,.you.will.be.
. returned.automatically.to.the.“SERVICE”.menu.
•. Press.arrow.down.
.or.up.
.until.
. “MIN.SUPP.AIR”.appears.in.the.display.
•. Confirm.by.pressing.
.
•. The.current.setting.appears.in.the.display..The.lamp
. change.mode.lamp.
.comes.on..Use.arrow.
. up/down.
.
to.specify.as.a.percentage.of.the.unit’s.
. capacity,.the.volume.of.supply.air.that.
. is.planned..Adjustable.between.19-50%.
•. Confirm.your.selected.setting.by.pressing.
.
•. Check.the.new.flow.over.the.units..If.necessary,.
. make.further.adjustments.to.the.capacities..
•. If.the.minimum.flow.for.exhaust.air.must.also.be.
. adjusted,.use.the.arrow.keys.until.“MIN.EX.AIR”.is
. shown.on.the.display..The.procedure.is.otherwise.the.
. same.as.for.the.supply.air.flow..Once.the.adjustment.
. has.been.made,.press.the.menu.button.
.to.return.
. to.the.main.menu.
SERVICE
CODE
253
MIN SUPP
AIR
MIN SUPP
AIR 20%