OPERATION
Custom applications may have slightly different instructions. If you have any questions contact
your installer or Real Power.
Warm Up and Cool Down
The generator should be allowed to warm up before use when the weather is cold. This allows the
system to reach operating temperature before the components are stressed with a load. For
temperatures at or below 32°F the system should be allowed to warm up for approximately 10 minutes.
When the weather is hot or the generator is used under heavy load the system needs time to cool
down. This can be done by leaving the truck idling for 10 minutes with the PTO engaged allowing the
integrated generator fan to cool down the generator. Approximately a 10 minute cool down period is
recommended if the air temperature is greater than 80°F or if the generator is used at greater than 80%
load.
Starting the Generator
1.
Verify that there is no load on the generator. All equipment should be unplugged or off.
2.
Confirm that the E-Stop switch on the panel is reset (pulled out).
3.
Ensure truck is in Park
4.
Set Parking Brake
5.
Turn the Ignition Key if vehicle is not running. (Truck does not need to be turned off and on.)
6.
Set upfitter switch labeled “PTO”
PTO Clutch will automatically engage. Engine RPM will automatically ramp to the correct speed
and hold there.
7.
Allow the generator to warm up if necessary. (see above Warm Up and Cool Down section)
8.
The generator is ready to supply power.
Stopping the Generator
The normal procedure for shutting down the generator is as follows:
1.
Remove all loads from the generator. All equipment should be unplugged or in off position.
2.
Return PTO switch to off.
3.
Reset Parking Brake.
4.
Allow the generator a few seconds to spin down and come to a rest before moving the vehicle.