INSTALLATION INSTRUCTIONS 

(continued)

INSTALLATION OF POWER FLUE KIT

HORIZONTAL / VERTICAL FLUE RUN

The standard length of flue for the Power Flue is up to 13.5m of flue with 4 x 90 degree or 45

degree bends. The flue size that connects to the firebox should be as stipulated in the product

IOM. All flue after the baffle shall be as noted in the FLUE SIZE matrix above. For flue runs longer

than 13.5m and more than 4 bends a flue schematic should be forwarded to Real Flame for

approval. Once the flue run is approved you will be notified in writing. All horizontal terminations

shall have a downward grade from the motor to the termination.

FLUE CLEARANCES

All flue clearances are as per the requirements listed in the heater specifications.

TERMINATION

The termination to be used for all horizontal installations is to be either a small flush cowl or if used

as a service access panel, a large flush cowl is required. For vertical termination a vertical

approved cowl must be used. An external motor can be used as an option on horizontal and

vertical terminations.

POWER FLUE MUFFLER

The power flue muffler has a spigot at each end. The end that attaches to the firebox has a spigot

equivalent to the inner flue spigot diameter of the firebox, the top of the muffler has a 150mm

spigot which the motor fits to, or the 150/200 twin skin flue if required. The flow arrow on the

muffler is to be pointing up. If a 1800 or 3300 unit is used the flue is 200mm/250mm.

WIRING (see wiring diagram pages 17 & 18)

A 3 metre lead is supplied with the power flue, this lead has a different connection on each end,

one end is plugged into the connection on the left hand side of the firebox and the other end is to

be plugged into the fan. The wire coming from the rear of the firebox with the standard 3-pin plug

attached is to be plugged into a power point. A single gang wall switch is also supplied attached to

the 3 metres of lead; this wall switch is to be attached at a location accessible to the client. No

other wiring is required.

SERVICING OF THE POWER FLUE MOTOR

The Real Flame Power Flue motor is designed so as to make servicing the motor a simple task.

The power lead connected to the motor is to be disconnected (unplugged) and the screws are to

be undone, the fan motor will then lift out for servicing. The fan Motor box connected 

to the flue does not have to be disconnected from the flue.

FLUE SIZE

The flue size for each model is different. Please refer to the table below.

7

B
A

MODELS

A mm B mm

Double Vision, Hot Box and all Heatseekers

150

200

Pure Vision, Simplicity, Elegance, Signature, 

Hybrid 850, 1000 & 1500 Sizes

150

200

Pure Vision, Simplicity, Elegance, Signature, 

Hybrid 1800 & 3300 Sizes

200

250

NOTE: 

Ensure all power flue inner and outer flue lengths are sealed at joins.

Содержание Power Flue

Страница 1: ...POWER FLUE INSTALLATION OPERATING MANUAL The Real Flame Power Flue system is approved to be installed with any open fronted Real Flame gas fireplace VERSION 16...

Страница 2: ...en installed in an outdoor setting 4 Limit of Liability The warranty provided under this warranty is limited to replacement or repair of the Real Flame Gas Burner only at our option To the extent perm...

Страница 3: ...d any other relevant statutory regulations IMPORTANT NOTES The Real Flame power flue system is designed and manufactured by Real Flame and is approved to be installed with the following Real Flame Pro...

Страница 4: ...Clearance 10 Frameout 11 Motor exploded view 12 Dimensions 13 Internal Motor 15 External Motor 15 Troubleshooting Electronic Ignition and Power Flue System 16 Wiring Diagram 18 Parts List 18 Interfac...

Страница 5: ...OWER FLUE MOTOR Access must be provided to the flue motor this access MUST be at least 400mm x 400mm There MUST be a minimum clearance of 250mm between the top of the motor and any fixed object i e ce...

Страница 6: ...other opening into a building with the exception sub floor ventilation 500mm ELECTRICAL SHOULD THE SUPPLY FLEX AT THE BACK OF THE FIREBOX BE DAMAGED A SPECIALLY PREPARED FLEX IS REQUIRED FOR REPLACEME...

Страница 7: ...which the motor fits to or the 150 200 twin skin flue if required The flow arrow on the muffler is to be pointing up If a 1800 or 3300 unit is used the flue is 200mm 250mm WIRING see wiring diagram p...

Страница 8: ...een 4 and 8 may be used These values will give flue gas temperatures of 140 C and 220 C respectively For appliances with modulating burners the CO2 concentration in the flue shall be considered when t...

Страница 9: ...dule Kit Standard Power Lead Wall switch for On Off Kit Electronic Ignition Kit Baffled Flue Kit Z C Heatseeker Series Powered flue kit comprising Indicated on Diagram as Kit 1 x Fan motor 1 x Control...

Страница 10: ...Minimum clearance 250mm 150mm 200mm twin skin flue optional for additional height Ensure there is adequate ventilation within this cavity to prevent motor over heating Baffle Height 980mm and diamete...

Страница 11: ...TYPICAL POWER FLUE FRAMEOUT 11...

Страница 12: ...POWER FLUE MOTOR Fan Casing Pressure Differential Switch Motor 12...

Страница 13: ...D E F G H 302 348 345 55 5 90 40 20 200 250 150 200 I J K L M N O P 13 20 120 60 105 75 45 112 MODELS H mm G mm Double Vision Hot Box and all Heatseekers 150 200 Pure Vision Simplicity Elegance Signat...

Страница 14: ...DIMENSIONS Internal Power Flue Motor Internal Power Flue Motor 200 250 A B C D E F G H 268 281 331 311 202 152 300 128 A B C D E F G H 268 281 322 336 252 202 336 128 14...

Страница 15: ...on 250mm min 900mm Min Distance Domestic 220mm 200mm or 300mm 500mm 25mm Flush Cowl termination Top Termination Flue Access Panel EXTERNAL MOTOR Baffle Heater 150mm x 200mm twin skin flue if required...

Страница 16: ...ront of burner B The power polarity is reversed Check polarity B Sparker is to far from metal C Pressure switch Power Flue is not operating correctly Adjust sparker so it cross lights to metal Remove...

Страница 17: ...red LED light that indicates the possible cause of a problem the LED light will flash in different sequences for different problems the most common are Long Flash Short Flash 1 0 Normal Running State...

Страница 18: ...ING DIAGRAM LED Indicator TECHRITE POWER FLUE CONTROL MODULE Heat Sensor Sparker Power Fan Pressure Switch Double Block Solenoid NOTE For C Bus and or make up air damper interlock systems refer to pag...

Страница 19: ...s required by the manufacturer see installation manual The damper is to operate from 240V power The damper must have an interlock signal that activates in the fully open position The make up air dampe...

Страница 20: ...en allow the gas to the fire and the fire will ignite After operating for 60 seconds the module will check that the make up air damper interlock safety switch is in the closed position which indicates...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...elong hotmail com au Sydney NSW Showroom 546 Pacific Highway Chatswood NSW 2067 Ph 02 8905 0189 Fax 02 8905 0192 E mail info realflame com au Miranda NSW Showroom 36 Kareena Rd Miranda NSW 2228 Ph 02...

Отзывы: