INSTALLATION
(continued)
Checking Operating Pressure
NOTE: Check ensure that the correct jets, for the gas being used, are installed
– see page 25.
This check is done at the regulator located at the lower front of the appliance.
This must be done before fascia has been fitted.
Pressure test point available for operating pressure (as shown below).
The operating pressure has been factory set. Please check that the operating pressure is exactly
as listed below and if not, adjust the regulator until the pressure is correct. If unable to achieve
this, reassess the inlet gas pressure / pipes.
Replace operating test point screw and leak-test the test point.
Test for overall soundness using an appropriate method.
A = Inlet gas connection
B = Pressure adjustment screw
C = Operating pressure test point
Propane
Natural Gas
ULPG
Minimum Inlet pressure
2.5 kPa
1.0 kPa
2.5 kPa
Maximum Inlet pressure
5.0 kPa
5.0 kPa
5.0 kPa
Operating Pressure
2.0 kPa
1.0 kPa
2.2 kPa
A
B
C
Pressure Table