2 SE
TTINGS
MENU
41
Automatic Season
──────────────────────
Auto
Set change:22.0 °C
Sampling:030 sec
Neutral Temp:1.0 °C
──────────────────────
Change mode
A
DDRESS
3 S
ETTINGS
M
ENU
/
3.2
S
ET
D
ATE
-T
IME
S
CREENSHOT
Table of movements
Button
Screenshot
0
MAIN
3.1
SET SEASON
3.2.1 DATE / TIME
3.3
SET HOLIDAYS
Table of movements
Button
Screenshot
3.1.1 SEASON
Table of variables
No. Description
1
Set Auto/Manual Season
2
External temperature value that determines the
change of season
3
Time elapsed between detections
4
Differential beyond which a zone can request the change
of season regardless of the external temperature.
2
,
3
,
4
variables are irrelevant if the change of season is
set to MANUAL.
[SET DATE-TIME]
Set Date and Time
of the control unit
1
3
4
2
A
DDRESS
3 S
ETTINGS
M
ENU
/ 3.1 S
ET
S
EASON
/ 3.1.1 S
EASON
3.1.1.1
Automatic/Manual Season
The Man/Auto Freehold allows changing the season as follows:
Man: the change of season is managed by the user through
the Summer/Winter field
Auto: The change of season is managed by the control unit,
according to set temperature. The control unit will decide
whether to set the season to Summer or Winter and, according
to the external temperature, whether the system must work in
heating or in cooling mode.
WINTER
SUMMER
Intermediate
Season
Neutral-T
20 °C
Delivery with external WINTER
compensation logic
Delivery with external Dew
Point compensation logic
T.Ext
P.R.
WARNING: This function is activated only for systems that can be hydraulically set to the automatic heating/cooling
mode.