TR16 Wall Display Unit Installation
WDU Location
Choose a location that best represents the temperature of the area to be controlled.
Avoid locations that are subject to drafts, from doors and windows, or areas with direct sunlight exposure.
WDU Mounting
Route the wires to the WDU through the access hole in the back of the case. Mount the
WDU to the wall with the screws and anchors provided. Be sure to plug any large access hole in the wall
with sealer or insulation to prevent wall drafts from affecting WDU operation.
WDU Prewiring
The recommended wiring to the WDU from the Control Unit should be a two twisted pair
cable, 24 Ga minimum. Cat 3 or 5, 4 pair cabling is acceptable. In retrofit applications the existing
thermostat wiring (a least 4 wires) may be adequate. However, such non-twisted wiring may be subject to
interference due to noise from adjacent wiring or other sources.
Wiring to the Wall Display Unit
Hook TOP here
and rotate into
base. Be sure
pins engage in
connector ok.
TO CLOSE
OPENING AND CLOSING THE WDU CASE
OPEN
CLOSE
TO OPEN
PULL FROM LOWER CORNERS
G
+12
C
D
1 POWER GND
2 POWER +
3 COM CLOCK
4 COM DATA
J2
G
+5
C
D
TS16 WDU
BASE
J1
BASE
WIRING
ACCESS
HOLE
For Remote Sensor
WDU WIRING DIAGRAM
TR16 WALL DISPLAY UNIT
TR16 CONTROL UNIT
WDU
+12V
GND
DATA
CLK
J1
GND G
+12VDC +V
CLOCK C
DATA D
** CAUTION **
DO NOT
MISWIRE WDU
CONNECTIONS
OR
DAMAGE WILL
RESULT
TWISTED PAIR 22 GA WIRE RECOMMENDED
Remote Sensor Wiring
The TS16 WDU has an addition connector, J2, on the WDU base for connection of an external remote
temperature sensor. Follow the wiring diagram with the remote sensor to connect to the WDU.
DCN: 141-00930-09 7/13/06
12