Optional 24R Connection for 

single transformer HVAC 

Systems 

RC and RH are jumpered 

together on thermostat 

board. 

Cut RC/RH jumper JP1 for 

separate heating & cooling 

transformers 

 

Standard HVAC System 

G   Fan  

W1 Heat Stage 1 

Y1 Compressor Stage 1 

R   24VAC  Return 

C   24VAC Common 

Thermostat Connection

 

Y2  Compressor Stage 2 

W2 Heat Stage 2 

Standard Gas/Electric HVAC System Wiring 

 

 
 
 
 
 

 

 

 
 

 

 

 

 

 

 
 
 

 

 

 
 
 
 
 

 

 

 
 
 
 
 

 
 
 
 
 
 
 
 

Thermostat Setup:   
Standard Gas/Electric HVAC Systems  

To set the HVAC system type, go to the 

SYSTEM

 menu. 

 

1. 

SYSTYPE

   Set the HVAC System Type:  set to 

(Standard) 

2. 

FANTYPE

  Set the HVAC Fan Type: 

 

 Set to 

(Gas) for typical gas furnace (fan is controlled by the furnace) 

 

 

Set to 

(Elec) for electric heat  (fan call with heat call) 

3. 

CO 

Not used for standard systems.  Ignore this setting. 

 
Go to ADVANCED SYSTEMS SETTINGS to set the following: 
4. 

AUX HT

   Not used for standard systems.  Ignore this setting 

5.

 2ND

 

HT   

 Enable second stage heating outputs 

 

If a single stage heating system, leave this set to 

N

 

 

If a 2 stage heating system, set to 

Y

 to enable.  

6.  

2ND CO  

  Enable second stage cooling outputs 

 

If a single stage cooling system, leave this set to 

N

 

If a two stage cooling system, set to 

Y

 to enable. 

 

 

Default Setup: 

 

Standard HVAC 

 

Fan: Gas Heat 

 

1 Stage heating 

 

1 Stage cooling 

 
No setup required for this 
configuration 

Thermostat back 

 

Y2

 

Y1

 

G

 

RC

 

C

 

RH

 

W1

 

W2

/O

 

 

Typical thermostat wiring colors.  
Caution: verify that original wiring 
matches. Colors may be different.  

Blue 

Black/Brown 

Red 

White 

Orange 

Yellow 

Green 

C wire is not required 
for battery operation.   
Must be connected 
for 24VAC operation. 

firealarmresources.com

Содержание TBZ48A

Страница 1: ...you need to reinstall the old unit Read all instructions before starting installation Standard HVAC System Wiring Terminal Marking Meaning Typical Wire Color Record the old thermostat wire connection...

Страница 2: ...Do not install batteries if the thermostat is powered from 24VAC They are not required for backup Heating Cooling System HVAC Setup The thermostat must be setup for the correct system type and config...

Страница 3: ...rsions and Z Wave network information CLOCK set the time and day ZWAVE install uninstall from Z Wave network SYSTEM HVAC system setup Changing the HVAC default settings To change the HVAC system defau...

Страница 4: ...ype is automatically selected this selection is not used Changeover Valve Type CO For Heat Pump HVAC systems only The changeover or reversing valve is used to change from heating to cooling operation...

Страница 5: ...inimum separation between heating and cooling setpoints Note Attempts to lower the cooling setpoint below the heating setpoint will PUSH the heating setpoint down to maintain this separation The same...

Страница 6: ...cooling cycle can begin Provides compressor short cycle protection Heat Fan Purge H PURGE Range 0 90 Seconds Default 0 Runs the fan for this many seconds after the heat call ends A value of 0 is OFF...

Страница 7: ...or N Y 2 nd Stage Cool Y or N N H C Delta 3 15 deg 3 Heat Delta Stage 1 On 1 6 1 Heat Delta Stage 1 Off 0 5 0 Heat Delta Stage 2 On 2 7 2 Heat Delta Stage 2 Off 0 6 0 Heat Delta Stage 3 On 3 8 3 Heat...

Страница 8: ...call with heat call 3 CO Not used for standard systems Ignore this setting Go to ADVANCED SYSTEMS SETTINGS to set the following 4 AUX HT Not used for standard systems Ignore this setting 5 2ND HT Ena...

Страница 9: ...O or B connect the wire to the thermostats W2 O terminal The setting of the CO Type will set the correct system operation For changeover with cooling systems Orange wire set to C cool most common and...

Страница 10: ...g displayed System is ON and cooling blinking System is ON and heating Minimum Run Time MRT delay is active blinking System is ON and cooling Minimum Run Time MRT delay is active Temperature Setting W...

Страница 11: ...he setpoints Special Heat Pump Mode Emergency Heat Heat E An additional system mode Heat E for Emergency Heat will be displayed if the HVAC system type is set to Heat Pump If there is a compressor fai...

Страница 12: ...nt It maintains a 3 degree separation between the heating and cooling setpoint The same is true for raising the heating setpoint above the cooling setpoint Again the thermostat will push the cooling s...

Страница 13: ...change the Fan mode Fan Modes Auto Fan automatically operated by the HVAC system normal setting On Manual Fan mode Fan stays on until mode is changed back to Auto independent of the heating or coolin...

Страница 14: ...ode options SETUP User preference settings INFO Displays thermostat version and setup info CLOCK Setting the thermostat time and day ZWAVE Z Wave network install or remove SYSTEM Thermostat HVAC syste...

Страница 15: ...stat firmware version ZWAVE Z Wave firmware version NODE ID Z Wave Node ID HOME ID Z Wave Home ID SYSTYPE STANDARD standard HVAC system HP Heat Pump HVAC system If HVAC type Standard FAN TYPE GAS ELEC...

Страница 16: ...off immediately The MRT can be adjusted in the Installer Settings menu of the thermostat Note The MRT status is shown in the thermostat Status display Minimum Off Time MOT The thermostat has a Minimu...

Страница 17: ...re installing the TBZ48A into a Z Wave Network check that is not already installed in a network by viewing the Home and Zone ID s located in the INFO screen An un installed TBZ48A will show a Node ID...

Страница 18: ...controller be installed first proceeding out in consecutive rings from the controller Exclusion Removing the TBZ48A from a network 1 Set your primary controller to Uninstall or Remove mode to remove t...

Страница 19: ...is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect...

Отзывы: