Appendix 1 
 

8.1

 

Recommended wiring Practice for RS-485 Networked Devices. 

Introduction

 

RS-485 transmits digital information between multiple locations. RS-485 is designed to transmit this information 
over significant lengths, and 1000 meters are well within its capability. The distance and the data rate with which 
RS-485 can be successfully used depend a great deal on the wiring of the system. RCS guidelines and 
recommendations are provided within this document to ensure robust and reliable RS-485 networks. 

Cable 

RS-485 is designed to be a balanced system. Simply put, this means there are 2 wires, (other than ground), that 
are used to transmit the signal. The system is called balanced, because the signal on one wire is ideally the exact 
opposite of the signal on the second wire. In other words, if one wire is transmitting a high, the other wire will be 
transmitting a low, and vice versa. 
Although virtually any cable is capable of transmitting RS-485 signals, good wiring practice dictates that 

TWISTED PAIR

 type cable is used. 

 
As its name implies, a twisted pair is simply a pair of wires that are of equal length and are twisted together. 
Using an RS-485-compliant transmitter with twisted-pair wire reduces two major sources of problems for 
designers of high-speed long-distance networks: radiated EMI and received EMI.  
RCS suggest the use of Belden type cable (or similar) such as 9501 / 2, with a characteristic impedance of 120 
ohms. The RCS SM1020 gateway devices have termination resistors incorporated, however an end of line 
terminator (120 Ohms) is recommended to be fitted on the last device on a zone. The two wire RCS system is 
polarity conscious and the + - connections must remain consistent throughout the network.   
 

Maximum Number of RS-485 controllers on a Network 

RCS system manager (RS-485) devices and gateways are provided with 1, 4 or 8 channels (Zones) of RS-485. 
Each one of these zones can accommodate 32 individual control devices. 

It is good practice to ensure that cable lengths are kept to the minimum required without compromising network 
integrity. The wiring configuration should be of a Multi-Drop (

daisy chain)

 fashion whereby a single twisted pair 

cable is terminated at the system manager / Gateway and run to each control device in turn using either the on-
board “in and out” RS-485 connectors or the supplied communications terminals as in the case of Williams 
devices, Eden Controller and pack controllers etc. To avoid impedance mismatches and signal reflections and 
distortions a 

Star Point

 wiring configuration must not be used.   

 
  

 

Содержание SM1020

Страница 1: ...way s Page 1 Product Guide Issue 1 5 The SM1020 GP Gateway s Page 1 Product Guide Issue 1 5 The SM1020 GP Gateway s Page 1 Product Guide SM1020 GP Gateway SM1020 W GP Gateway Product Guide Issue 1 5 G...

Страница 2: ...mation 4 2 SETTING UP THE GATEWAY 5 2 1 User Instructions 5 2 2 Screen Shot of the Configuration Page 5 3 CONFIGURATION 6 3 1 Units 6 3 2 Network Parameters 6 3 3 XML Parameters 6 3 4 Adaptor Control...

Страница 3: ...arameter management Communicate with 32 RS485 Devices View real time controller status information The SM1020 W version supports the following Williams LAE controller types AD2 5 AD3 5 WUMC2 WUMC3 WUB...

Страница 4: ...present RS485 Status LED Red This indicator will initially be off until valid communication activity is detected Once RS485 communication activity is present the LED will flash at an intermittent rate...

Страница 5: ...et port of the GP Gateway 2 Connect the CAT5 patch lead into the Ethernet port of the laptop PC which will be used to configure the GP Gateway 3 Ensure that the laptop PC is assigned a static IP addre...

Страница 6: ...commence after a period of 2 minutes following a restart 3 2 Network Parameters To assign the GP Gateway a static IP address simply click into the desired field and type the required address If the us...

Страница 7: ...2A DC 5V 5 0 5A EMC EN 55014 1 2006 A2 Weight 65 Grams Excluding PSU Size 110mm L x 57mm W x 26mm D Inclusive of mounting flanges Ventilation No requirement for forced air cooling Operating temperatu...

Страница 8: ...teway 4 2 Ordering Information Part Number Product Name Description SM1020 GP Gateway General Purpose RS485 to IP Protocol Converter SM1020 W GP Gateway for use with Williams refrigeration units Gener...

Страница 9: ...nts First Draft 02 02 2013 DS First Draft Issued for internal review Issue 1 0 17 06 2013 DS Agreed content format Issued for customer distribution Issue 1 1 28 06 2013 DS Image alteration Issued for...

Страница 10: ...improvements the information contained within this document is subject to change at any time without prior notice RCS Energy Management shall not be liable for any errors or omissions for incidental...

Страница 11: ...ls RCS Energy Management 30 Kingfisher Court Hambridge Road Newbury Berkshire RG14 5SJ UNITED KINGDOM Tel 44 0 1635 231600 Fax 44 0 1635 231699 Email sales rcsenergymanagement co uk Website www rcsene...

Страница 12: ...ogether Using an RS 485 compliant transmitter with twisted pair wire reduces two major sources of problems for designers of high speed long distance networks radiated EMI and received EMI RCS suggest...

Отзывы: