8310-IQ, 8320-IQ, 8330-IQ & 8340-IQ Electromagnetic Lock
Installation Instructions
(Continued)
3
Lock Assembly
The IntelliMag
®
Electromagnetic Locks come with screws installed
in the housing. These screws, when in place, inhibit the insertion
of an Allen wrench into the mounting screw openings on the
underside of the lock. These screws will need to be removed prior
to installing the lock so as to allow the mounting plate to be
removed from the top of the lock. Fig 3 illustrates the location of
these screws. One screw acts solely to inhibit tampering while the
screw on the other end discourages tampering while holding the
cavity cover in place.
Inspection and Maintenance
This product and all related accessories or parts must be inspected
and maintained on a quarterly basis. Contacting surfaces of the
electromagnetic lock and armature plate must be kept free of
contaminating materials. Surfaces must be cleaned periodically
with a non-abrasive cleaner.
All mounting fasteners must be inspected on a quarterly basis.
When properly installed, the ends of the armature plate allow a
slight movement but the plate will feel secure when grasped at the
bolt. There should be no movement to the mounting bracket or
housing of the electromagnetic lock.
For added safety, thread locking compound has been provided for
the armature plate bolt and the four captive electromagnetic lock
mounting screws.
WARNING: Improper installation, maintenance, inspection or usage
of the product or any related accessories or parts may cause the
electromagnetic lock, armature plate and associated hardware to
disengage and fall, causing serious bodily injury and property
damage.
PLEASE DELIVER ALL INSTALLATION INSTRUCTIONS TO
THE END-USER UPON COMPLETION OF THE INSTALLATION.
For product support, parts and ordering information contact:
Rutherford Controls Int’l Corp.
USA:
2517 Squadron Court, Suite 104,
Virginia Beach, VA 23453
Canada: 210 Shearson Crescent
Cambridge, ON N1T 1J6
Phone: 1-800-265-6630 / 1-519-621-7651
Fax:
1-800-482-9795 / 1-519-621-7939
E-mail: [email protected]
Website: www.rutherfordcontrols.com
Fig. 3 – Lock Assembly View
anti-tamper
screw
cavity screw
To Ensure Instant Release
All switching devices must be wired in
between the DC power source and the positive terminal of the lock
in Fig 2.
Switching the negative power supply line will not allow the lock to
release immediately. RCI electromagnetic locks contain MOV's for
surge suppression and do not require any additional suppression
to be added during installation. The installation of diodes across
the lock input terminals will cause a delay in release.
Fig. 2 – Power Connections
SWITCH
+
-
INCORRECT
CORRECT
+
-
SWITCH
FILTERED DC SUPPLY
FILTERED DC SUPPLY