background image

8310-IQ, 8320-IQ, 8330-IQ & 8340-IQ Electromagnetic Lock

Installation Instructions 

(Continued)

3

Lock Assembly

The IntelliMag

®

Electromagnetic Locks come with screws installed

in the housing. These screws, when in place, inhibit the insertion
of an Allen wrench into the mounting screw openings on the
underside of the lock. These screws will need to be removed prior
to installing the lock so as to allow the mounting plate to be
removed from the top of the lock.  Fig 3 illustrates the location of
these screws. One screw acts solely to inhibit tampering while the
screw on the other end discourages tampering while holding the
cavity cover in place.

Inspection and Maintenance 

This product and all related accessories or parts must be inspected
and maintained on a quarterly basis. Contacting surfaces of the
electromagnetic lock and armature plate must be kept free of
contaminating materials. Surfaces must be cleaned periodically
with a non-abrasive cleaner. 

All mounting fasteners must be inspected on a quarterly basis.
When properly installed, the ends of the armature plate allow a
slight movement but the plate will feel secure when grasped at the
bolt. There should be no movement to the mounting bracket or
housing of the electromagnetic lock.

For added safety, thread locking compound has been provided for
the armature plate bolt and the four captive electromagnetic lock
mounting screws.

WARNING: Improper installation, maintenance, inspection or usage

of the product or any related accessories or parts may cause the
electromagnetic lock, armature plate and associated hardware to
disengage and fall, causing serious bodily injury and property
damage. 

PLEASE DELIVER ALL INSTALLATION INSTRUCTIONS TO

THE END-USER UPON COMPLETION OF THE INSTALLATION. 

For product support, parts and ordering information contact:

Rutherford Controls Int’l Corp.

USA:

2517 Squadron Court, Suite 104, 
Virginia Beach, VA 23453

Canada: 210 Shearson Crescent

Cambridge, ON N1T 1J6

Phone:  1-800-265-6630 / 1-519-621-7651
Fax:

1-800-482-9795 / 1-519-621-7939

E-mail: [email protected]
Website: www.rutherfordcontrols.com 

Fig. 3 – Lock Assembly View

anti-tamper
screw

cavity screw

To Ensure Instant Release

All switching devices must be wired in

between the DC power source and the positive terminal of the lock
in Fig 2. 

Switching the negative power supply line will not allow the lock to
release immediately. RCI electromagnetic locks contain MOV's for
surge suppression and do not require any additional suppression
to be added during installation. The installation of diodes across
the lock input terminals will cause a delay in release.

Fig. 2 – Power Connections

SWITCH

+

-

INCORRECT

CORRECT

+

-

SWITCH

FILTERED DC SUPPLY

FILTERED DC SUPPLY

Содержание IntelliMag 8310-IQ

Страница 1: ...nough to meet the magnet surface Refer to the Product Accessories Guide section of the Installation Instructions for further information 11 Installation of this product should be done by an experienced installer with knowledge of this product NOTE It is highly recommended that thread locking compound be applied to all screws during installation to reduce chance of screws loosening over extended ti...

Страница 2: ...ents Alarm Alarm Status Remote Indication When the door is closed and an illegal armature plate is detected the common contact TB1 6 and the normally open contact TB1 7 are activated for the preset period of time The alarm status relay contacts are rated at 30VDC 2 0 amps maximum Alarm Time Setting Refer to figure 1 JP2 Note 15 or 30 seconds requires one jumper 60 seconds requires no jumper and in...

Страница 3: ...dded safety thread locking compound has been provided for the armature plate bolt and the four captive electromagnetic lock mounting screws WARNING Improper installation maintenance inspection or usage of the product or any related accessories or parts may cause the electromagnetic lock armature plate and associated hardware to disengage and fall causing serious bodily injury and property damage P...

Страница 4: ... not include a shunted light option Check to see that armature plate is correctly aligned with the electromagnetic lock If there is improper alignment make a 1 4 turn of the armature plate mounting bolt and check for alignment CAUTION The armature plate must remain affixed securely to the door or serious bodily injury or property damage may occur Bolt should be tight enough to hold the armature pl...

Страница 5: ...cient space on the frame header to mount the lock The lock mounts to the underside of the L bracket and the L bracket then gets mounted to the doorframe Available in several different sizes and finishes Available for all 8310 and 8320 locks Allows an armature plate to be mounted to a glass or Herculite door that does not have a frame The Glass Door Bracket is a U shaped piece of 1 16 thick materia...

Страница 6: ... lowered then a spacer bar can be used to lower the lock from the frame Available in several different heights For use with doors that do not permit the armature plate to be mounted low enough to meet the magnet surface Eg Some aluminum framed commercial glass doors The armature holder can be mounted to whatever frame is available and the armature plate in turn mounted to the holder Available in b...

Страница 7: ...00 18 16 14 12 12 12 10 400 18 14 12 12 10 10 500 16 14 12 10 10 750 14 12 10 10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart c...

Страница 8: ...A 23453 CANADA 210 SHEARSON CRESCENT CAMBRIDGE ON N1T 1J6 PHONE 1 800 265 6630 519 621 7651 FAX 1 800 482 9795 519 621 7939 E MAIL SALES RUTHERFORDCONTROLS COM 8310 IQ 8320 IQ 8330 IQ 8340 IQ Electromagnetic Lock Installation Instructions Continued Maintenance Schedule COMPANY NAME DOOR LOCATION DATE NOTES INITIAL ...

Отзывы: