EW8310 Early Warning Electromagnetic Lock
Installation Instructions
(Continued)
3
Specifications
LISTING Auxiliary Lock.
This product has been successfully tested and evaluated by
UL for use in both the United States and Canada.
Our GWXT fire listing qualifies the EW8310 series as an
“Auxiliary Lock” for use with UL Classified fire doors
maximum 4’ in width and 8’ in height, rated up to and
including 1-1/2 hr with the “Positive Pressure Fire Test of
Door Assemblies”, ANSI/UL 10C.
Patents: US 8,292,337 and Canada 2,632,243
MECHANICAL:
EW8310 Lock Dimensions
Including 1/4” (6.4mm) mounting bracket:
2-1/8”D x 2-7/8”H x 10-13/16”L (54mm x 73mm x 275mm)
EW8310 Armature Plate Dimensions:
5/8”D x 2-3/8”H x 7-7/16”L (16mm x 61mm x 190mm)
ELECTRICAL:
Auto Sensing Voltage: 12VDC to 24VDC
Power Consumption: 12VDC - Max 0.58A
24VDC - Max 0.29A
Local Alarm Output: SPDT 1.0A 120VAC, 2A 30VDC
Remote Alarm Output: DPDT: 1.0A 120VAC, 2A 30VDC
ENVIRONMENTAL:
Not for use in outdoor environments.
Circuit board operating temperature: 14 to 140˚F (-10 to
60˚C)
NOTE: The EW8310 electromagnetic lock must be powered
with a filtered and regulated DC power supply rated 12 to
24V. RCI recommends our 10 Series Power Supplies and
full line of switching devices.
The magnet warranty is 10 years.
Specifications subject to change without notice.
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKS FOR CANADA AND THE U.S.
These Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the
UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which is
Helvetica Condensed Medium. No other fonts are acceptable.
Please Note:
The word "MARINE" should only be used for UL Classified marine products.
200-195F 20M/11/97
To Ensure Instant Release All switching devices must be wired in
between the DC power source and the positive terminal of the lock
as illustrated in Fig 2.
Switching the negative power supply line will not allow the lock to
release immediately. RCI electromagnetic locks contain MOV’s for
surge suppression and do not require any additional suppression
to be added during installation. The installation of diodes across the
lock input terminals will cause a delay in release.
Fig. 2 – Power Connections
SWITCH
+
-
INCORRECT
CORRECT
+
-
SWITCH
FILTERED DC SUPPLY
FILTERED DC SUPPLY
Low Voltage Detection
Each circuit board includes a low voltage detection circuit that is
enabled when shipped from the factory. This feature will cause
the Local Alarm relay and status LED to activate and the Remote
Alarm relay to de-energize should the lock input voltage drop below
9.0VDC. That signals a monitored system or guard station that the
holding force of the lock may have been compromised.