66
Figure 11-11 - Stainless steel
air intake/vent connection
A = MOMENTIVE - RTV 106
high temperature silicone (or
equivalent) (Field provided)
B = Flue exhaust connection
F = Mechanically secure clamp
G = Stainless steel exhaust pipe
(Field provided)
H = Combustion analization
probe (Field installed)
L = Cap (Field provided)
N = Stainless steel air inlet pipe
(Field provided)
P = Air intake connection
R = Stainless steel adapter
(Field provided)
A
B
F
P
R
F
H
R
G
A
L
N
A
B
F
P
R
F
H
R
G
A
L
N
020010.01.038
Combustion
air intake
Flue
exhaust
Figure 11-12 - Stainless steel
air intake/vent connection
correctly in place
Extend the
flue exhaust
pipe to
outside
building
020010.01.016
Extend the
air intake
pipe to
outside
building
11 - INSTALLATION - CATEGORY IV: Vent and combustion air
b. Apply a liberal even coat of
MOMENTIVE - RTV 106
high temperature silicone (or
equivalent) to the adapter “R”
approximately 2” beyond the
socket depth;
c. While the MOMENTIVE - RTV
106 high temperature silicone is
still wet, insert the adapter “R”
into the appliance connection “B”.
NOTICE!
If voids are present,
sufficient MOMENTIVE - RTV 106
was not applied and joint could be
defective;
d. Tight the clamp to mechanically
secure the joint.
2.- Insert vent pipe “G”, into adapter
“R”, following instruction of
stainless steel pipe manufacturer.
11.7.2 - Stainless steel
vent connection
Vent connection (Figure 11-
11 item “C”)
is used to provide
a passageway for conveying
combustion gases to the outside. Vent
piping must be supported per the
National Building Code, Section 305,
Table 305.4 or as local codes dictate.
To connect a stainless steel pipe
to the vent connection proceed as
follows while referring to Figure 11-11:
1.- Dry fit adapter “R” to ensure proper
fit up before assembling adapter to
the appliance connection “B”. The
adapter “R” should go completely
into the appliance adapter to ensure
proper sealing after sealant is
applied;
a. Handle adapters “R” and
appliance connection “B” carefully
to prevent contamination of
surfaces;
020010.01.039
CAUTION!!!
Apply a liberal
even coat of MOMENTIVE -
RTV 106 high temperature
silicone (or equivalent) to the
internal side of the appliance
adapter (item “B” and “P”
fig.11-11)
Содержание Infinite Energy2 IW199
Страница 3: ...3 SAFETY INSTRUCTIONS...
Страница 5: ...5 SAFETY INSTRUCTIONS...
Страница 122: ...122 16 MAINTENANCE...
Страница 126: ...126 18 SPARE PARTS Spare parts...
Страница 154: ...154 21 SEQUENCE OF OPERATION...