31
P/N HN-IOM-1 82-0331 Copyright 2009 Mestek, Inc.
Finned copper tube gas boilers & water heaters – Control manual
Table 7
SETUP
menus
(continued)
(
see Table 9, page 35 for explanations
)
Level 1
next item
to select
Level 2
next item
to select
back one level
Level 3
next item
to select
back one level
Default {Range}
to change value
to accept value and return to previous menu level
Typical line
(Display shows four lines at a
time; cursor indicates active
line)
PUMP OPTIONS
SYSTEM PUMP
POST PRG TIME
2 minutes {1 to 60 minutes}
POST PRG TIME 2M
ALWAYS ENABLED OFF
SUMMER PUMP JOG:OFF
OVR ENAB IN WWS:OFF
ALWAYS ENABLED
OFF {ON or OFF}
SUMMER PUMP JOG:
OFF {Day of week, MON , TUE, etc.}
OVR ENAB IN WWS
OFF {ON or OFF}
LOCAL PUMP
DELTA TEMP ENAB
OFF {ON or OFF}
DELTA TEMP ENAB OFF
DELTA TEMP 10°
POST PRG TIME 2M
ALWAYS ENABLED OFF
DELTA TEMP
10°F {0 to 50°F}
POST PRGE TIME
2 minutes {1 to 60 minutes}
ALWAYS ENABLED
OFF {ON or OFF}
PUMP/VALVE OPTION
MASTER PUMP/VALVE
REMAINS ON:
OFF {ON or OFF}
MASTER PUMP/VALVE
REMAINS ON: OFF
FLOW PROVE:
10 seconds {10 to 240 seconds)
FLOW PROVE: 10S
NIGHT SETBACK
SETBACK ENTRY
1 {1 through 4}
SETBACK ENTRY 1
ENTRY IS OFF
SETBACK 20°F
SETBACK TIME
ENTRY IS
OFF {ON of OFF}
SETBACK
20 °F {0 to 50°F}
SETBACK TIME
START DAY
MON {SUN, MON, TUE, WED, THU, FRI, SAT}
START DAY MON
TIME 10:00 PM
END DAY FRI
TIME 9:00 PM
TIME
12:00 AM {Time, AM or PM}
END DAY
MON {SUN, MON, TUE, WED, THU, FRI, SAT}
TIME
12:00 AM {Time, AM or PM}
OPTIONS
TEMP SCALE
°F {°F or °C}
TEMP SCALE °F
KEY CLICK ON
SKIP PASSW ON
BRIGHTNESS 50%
KEY CLICK
ON {ON or OFF}
SKIP PASSWORD
ON {ON or OFF}
BRIGHTNESS
50% {12, 25, 37, 50, 62, 75, 87, 100%}
LOG/RUNTIME
RUN HOURS
Total time gas valve has been open
RUN HOURS 1240
DATA LOG ENTRY 327
SIZE 1000
BOILER CYCLES 5021
DATA LOG ENTRY
Current entry in the log (see Table 9, page 35)
SIZE
The size of the data log
BOILER CYCLES
Number of times gas valve has been cycled on/off
Control menus and adjustments
(continued)