FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS

K =

Clearance to a mechanical air 

supply inlet

6 ft (1.83 m)

3 ft (91 cm) above if within 10 ft (3 m) 

horizontally

L =

Clearance above paved sidewalk 

or paved driveway located on 

public property

7 ft (2.13 m)†

M =

Clearance under veranda, porch, 

deck, or balcony

12 in (30 cm)‡

 

‡ 

A  vent  shall  not  terminate  directly  above  a  sidewalk  or  paved  driveway  that  is  located  between  two  single  family 
dwellings and serves both dwellings.

NOTES:

1)

In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

2)

In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

3)

If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearances must prevail.

Torus Stainless Steel Condensing Boilers & Water Heaters – Installation Manual

Per local installation codes

Canadian Installations¹

US Installations²

A =

Clearance above grade, veranda, porch, 

deck, or balcony

12 in (30 cm)

12 in (30 cm)

B =

Clearance to window or door that may 

be opened

6 in (15 cm) for appliances < 10,000 

Btuh (3 kW); 12 in (30 cm) for appliances

> 10,000 Btuh (3 kW) and < 100,000

Btuh (30 kW); 36 in (91 cm) for

appliances > 100,000 Btuh (30 kW)

4 ft (1.2 m) below or to side of opening; 

1 ft (300 mm) above opening

C =

Clearance to permanently closed 

window

D =

Vertical clearance to ventilated soffit 

located above the terminal within a 

horizontal distance of 2 ft (61 cm) 

from the center line of the terminal

E =

Clearance to unventilated soffit

F =

Clearance to outside corner

G =

Clearance to inside corner

H =

Clearance to each side of center line 

extended above meter/regulator 

assembly

I =

Clearance to service regulator vent 

outlet

3 ft (91 cm) 

Per local installation codes

Figure 

A

 - 

Other Than Direct Vent Terminal Clearances

Figure 

A

 - 

Direct Vent Terminal Clearances - Concluded

J =

Clearance to nonmechanical air supply 

inlet to building or the combustion air 

inlet to any other appliance

6 in (15 cm) for appliances < 10,000 

Btuh (3kW); 12 in (30 cm) for appliances

> 10,000 Btuh (3 kW) and < 100,000

Btuh (30 kW); 36 in (91 cm) for

appliances > 100,000 Btuh (30 kW)

4 ft (1.2 m) below or to side of opening; 

1 ft (300 mm) above opening

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

Vents for Category II and IV appliances 

cannot be located above public walkways 

or other areas where condensate or vapor 

can cause a nuisance or hazard  

3 ft (91 cm) within a height of 15 ft (4.6m)

Содержание FUTERA II 1000

Страница 1: ...uction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be op...

Страница 2: ...as Fired Low Pressure Steam and Hot Water Boilers ANSI Z21 56 CSA 4 7 Gas Fired Pool Heaters Canada Only Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160...

Страница 3: ...er heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater...

Страница 4: ...st be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized p...

Страница 5: ...the horizontal combustion air pipe on installations that used the Direct Vent option is 60 ft 18 3 m The maximum equivalent length for the horizontal combustion air pipe on installations that use the...

Страница 6: ...61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter re...

Страница 7: ...3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertical clearance...

Страница 8: ...or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z...

Страница 9: ...meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air in...

Страница 10: ...10 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 1 Air Intake Vertical or Thru Wall Figure 2 Venting Thru Wall Vertical...

Страница 11: ...gle or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wal...

Страница 12: ...AND OPERATION INSTRUCTIONS Figure 5 Vertical Air Intake and Venting for Direct Vent System Figure 6 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Страница 13: ...venter for the boiler water heater see Table 4 Follow the power venter manufacturer s installation instructions Table 4 Power Venter Sizes VERTICAL CHIMNEY VENT NEGATIVE PRESSURE CATEGORY I The Futer...

Страница 14: ...ingle wall vent connection with at least 3 corrosion resistant sheet metal screws Always provide a minimum clearance of 6 in 152 mm between single wall vent pipe and any combustible materials Type B1...

Страница 15: ...15 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 8 Vertical Venting with a Metal Chimney System...

Страница 16: ...r window or gravity air inlet into any building and at least 3 ft 1 m from any overhang unless local codes dictate differently Avoid locations where wind deflection off of adjacent walls buildings or...

Страница 17: ...marche Suivre les instructions d allumage R gler le thermostat de fa on que l appareil fonctionne de fa on continue e Test for spillage at the draft hood relief opening after 5 minutes of main burner...

Страница 18: ...water mix that prevents foaming Air entrapped within foam significantly decreases heat transfer and can result in damage to the heat exchanger Products such as DOWFROST DOWTHERM UCARTHERM or an equiva...

Страница 19: ...4 C The adjustable pump delay turns the pump on each time the burner fires and runs the pump for 6 to 600 seconds after the call for heat is satisfied CAUTION A temperature rise outside of the range...

Страница 20: ...econdary systems In order to prevent boiler s short cycling the system flow must be equal to or higher than the boiler s local flow Low Return Water Temperatures To prevent the problems associated wit...

Отзывы: