RBI FUTERA II 1000 Скачать руководство пользователя страница 20

20

FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS

Low Water Cutoff

If a boiler is installed above any radiation elements it must 
be fitted with a low water cutoff device. 

Refer to the wiring diagram supplied with the boiler/water 
heater for proper wiring connections.

Expansion Tank & Air Separator

 

An expansion tank or other means to control thermal 
expansion must be installed in the heating system. An 
expansion tank must be installed close to the boiler on the 
suction side of the pump. An air scoop and automatic air 
vent must also be installed to eliminate air trapped in the 
system.

Primary/Secondary Piping

 

Boilers connected to heating systems using zone valves, 
zone pumps, or systems that have excessive flow rates or 
return water temperatures less than 

125°F,

 52°C must be 

isolated from these systems to protect the boiler. Figure 
13, shows a typical primary/secondary piping system. A 
dedicated pump is used to maintain a constant water flow 
through the boiler. This boiler pump is sized to overcome 
the head loss of the boiler and near-boiler piping system 
while supplying the flow rate required to maintain the 
desired temperature rise across the boiler heat exchanger. 
The system pump is sized to provide the required flow 
to the heating system. The boiler piping connections to 
the heating system piping must be a maximum 10X pipe 
diameters between centers to ensure zero pressure drop 
in the primary system. Flow must be properly accounted 
for in the design of primary/secondary systems. In order 
to prevent boiler(s) short cycling the system flow must be 
equal to or higher than the boiler(s) local flow.

Low Return Water Temperatures

 

To prevent the problems associated with condensation 
of the products of combustion due to low return water 
temperatures a primary/secondary piping system with a 
bypass and bypass valve must be installed, see Figure 
14 and 14A. The bypass and bypass valve must be sized 
the same as the secondary piping. A balancing valve must 
also be installed in the supply side of the secondary piping 
downstream of the bypass. The balancing valve should be 
adjusted to divert some of the heated discharge water into 
the return water until the required inlet water temperature 
is achieved. The primary and secondary pumps should be 
sized to provide the required flow through each system. 
The secondary piping connections to the primary system 
piping must not be more than 10X pipe diameters apart 
to ensure zero pressure drop in the primary system, see 
Figure 14.

Multiple Boiler Systems

Systems using multiple boilers can also be installed using 
a primary/secondary manifold system, Figure 15. 

Piping For Use With Cooling Units

The boiler, when used in connection with a refrigeration 
system, must be installed so the chilled medium is piped in
parallel with the boiler. Appropriate valves must be used to
prevent the chilled water from entering the boiler.

When a boiler is connected to a heating coil that may be 
exposed to refrigerated air from an air handling device, the
piping system must be equipped with flow-control valves 
or some other automatic means of preventing gravity 
circulation of the boiler water during the cooling cycle.

Содержание FUTERA II 1000

Страница 1: ...uction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be op...

Страница 2: ...as Fired Low Pressure Steam and Hot Water Boilers ANSI Z21 56 CSA 4 7 Gas Fired Pool Heaters Canada Only Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160...

Страница 3: ...er heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater...

Страница 4: ...st be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized p...

Страница 5: ...the horizontal combustion air pipe on installations that used the Direct Vent option is 60 ft 18 3 m The maximum equivalent length for the horizontal combustion air pipe on installations that use the...

Страница 6: ...61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter re...

Страница 7: ...3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertical clearance...

Страница 8: ...or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z...

Страница 9: ...meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air in...

Страница 10: ...10 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 1 Air Intake Vertical or Thru Wall Figure 2 Venting Thru Wall Vertical...

Страница 11: ...gle or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wal...

Страница 12: ...AND OPERATION INSTRUCTIONS Figure 5 Vertical Air Intake and Venting for Direct Vent System Figure 6 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Страница 13: ...venter for the boiler water heater see Table 4 Follow the power venter manufacturer s installation instructions Table 4 Power Venter Sizes VERTICAL CHIMNEY VENT NEGATIVE PRESSURE CATEGORY I The Futer...

Страница 14: ...ingle wall vent connection with at least 3 corrosion resistant sheet metal screws Always provide a minimum clearance of 6 in 152 mm between single wall vent pipe and any combustible materials Type B1...

Страница 15: ...15 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 8 Vertical Venting with a Metal Chimney System...

Страница 16: ...r window or gravity air inlet into any building and at least 3 ft 1 m from any overhang unless local codes dictate differently Avoid locations where wind deflection off of adjacent walls buildings or...

Страница 17: ...marche Suivre les instructions d allumage R gler le thermostat de fa on que l appareil fonctionne de fa on continue e Test for spillage at the draft hood relief opening after 5 minutes of main burner...

Страница 18: ...water mix that prevents foaming Air entrapped within foam significantly decreases heat transfer and can result in damage to the heat exchanger Products such as DOWFROST DOWTHERM UCARTHERM or an equiva...

Страница 19: ...4 C The adjustable pump delay turns the pump on each time the burner fires and runs the pump for 6 to 600 seconds after the call for heat is satisfied CAUTION A temperature rise outside of the range...

Страница 20: ...econdary systems In order to prevent boiler s short cycling the system flow must be equal to or higher than the boiler s local flow Low Return Water Temperatures To prevent the problems associated wit...

Отзывы: