background image

SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 7

Flow Switch

The flow switch supplied with the boiler/water heater
must be wired to the terminal strip in the junction box
to prevent the boiler from firing unless there’s adequate
water flow through the unit. The flow switch must be
installed in the supply piping adjacent to the boiler outlet
connection.

CAUTION: Failure to properly install the flow switch
may result in damage to the boiler/water heater heat
exchanger voiding the warranty!

HEATING SYSTEM PIPING

General Piping Requirements

All heating system piping must be installed by a qualified
technician in accordance with the latest revision of the
ANSI/ASME Boiler and Pressure Vessel Code, Section
IV, and ANSI/ASME CSD-1, Standard for Controls and
Safety Devices for Automatically Fired Boilers. All
applicable local codes and ordinances must also be
followed. A minimum clearance of 1" must be maintained
between heating system pipes and all combustible
construction. All heating system piping must be
supported by suitable hangers not the boiler. The
thermal expansion of the system must be considered
when supporting the system. A minimum system
pressure of 12 psig must be maintained.

Heating Boiler Piping Connections

The supply and return connections should be sized to
suit the system, see Table 4.

Table 4 - Supply & Return Pipe Sizing

Boiler Model

Supply Size (in)

Return Size (in)

8900

2

1

/

2

" NPT

2

1

/

2

" NPT

8800

3" Victaulic

3" Victaulic

*Models 420-950 may have 2

1

/

2

” x 2” reducing fitting

installed.

Pump Requirements

This low mass boiler requires a continuous minimum
water flow for proper operation. The system pump must
be sized to overcome the head loss of the boiler and
the heating system in order to achieve the required
temperature rise. Table 5 provides the heat exchanger
pressure drop and temperature rise figures. 

The

temperature rise across the boiler must never
exceed 30°F (17°C).

 The pump should be wired to run

continuously unless the optional pump delay is installed.
The pump delay turns the pump on each time the
burners fire and runs the pump for 100 seconds after
the call for heat is satisfied.

CAUTION: A temperature rise outside of the range
listed in Table 5 indicates that the flow rate through
the heat exchanger is incorrect which will damage
the heat exchanger voiding the warranty! The
maximum allowable flow rate through an 8900 boiler
is 100 GPM, 200 GPM for an 8800. If higher flow rates
are required the optional Cupro-Nickel heat
exchanger should be considered.

Low Water Cutoff

If a boiler is installed above any radiation elements it
must be fitted with a low water cutoff device.

Expansion Tank

An expansion tank or other means to control thermal
expansion must be installed in the heating system. An
expansion tank must be installed close to the boiler on
the suction side of the pump.

Primary/Secondary Piping

Boilers connected to heating systems using zone valves,
zone pumps, or systems that have excessive flow rates
or return water temperatures less than 110 °F (43°C)
must be isolated from these systems to protect the
boiler.

Variable Water Flows

Figure 1 shows a typical primary/secondary piping
system. A dedicated pump is used to maintain a
constant water flow through the boiler. This secondary
pump is sized to overcome the head loss of the boiler
and secondary piping system while supplying the flow
rate required to maintain the desired temperature rise
across the boiler. The primary pump is sized to provide
the required flow to the heating system. The secondary
piping connections to the primary system piping must
not be more than 12" apart to ensure zero pressure drop
in the primary system, see Figure 1.

Low Return Water Temperatures

To prevent the problems associated with condensation
of the products of combustion due to low return water
temperatures a primary/secondary piping system with
a bypass and bypass valve must be installed, see Figure
2. The bypass and bypass valve must be sized the same
as the secondary piping. A balancing valve must also
be installed in the supply side of the secondary piping
downstream of the bypass. The balancing valve should
be adjusted to divert some of the heated discharge
water into the return water until the required inlet water
temperature is achieved. The primary and secondary
pumps should be sized to provide the required flow
through each system. The secondary piping connections
to the primary system piping must not be more than 12"
apart to ensure zero pressure drop in the primary
system, see Figure 2.

Содержание 8800 Series

Страница 1: ...roperty damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try...

Страница 2: ...le efficient operation and long life for which this heating boiler water heater was designed these instructions must be read understood and followed The Series 8800 and 8900 finned copper heating boil...

Страница 3: ...mply with this warning may result in a fire causing extensive property damage severe personal injury or death 4 Locate the boiler water heater in an area that will prevent water damage to adjacent con...

Страница 4: ...re communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 in2 2000 Btu hr 1100 mm2 kW of the total input rating of all of the equipment in the enclos...

Страница 5: ...ollar Failure to comply with this warning can result in severe personal injury or death Always provide a minimum clearance of 6 inches 152 mm between type C vent pipe and any combustible materials Typ...

Страница 6: ...e fa or ad quate Remettre les portes et les fen tres les ventilateurs les registres de chemin es et les appareils au gaz leur position originale g Any improper operation of the common venting system s...

Страница 7: ...outside of the range listed in Table 5 indicates that the flow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty The maximum allowable flow rate th...

Страница 8: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 8 Figure 1 Typical Primary Secondary Piping System Figure 2 Low Temperature Piping...

Страница 9: ...8 3 42 4 59 9 34 3 40 8 47 6 54 4 61 6 68 1 75 2 81 7 88 8 95 2 102 4 109 2 116 0 123 1 131 2 157 4 183 6 209 9 236 1 2 2 2 6 3 0 3 4 3 9 4 3 4 7 5 2 5 6 6 0 6 5 6 9 7 3 7 9 8 3 9 9 11 6 13 2 14 9 0 6...

Страница 10: ...ed with bronze headers Piping and components connected to the water heater must be suitable for use with potable water The water heater must not be connected to any heating system piping or components...

Страница 11: ...er heater inlet must not be less than 110 F 43 C or excessive condensation of the products of combustion will damage the water heater voiding the warranty The method outlined below can be employed to...

Страница 12: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 12 Figure 5 Typical Water Heating Piping Figure 6 Multiple Water Heating Piping...

Страница 13: ...0 1100 2100 3300 5900 12 000 40 245 500 760 1450 2300 4100 8300 50 215 440 670 1270 2000 3600 7400 60 195 400 610 1150 1850 3250 6800 80 170 350 530 990 1600 2800 5800 100 150 305 460 870 1400 2500 51...

Страница 14: ...rol valve to the appliance Do Not interrupt water flow through the boiler water heater En cas de surchauffe ou si l alimentation en gaz ne s arr te pas fermez manuellement le robinet d arr t de l admi...

Страница 15: ...6 Wait five 5 minutes to clear out any gas Then small for gas including near the floor If you smell gas STOP Follow B in the safety infomration above If you don t smell gas go to next step 7 Connect...

Страница 16: ...ing probe Figure 8 To adjust the pilot the following steps must be taken 1 Remove the pilot gas pressure regulator cap 2 Turn the pressure regulator adjustment screw clock wise to increase the flame a...

Страница 17: ...ticipator setting may be necessary if the unit cycles frequently If the room temperature over shoots the thermostat setting reduce the anticipator setting Water Heater Operation Controls The operating...

Страница 18: ...Exchanger Replacement 1 Sagging or distorted heat exchanger tubes are an indication of low water flow through the system 2 A damaged heat exchanger must be replaced and the condition that caused the d...

Страница 19: ...rn Header 8 Black O Rings 9 Stud Bolts 10 Flange Nuts 11 V Baffle 12 Frame Assembly 13 Main Burner 14 Union 15 Firing Valve 16 Main Gas Valve 17 A Valve 18 Refractory 19 Flue Collector End 20 Down Dra...

Страница 20: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 Lower Left Right Jacket End Pnl 72 0016 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 Inlet Outlet Header Cast Iron 01 0001 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Inlet Outlet Header Bronze 01...

Страница 21: ...17 19 21 23 25 27 29 31 33 35 Burner Tube Stainless w Bracket 70 0500 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 14 Union 1 53 0054 1 1 1 1 1 1 Union 1 1 4 53 0055 1 1 1 1 1 1 1 Union 1 1 2 53 0056 1 1 15 Firing...

Страница 22: ...70 1 70 0371 1 70 0372 1 70 0373 1 70 0374 1 70 0375 1 70 0376 1 70 0377 1 Upper Front Refractory Channel 70 0177 1 70 0178 1 70 0179 1 70 0180 1 70 0181 1 70 0182 1 70 0183 1 70 0184 1 70 0185 1 70 0...

Страница 23: ...1 70 0035 1 70 0036 1 70 0037 1 70 0038 1 70 0039 1 70 0040 1 70 0041 1 70 0042 1 70 0043 1 70 0044 1 22 Upper Front Jacket Panel 72 0001 1 72 0002 1 72 0003 1 72 0004 1 72 0005 1 72 0006 1 72 0007 1...

Страница 24: ...07 1 72 0008 1 72 0009 1 72 0010 1 72 0011 1 72 0012 1 72 0013 1 72 0014 1 72 0015 1 29 Burner Drawer Side Rail Assy Left 70 0361 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Burner Drawer Side Rail Assy Right 70 03...

Страница 25: ...Operator L4008A US only 14 0102 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Operator GIP 9868 CAN only 14 0116 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Operator L6008A 1242 Water Heaters 14 0106 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1...

Страница 26: ...1 0154 1 21 0155 1 21 0156 1 21 0157 1 21 0158 1 21 0159 1 21 0160 1 Not Shown Natural to LP Conversion Kit 21 0161 1 2000 to 4500 feet 21 0162 1 21 0163 1 21 0164 1 21 0165 1 21 0166 1 21 0167 1 21 0...

Страница 27: ...rn Header 8 Copper Fin Tube 9 Black O Rings 10 Stud Bolts 11 Flange Nuts 12 V Baffle 13 Frame Assembly 14 Main Burner 15 Union 16 Firing Valve 17 Main Gas Valve 18 A Valve 19 Burner Drawer Side 20 Ref...

Страница 28: ...0001 32 32 32 32 32 32 10 Stud Inlet Outlet Return Headers 57 0223 24 24 24 24 24 24 11 Nut Inlet Outlet Return Headers 57 0491 24 24 24 24 24 24 12 Heat Exchanger V Baffle 03 1147 15 03 1148 15 03 11...

Страница 29: ...nd Refractory Panel Left Right 05 0050 2 2 2 2 2 2 Not Shown Center Refractory Panel 05 0051 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4 05 0057 4 21 Draf...

Страница 30: ...1 1 1 Operator L6008G1009 2 Stage 14 0107 1 1 1 1 1 Operator T991E 1018 Modulating Boilers 14 0108 1 1 1 1 1 Operator T991E 1034 Modulating Water Heaters 14 0110 1 1 1 1 1 Operator T6031A 1052 Pool H...

Страница 31: ...re between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace S8610 module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused by high or...

Страница 32: ...eup valve is open and functioning Remove return header and inspect the heat exchanger tubes Ensure relief valve is properly sized for the system never exceed 160 psi Ensure expansion tank is properly...

Отзывы: