UNC100 Hardware Manual V1.4
RBH Access Technologies Inc.
Page
14
of
36
Master Controller
Each network must have a single unit designated as the master controller. The master controller connects
to the PC. Setting the DIP switch address to 1 will automatically designate a unit as the master controller.
Slave Controller
All controllers addressed 2 through 15 are referred to as slave controllers.
Ethernet Secure Mode
When dip-switch 5 is ON the IP locator program cannot locate the unit on the Ethernet and therefore cannot
make any changes or reset the unit.
RS485 (HOST) Port Baud Rate Selection (Master Only)
The controller's serial port baud rate is set with controller DIP switches 6 and 7. This setting determines
the speed used to communicate with the PC; the controller baud rate must be the same as the baud rate set
for the port within the Axiom™ software. The default baud rate is 9600.
Controller Baud Rate Selection
DIP Switch 6
DIP Switch 7 Baud Rate
OFF
OFF
9600
ON
OFF
38400
OFF
ON
57600
ON
ON
115200