UNC100 Hardware Manual V1.4
RBH Access Technologies Inc.
Page
13
of
36
DIP Switch Settings
The UNC100 DIP switch controls the device’s address and serial port baud rate.
To Clear Panel memory
–
All DIP switches must be off and the unit powered off and on.
DIP Switch
DIP Switch
Function
1 - 4
Controller Address
5
Ethernet Secure Mode
1
6,7
Controller Baud Rate
8
Not used
Controller Addressing
Use DIP switches 1, 2, 3, and 4 to select the controller address. The address is binary coded and the
switch settings for all fifteen possible addresses are given below.
Controller Addressing
Switch 1
Switch 2
Switch 3
Switch 4
Address
On
Off
Off
Off
1 (Master)
Off
On
Off
Off
2 (Slave)
On
On
Off
Off
3 (Slave)
Off
Off
On
Off
4 (Slave)
On
Off
On
Off
5 (Slave)
Off
On
On
Off
6 (Slave)
On
On
On
Off
7 (Slave)
Off
Off
Off
On
8 (Slave)
On
Off
Off
On
9 (Slave)
Off
On
Off
On
10 (Slave)
On
On
Off
On
11 (Slave)
Off
Off
On
On
12 (Slave)
On
Off
On
On
13 (Slave)
Off
On
On
On
14 (Slave)
On
On
On
On
15 (Slave)
1
DIP switch 5 up will enables Ethernet Secure Mode. This will prevent access to the panel’s programming through
the Ethernet.