Point Number
Point numbers are translated into panel IDs and input IDs through a fixed table.
Each point can be programmed as either an input or an output. Event messages
will only be sent for those panels whose addresses are within the parameters
defined by the address DIP-switches.
P
a
n
e
l
A
d
d
r
e
s
s
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20
1
1
17 33 49 65 81 97 113 129 145 161 177 193 209 225 241
2
2
18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
3
3
19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
P
4
4
20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
O
5
5
21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
I
6
6
22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
N
7
7
23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
T
8
8
24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
9
9
25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
I
10
10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
D
11
11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251
12
12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252
13
13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253
14
14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254
15
15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255
16
16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 256
Examples
1. RBH1561 C/R
= Input #12 on panel address #14 has gone into alarm.
2. RBH1030 C/R
= Input #7 on panel address #11 has restored.
3. OUT1811 C/R
= Output #5 on panel address #16 has turned on.
4. OUT0440 C/R
= Output #12 on panel address #7 has turned off.
Firmware Upgrade
It is anticipated that the protocol will change according to manufacturer
requirements. A method of upgrading firmware for this purpose is available in
the latest version of Axiom software (Service Pack 5 [5.2.14] 5-Apr-07). By
selecting only one of the emulated IOC16s for a device firmware upgrade the
firmware will be overwritten with a selected RBH file.
It takes approximately two minutes for the upgrade to be completed.
Be sure to use the proper firmware file when upgrading a virtual IOC board.
A regular IOC firmware file will not work in a virtual IOC (and vice versa). If
this does happen the only way to correct the situation will be to replace the
firmware chip.