background image

14

Type "B" double-wall or equivalent vent pipe is recom-

mended. However, single-wall metal vent pipe may be

used as specified in the latest edition of the National

Fuel Gas Code

ANSI Z223.1.

Manifolds that connect more than one boiler to a com-

mon chimney must be sized to handle the combined

load. Consult available guides for proper sizing of the

manifold and the chimney. At no time should the area

be less than the area of the largest outlet.

At the time of removal of an existing boiler, the follow-

ing steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances remain-

ing connected to the common venting system are not

in operation.

(a) Seal any unused openings in the common venting

system.

(b) Visually inspect the venting system for proper size

and horizontal pitch and make sure there is no

blockage or restriction, leakage, corrosion and

other deficiencies which could cause an unsafe

condition.

(c) As much as possible, close all building doors and

windows and all doors between the space in which

the appliances remaining connected to the com-

mon venting system are located and other spaces

of the building. Turn on clothes dryers and any

appliance not connected to the common venting

system. Turn on any exhaust fans, such as range

Fig. 15: Common Venting

hoods and bathroom exhausts, so they will oper-

ate at maximum speed. Do not operate a summer

exhaust fan. Close fireplace dampers.

(d) Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust thermostat

so appliance will operate continuously.

(e) Test for spillage at the drafthood relief opening

after 5 minutes of main burner operation. Use the

flame of a match or candle, or smoke from a ciga-

rette, cigar or pipe.

(f) After it has been determined that each appliance

remaining connected to the common venting sys-

tem properly vents when tested as outlined above,

return doors, windows, exhaust fans, fireplace

dampers and any other gas burning appliance to

their previous conditions of use.

(g) Any improper operation of the common venting

system should be corrected so that the installation

conforms with the latest edition of the National

Fuel Gas Code, ANSI Z223.1. When re-sizing any

portion of the common venting system, the com-

mon venting system should be re-sized to

approach the minimum size as determined using

the appropriate tables in Part 11 of the National

Fuel Gas Code, ANSI Z223.1.

For special venting applications that require reduced

vent sizes and through-the-wall venting, the Type D

Induced Draft Assembly can be used. Consult the fac-

tory or your local Raypak representative.

5' MIN

2' MIN

10' OR LESS

2' MIN

VENT CAP

VENT PIPE

DRAFT HOOD

HEATER

Fig. 16: Venting Clearances

Содержание 133-4001

Страница 1: ...pplier s instructions If you cannot reach your gas supplier call the fire department WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Refer to this manual Installation and service must be performed by a qualified installer service agency or the gas supplier FOR YOUR SAFETY Do not store or use gasoline or other flam...

Страница 2: ...on page 19 Multiple Boiler Reverse Return Hook Up diagram on page 20 Low Water Cut Off and High and Low Gas Pressure Switch instructions on page 23 Additions Expanded Operating Controls section on pages 21 23 to cover all modes Manual and Auto Reset High Limit instructions on page 23 Deletions Diaphragm Tank System diagram on page 19 Multi zone Heating Systems diagram on page 20 ...

Страница 3: ...c Ignition 21 Operating Controls 21 Limit Controls 23 ELECTRICAL CONNECTIONS 24 START UP 25 Before Start Up 25 General 25 CONTENTS 3 Filling System Heating Boilers 25 Ethylene Glycol Systems Heating Boilers 25 Initial Start Up Pump And Motor 25 For Models with Automatic Gas Valves 28 After Start Up 28 Standing Pilot Checkout Procedure 28 Intermittent Pilot System Checkout S8600 28 Inspections 29 B...

Страница 4: ... be required to de energize the equipment before servicing CAUTION This heater requires forced water circulation when the burner is operating See minimum and maximum flow rates Severe damage will occur if the heater is operated without proper water flow circulation CAUTION Operation of this heater in low temperature systems requires special piping Harmful internal condensation will occur if the in...

Страница 5: ...odel num ber represent MODEL NUMBER EXAMPLE H 3 0 5 1 4 A Series Model Size Representative of approximate MBTUH input Model 0514 has input of 511 500 BTUH Firing Mode 1 Mechanical Modulation 2 Motorized Modulation 3 2 Stage Firing 4 On Off Firing 5 Low Temperature Mechanical Modulation 9 4 Stage Firing Application H Heating Boiler Boiler rating plate showing model number ...

Страница 6: ...rs are design certified and tested under the latest requirements of the American National Standard ANSI Z21 13 Each boiler has been constructed and pressure tested in accordance with the requirements of Section IV of the American Society of Mechanical Engineers Code and factory fire tested All models are National Board approved Temperature and pressure gauge is standard Model 0133 has a 4 pass hea...

Страница 7: ...be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure When such locations cannot be avoided it is recommended that a suitable drain pan adequately drained be installed under the appliance The pan must not restrict air flow Boiler Model No Base Part No Boiler Model No Base Part No 926 1083 1178 1287 1414 1571 1758 962 1125 1223...

Страница 8: ...under the over hang Roof water drainage must be diverted away from the boilers with the use of gutters The point from where the flue products exit the boiler must be a minimum of four 4 feet below four 4 feet horizontally from or one 1 foot above any door win dow or gravity inlet to a building The top surface of the boiler shall be at least three 3 feet above any forced air inlet or intake ducts l...

Страница 9: ... 3000 962 962 3500 3500 4001 4000 Model Sq Inches Model Sq Inches 133 34 1125 282 182 181 46 1223 306 260 261 66 1336 335 330 331 84 1468 367 400 401 100 1631 408 514 128 1826 457 624 157 2100 525 724 182 2500 625 824 207 3001 750 962 241 3500 875 4001 1000 Table E Minimum Net Free Air from Inside Building Table F Minimum Net Free Air from Outside Building Venting Outdoor Installations Model 133 1...

Страница 10: ...wer switch to boiler 2 Turn heater manual switch located in upper control panel to the OFF position 3 Shut off gas supply and water supply to the boiler 4 Mount drafthood on boiler and attach with the sheet metal screws provided Drafthood should be positioned with the vent sensor located on the front left side see next page 5 Remove plastic plug from left side of boiler jacket and install the plas...

Страница 11: ...heater Make sure the flanged side of the flue opening is up 4 Turn the stack drafthood upside down and set it down bottom side up 5 Turn the jacket top panel removed in step 1 upside down and place it over the stack 6 Attach the three 3 mounting brackets to the stack using the screws provided and the holes that are pre drilled in the stack Make sure the brackets are positioned with the flange near...

Страница 12: ... of boiler as shown in Fig 12 Drafthood should be positioned with the vent sensor located on the front right side as shown 5 Remove plastic plug from left side of boiler jacket and install plastic grommet provided 6 Route flue sensor wire harness through the grom met installed in Step 5 7 Remove door and locate wire from roll out sensor to high limit with the male female connector 8 Disconnect mal...

Страница 13: ...e of insulated vent pipe spacers through the roof and walls For protection against rain or blockage by snow the vent pipe must terminate with a vent cap which com plies with the local codes or in the absence of such codes to the latest edition of the National Fuel Gas Code ANSI Z223 1 The discharge opening must be a minimum of 2 ft ver tically from the roof surface and at least 2 ft higher than an...

Страница 14: ...stem Turn on any exhaust fans such as range Fig 15 Common Venting hoods and bathroom exhausts so they will oper ate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers d Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously e Test for spillage at the drafthood relief opening after 5 minute...

Страница 15: ...energy savings of the vent damper can be improved by plugging the hole in the vent damper blade using the knockout plug Part No 105612R provided in the parts envelope DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazard Fig 17 Vent Damper Installation Model 133 Drafthood Shown WARNING Do not use thermally actuated vent dampers on a modulating...

Страница 16: ...elow 3 Turn the thermostat or controller down again and check that the vent damper position indicator returns to the closed position NOTE The vent damper must be inspected at least once a year by a trained experienced service technician The name of the person who originally installed your vent damper is shown on the installation label Damper must be in open position when boiler main burners are op...

Страница 17: ...ed to the outdoors as required by the National Fuel Gas Code Under NO circumstances shall bleed lines terminate in the gas utilization equipment flue or exhaust system General Boiler should be located so that any water leaks will not cause damage to any adjacent areas or structures See piping diagrams for proper water connections for the type of boiler and system Pump Selection In order to ensure ...

Страница 18: ...heating systems 4 Pass Heat Exchanger BOLD TYPE indicates Low NOx models difference between the inlet and outlet water when the boiler is firing at full rate For some boilers the Delta T is more than 20 F 22 33 F at the recommended flow rates Feedwater Regulator We recommend that a feedwater regulator be installed and set at 12 PSIG minimum pressure Install a check valve or back flow device upstre...

Страница 19: ...LESS THAN 4 STAGE CONTROLLER SENSOR 4 STAGE OR MODULATION 5 MAX 5 MAX Fig 24 Single Boiler Primary Secondary Piping Models 133 4001 Note Expansion tanks supplied by others should be installed per manufacturer s instructions ...

Страница 20: ...X Reverse return piping is a proper method of manifolding multiple boiler hook ups to ensure balanced flow through each boiler Valves on supply and return are needed to isolate any boiler as required Fig 25 Multiple Boiler Reverse Return Hook Up Models 133 4001 ...

Страница 21: ...nnot open until the pilot relights and is proven All units are shipped with lockout ignition module as standard NOTE Pump will come on when power is first applied to boiler Fig 26 Economaster PCB Operating Controls Modes H1 and H5 Mechanical Modulation Models 133 1826 with mechanical modulating controls have one or more Robertshaw Invensys Unitrol 7000 Series hydraulic snap on thermostatic combina...

Страница 22: ...The boiler will fire at low fire when there is closure across the stage 1 contacts Thereafter it will fire at high fire when there is closure across the stage 2 contacts Numerous staged controllers are available Mode H4 On Off Firing The boiler will fire at full fire when there is closure across the TH contacts Numerous mechanical staged controllers are available see fig 37 as well as digital cont...

Страница 23: ...of a pump failure or low water condition It is mounted and wired in series to the main gas valve Standard on all models except the 133 NOTE Flow switch will not operate if flow is less than 12 gpm Fig 33 Flow Switch 100 Pilot Safety All standard boiler models 181 4001 employ electron ic devices which close the main gas valve within 8 10 of a second whenever the pilot flame is interrupted Pilot fla...

Страница 24: ... replaced with 105 C wire or its equivalent CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing DANGER SHOCK HAZARD Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to components Low Water Cut Off Optional The probe type low water c...

Страница 25: ...eme care in light ing boiler in confined areas CAUTION Pump must be off to check oil in bearing assembly Do not run pump without water in system MECHANICAL MODULATING GAS VALVES WITH REGULATOR T P GAUGE NOT SHOWN INLET HI LIMIT Fig 37 General Location of Controls Ethylene Glycol Systems Heating Boilers Fill through filler opening on the top on the Air X Tank to solution desired Always maintain sol...

Страница 26: ...rol knob counter clockwise to ON 11 Replace boiler door panel 12 Turn on all electric power to the appliance 13 Set the thermostat to the desired setting PILOT THERMO BURNER COUPLE A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appli ance area for gas Be sure to smell next to the floor beca...

Страница 27: ... clockwise to ON 9 Replace boiler door panel 10 Turn on all electrical power to the appliance 11 Set thermostat to desired setting 12 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier HONEYWELL GAS CONTROL KNOB SHOWN IN ON POSITION GAS INLET ROBERTSHAW GAS CONTROL KNOB SHOWN IN ON POSITION GAS INLET TO TURN OFF G...

Страница 28: ...e thermocou ple or generator tip 3 Place system in operation and a Check for satisfactory ignition of main burner b Make certain the pilotstat holds in and that shutdown occurs within 2 1 2 minutes after the pilot flame is extinguished c Observe operation for at least three cycles to be sure the system is functioning normally Intermittent Pilot System Checkout S8600 1 Turn on power to the ignition...

Страница 29: ... main burner Observe pilot burner when shutting off pilot gas Ignition spark should go on Main gas valve will also drop out To check high limit switch turn dial setting down to a point slightly below the temperature of the water leav ing the heater The reset button should snap out and the burner should shut off Reset dial to 30 F to 40 F above desired operating temperature and push reset button Bu...

Страница 30: ... boiler will shut down Start Up S8600H 1 Turn on power to the boiler with gas supply off 2 Check ignition module as follows a Set the thermostat or controller to call for heat b Watch for continuous spark at the pilot burner c Check the ignition spark operation Time must be within the lockout timing period 90 sec onds d Turn control down to end call for heat and wait 60 seconds before beginning st...

Страница 31: ...screw 4 screws that secure the control box 8 Disconnect pilot wire from the ignition module 9 Disconnect wire harness from the combustion blower 10 Carefully slide out the burner tray assembly 11 Reverse above procedure to re install Gas Valve Removal 1 Remove burner tray See Burner Tray Removal procedure 2 Disconnect pilot tubing from gas valve 3 Turn vertical gas pipe from manifold slightly and ...

Страница 32: ... slots 8 Reverse above procedure to re install Pilot Removal 1 Disconnect pilot tubing from gas valve 2 Remove 4 screws from control box Open the control box 3 Remove the pilot wire from the ignition wire 4 Remove 2 screws that mount the pilot bracket to the air manifold assembly 5 Pull the pilot bracket slightly then drop and pull downwards and outwards 6 Reverse above procedure to re install Mak...

Страница 33: ...eplace module Check for 24 Vac across MV MV PV terminals If no voltage replace module Check electrical connections between module and gas control If okay replace gas valve or gas control operator i e pilot gas valve flow switch etc NOTE IF S8600H goes into lockout reset system Check continuity of ignition cable and ground wire NOTE If ground is poor or erratic shutdowns may occur occasionally even...

Страница 34: ... B E L P U O C O M R E H T K C E H C V 4 2 R O F K C E H C AT GAS VALVE IF NOT 24 V IF 24 V IF O K IF DEFECTIVE CHECK TRANSFORMER OUPUT REPLACE E C A L P E R E C A L P E R E V L A V S A G V 4 2 R O F GAS VALVE THERMOCOUPLE IF NO IF 24 V 24V REPLACE PROBLEM IN TRANSFORMER LIMIT CIRCUITS Electrical Standing Pilot WARNING HIGH VOLTAGE For qualified technicians ONLY ...

Страница 35: ...35 TYPICAL ON OFF INTERMITTENT IGNITION CONTROL WIRING DIAGRAM ...

Страница 36: ...ON Light pilot Standing pilot models Check the circuit breaker outdoor con troller etc upstream of boiler If power to Leads L1 and L2 of trans former but no power on 24V side re place Jumper thermostat Replace with new if boiler fires If power to toggle switch but not through switch replace If power to relay but not operating replace Open valve Loosen bleed line and clean Replace coupler Inspect b...

Страница 37: ...pid Wear Of Coupling 1 Misalignment or a bent shaft 2 Sagging motor mounts over oiling Pump Loses Prime 1 Air leaks in suction line 2 Excessive amount of air in water 3 Water seal in stuffing box not functioning 4 Excessive suction lift and pump operating too near shut off point Overloaded Driving Unit 1 Head much lower than that for which pump is designed 2 Speed too high or higher than that cont...

Страница 38: ...erally After reaming with the auger mount the wire brush and clean out the debris remain ing in the tubes Another method is to remove the heat exchanger ream tubes and immerse heat exchanger in noninhibited de scale solvent Burner Tray Removal 1 Shut off power and gas supply to the boiler Disconnect union s and pilot tubing then loosen and remove burner hold down screws 2 Disconnect wires at gas v...

Страница 39: ...parts 2 Remove front inspection panel 3 Remove wires to high limit and loosen screws holding high limit to cabinet 4 Remove wedge clip holding sensing bulb in con trol well 5 Remove high limit and install a new one 6 Check control operation before leaving job Heat Exchanger Removal 1 Shut water gas and electricity off close valves and relieve pressure remove relief valve Remove side inspection pan...

Страница 40: ...pection pan els Install top holding screws Install draft diverter and vent piping if so equipped 10 If gas piping was disconnected reconnect gas pip ing system and check for leakage using a soapy solution 11 Check for correct water pressure and water level in the system Make sure that system pump oper ates immediately on the call for heat The system is ready for operation 12 Within two 2 days of s...

Страница 41: ...nd wash heat exchanger mak ing sure soot is removed from between fins Avoid excessive water against refractory 5 Reassemble when boiler is fired some steam will form from wet refractory This is normal 6 Correct reason for soot formation REPLACEMENT PARTS See separate parts sheet in instruction envelope Any part returned for replacement under standard company warranties must be properly tagged with...

Страница 42: ... conditions satisfied The replacement part will be warranted for only the unexpired portion of the original warranty Raypak makes no warranty whatsoever on parts manufactured by others but Raypak will apply any such warranty as may be provided by the parts manufacturers TO MAKE WARRANTY CLAIM Promptly notify the original installer supplying the model and serial numbers of the unit date of installa...

Страница 43: ...43 ...

Страница 44: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...

Отзывы: