4.2.2 Comparison of International Standards
High Winding Side:
Wire Color
ANSI
Wire Color
IEC
Wire Color
Australian
RED
H1
RED
U
RED
A
BLACK
H2
BLACK
V
YELLOW
B
BLUE
H3
BLUE
W
BLUE
C
YELLOW
H0
YELLOW
N
BLACK
N
Low Winding Side:
Wire Color
ANSI
Wire Color
IEC
Wire Color
Australian
RED
X1
RED
u
RED
a
BLACK
X2
BLACK
v
YELLOW
b
BLUE
X3
BLUE
w
BLUE
c
YELLOW
X0
YELLOW
n
BLACK
n
NOTE
This manual refers to the ANSI standards for all examples. To change
the standard in the test instrument please refer to chapter ‘8.5.3
Standards’.
WARNING!
BEFORE OPERATING THIS OR ANY OTHER TEST EQUIPMENT
READ ALL SAFETY WARNINGS AND UNDERSTAND THEM FULLY.
DO NOT VARY INPUT VOLTAGE (MAINS) AFTER POWERING ON
TEST SET.
The TR-MARK III auto-senses the input (mains) voltage 110 or 240
VAC 50 / 60 Hz.
The TR-MARK III then “locks–in” the test voltage range. If the input
voltage (mains) is varied after the TR-MARK III was powered on the
actual test voltage may be higher or lower than indicated and system
may get damaged
90100-2.20 Instruction Manual TR-MARK III 250V
Page 14 of 68