1. Safety instructions

1.

  Read this leaflet carefully before commencing to install the WARRIOR unit and retain it 

for future use. Installation can only be carried out by suitably qualified personnel.

2.

  Check the certification to ensure that the mains supply and the ambient temperature 

present is suitable for the unit being installed.

3.

  If the WARRIOR unit is to be installed in areas of high vibration, please consult Raytec.

4.

  The WARRIOR unit housing is constructed from marine grade aluminium and 

polycarbonate.  The  end  user  must  ensure  that  these  materials  are  suitable  for  the 
atmosphere the WARRIOR unit will be installed in; Zone 1 and Zone 2 Hazardous areas.

5.

  The  incoming  mains  cable  should  not  exceed  a  temperature  rise  of  61˚C  above 

the ambient conditions; select suitable cable and cable gland. You must use ATEX 
approved cable and glands e.g. M25, for advice on suitable glands and cables please 
contact Raytec

Specifications subject to change without notice. 
Installation to be carried out by suitable trained and qualified personnel.

        

!

Isolate mains before 

removing cover

Install in a well 

ventilated area

Do not continually 

stare at lamp

1.5m

Содержание RAYMAX WARRIOR

Страница 1: ...ing Version 4 0 Important information The WARRIOR series of explosion protected illuminators are specialist devices certified for use in specific operating environments The units must be installed in...

Страница 2: ...ine grade aluminium and polycarbonate The end user must ensure that these materials are suitable for the atmosphere the WARRIOR unit will be installed in Zone 1 and Zone 2 Hazardous areas 5 The incomi...

Страница 3: ...ng light conditions 3 The WARRIOR illuminator and the mounting bracket is supplied together as a unit The bolts in the side of the housing shall be removed and used to secure the bracket to the WARRIO...

Страница 4: ...LOW GREEN YELLOW Photocell Black ve Red ve N L E Wire the Mains cable into the terminal block Provision has been made for this and identified as the E Earth Ground L Live and N Neutral terminals There...

Страница 5: ...1 mm of the metal of the terminal throat iii All terminal screws used and unused on the WARRIOR terminal block type Bk IECEx SIR 05 0035U terminal block shall be tightened down to between 0 5 Nm and...

Страница 6: ...y must be replaced contact Raytec for assistance 3 It is essential that all WARRIOR units are maintained in accordance with the requirements of the EN60079 17standard Electrical apparatus for explosiv...

Страница 7: ...correctly wired to terminal block Red to Red Black to Black 2 Ensure Mains input is correctly connected Earth Ground to Yellow Green Live to Brown Neutral to Blue 3 Ensure Mains Input is turned on at...

Страница 8: ...8 UK Europe T 44 0 1670 520055 F 44 0 1670 819760 sales rayteccctv com Americas Toll Free T 1 888 505 8335 ussales rayteccctv com www rayteccctv com WII 11 10 1...

Отзывы: