14
Enable followers from appropriate BOILER menu at the master:
Item
Range
Default
User Settings
When is it
Displayed
Description
BOILER 1, 2, 3, 4
ON <> OFF
OFF
Cascade Followers
present
FT_Bus 1, 2, 3,4
are connected
The following settings are available in the SETUP/ADJUST Menu:
Item
Range
Default
User Settings
When is it Displayed
Description
Target
Reset - Setpoint
EMS
Modbus
SETP
PIM™ Identity is H
EMS = Temp/Rate
Modbus = Temp/Rate
RSET = Outdoor Reset
SETP = Setpoint
EMS = Energy
Management System
(Analog Target
Temperature)
MODB = Modbus
Mode
1 - 2 - 3
1
PIM™ Identity is H
TARGET = Rset or Setp
Piping and application
configuration
SETPOINT
XFYRE 50 TO 192°F
XPAKFT 50 TO 192°F
MVB/XTHERM 50 TO
220°F
180°F
PIM™ Identity is H
Piping and application
configuration
Target Max.
XFYRE 190°F
XPAK FT 190°F
MVB/XTHERM 220°F
192°F
192°F
220°F
Modbus Rate
EMS Rate
PIM™ Identity is H
Maximum Target Boiler
Temperature
Target Min.
50 to 180°F
50°F
Modbus Rate
EMS Rate
PIM™ Identity is H
Minimum Target Boiler
Temperature
Sys. Purge
0:20 to 20:00 min
0:20 min
Modbus
Temp/Rate
PIM™ DIP = Purge On
Sets the length of the
System Pump Purge
Units
F or C
F
Always
Show Units Using Icons
in Display
When RESET from target screen is selected the following items will be available for adjustment:
Out Start
35 to 85°F
70°F
PIM™ Identity is H
Target = Rset
Outdoor Reset Starting
Temperature
Out Design
-60 to 45°F
10°F
PIM™ Identity is H
Target = Rset
Outdoor Reset Design
Temperature
Boil Start
35 to 150°F
70°F
PIM™ Identity is H
Target = Rset
Starting Boiler Target
Temperature when
Outdoor Temperature is
at Outdoor Start
Boil Design
70 to 200°F
180°F
PIM™ Identity is H
Target = Rset
Design Boiler Target
Temperature when the
Outdoor Temperature is
at Outdoor Design
(Hottest Water on
Coldest Day)
WWSD
40 to 100°F
70°F
Target = Rset
PIM™ Identity is H
The System Warm
Weather Shut Down
Temperature
When manual differential is selected via PIM™ DIP switch #1, the following item will appear:
Target Diff
2 to 42°F
10°F
PIM™ Identity is H
PIM™ DIP = Manual Diff
Differential for Target
Boiler Temperature
Содержание VERSA IC
Страница 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual...
Страница 28: ...28 Fig 26 WH Direct DHW single Heater with CWP VS Pump MIX TYPE 2 Fig 25 WH Direct DHW Single Heater...
Страница 78: ...78...
Страница 79: ...79...
Страница 80: ...80 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 9725 Litho in U S A...